Page 31
Figure 4-10
SERI Web Server Add Mapper Entry Page
The Add Mapper Entry page allows the changing or editing of the mapper entries. The Modbus Register is the register in the SERI where the data will be mapped. The Source can be R1 Drop 0 or R1 Drop 255. The Source Address is the starting address of the data. Word Count is the words needed to contain the data. Direction is input, output, input reversed, output reversed.
SERI Manual
4
Web Server 31
Page 32
Change Password Page
Figure 4-11
SERI Web Server Change Password Page
Change Password page allow users to set their own password. Passwords can be up to twenty characters or numbers in length. Passwords are also case sensitive so upper case and lower case characters are different.
32 Web Server
4
SERI Manual
Page 33
Statistics Page
Figure 4-12
SERI Web Server Statistics Page
The Statistics Page shows the statistics about the Module, Backplane, Ethernet, and Serial port. This is a freeze frame look at the statistics. Refresh this screen using the F5 key or the Reload button in the browser to see changing statistics.
SERI Manual
4
Web Server 33
Page 34
Page 35
5 Configuration Software SERISW32
The SERISW32.EXE software program is provided free of charge to SERI users. This software is used to help configure the operation of the SERI.
Data Entry Keys Whenever data entry is allowed by the program, certain keys can be used to facilitate data entry. They are: BACKSPACE
Move cursor left and remove character there
LEFT ARROW
Move cursor to the left one character
RIGHT ARROW
Move cursor to the right one character
DEL
Remove the character under the cursor
INS
Change between insert and overstrike modes of entry
HOME
Move cursor to the left edge of the field
END
Move cursor to the end of the data
Control-F
Move cursor right (Forward) one word
Control-R
Move cursor left (Reverse) one word
Control-D
Delete from the cursor to the end of the field
Control-U
Delete from cursor to the beginning of the field
Control-Y
Delete all characters in the field
ESC
Exit the field without modifying it
ENTER
Accept the contents of the field
When a field is opened for input, the cursor is positioned at the left side of the field. If data is already present in the field, typing any character other than those listed above will cause the field to be blanked allowing entry of new data without first deleting the
SERI Manual
5 Configuration Software SERISW32 35
Page 36
old. If it is desired to retain the previous data for editing, make sure the first key you type is an editing key such as a left or right arrow.
Main Menu The startup screen of SERISW is shown in Figure 5-1. The operational modes are selected by the highlighted menu bar on the fourth line. Selection can be made by moving the cursor to the desired option using the arrow keys and pressing ENTER. A short cut is provided: simply type "N" for oNline, "F" for oFfline, "U" for Utility, "S" for setup or "Q" to quit.
Figure 5-1 Main Menu Screen oNline The oNline selection provides a sub-menu for dynamically editing the parameters in the module. Edit Configuration Upon selection of Edit, SERISW attempts to connect to the SERI using the Setup parameters defined in the Serial Setup menu. For oNline Edit to function properly, all setup parameters must be correct for the equipment used including the connection type, IP Address, Index, baud rate, parity, checksum, etc. For more information on the Serial Setup parameters see page 44. Once SERISW has been able to connect to an SERI, the screen should look something like Figure 5-2. The TX and RX lights over the RS-422 port or Ethernet port will be flashing, and the small line in the upper right corner of the screen should be spinning. While oNline, SERISW is continuously polling the SERI and displaying the parameters on the screen. If any parameters are changed, the effect will be immediate and the module will react according to the change. It is important to realize this, as changes made to parameters such as the mode, parity, baud rate, etc. may result in the loss of communication to the SERI.
36 Configuration Software SERISW32
5
SERI Manual
Page 37
Figure 5-2 oNline Edit
The block cursor is moved about the screen using the arrow keys on the keyboard. Individual parameters may be modified by toggling through the permitted parameters using the -. +, and space bar. Parameters requiring direct value entry, such as the I/O Map table entries, may be edited with the commands listed on page 35. Several Function keys are active while in the online screens and are described below: • F1 Print - The F1 Function key will allow a direct printing of the screen to a printer or ASCII file. A window will open in the middle of the screen prompting for the destination of the print. The target may be a DOS device may be such as "LPT1" etc. or to an ASCII text file by entering a filename. Pressing Escape will abort the print screen. • F9 Serial Setup - The F9 Function key will bring up the Serial Setup window for immediate modification of the setup parameters of SERISW. Pressing Escape will exit from the Setup window without making changes. • F10 Clear Error - When any Error Window appears with a beep, the F10 key may be used to clear that error. The opening screen of the oNline Edit provides the IP Address parameters for the SERI. Near the top of the center of the screen, the firmware revision of the SERI is displayed. The date displayed in the upper right hand corner of the screen is the revision of the SERISW32 software. The Scan Time of the SY/MAX rack is dynamically displayed in the lower right hand corner of the screen along with the IP Address of the current Master. The Disable outputs item allows an immediate disabling of the outputs on the SY/MAX rack. Toggling this value to [X] causes R[1001].2 to be set in the SERI. Setting this value to [ ] causes this bit to be cleared. The Halt/Run item controls the outputs on the SY/MAX rack. Toggling this value to [X] causes R[1001].1 to be set in the SERI. Setting this value to [ ] causes this bit to be cleared.
SERI Manual
5
Configuration Software SERISW32 37
Page 38
The Serial port baud rate is fixed at 9600. The parity is fixed at EVEN. Data bits are fixed at 8 and Stop bits are fixed at 1. The serial protocol is fixed at Dual Slave.
Edit Allowed Master List The SERI may receive commands from up to four Modbus/TCP masters. This table must be set to allow writes from those masters. Any master not configured in this table will be allowed to read the registers in the SERI, but will not be allowed to write the Outputs. Also in this table is the Watchdog timeout for writing the Outputs. Failure to write the Outputs within the specified time will result in the SERI setting the Outputs to the default value. The final configuration in this option is of the rack in which the SERI will reside. Valid options are HRK100, HRK150, HRK200, RRK100, RRK200, or RRK300. The allowed masters list is shown in Figure 5-3.
Figure 5-3 oNline Allowed Masters
Edit Mapper Configuration This option determines how the I/O will be mapped within the SERI. In the first column, the user chooses the first register (1-10000) into which the data for the chosen module will reside. The second column references the slot in the SY/MAX rack (D116 or R1-16). The third column dictates the first register in the chosen module that will be referenced. For most discrete modules, this number must always be 1. In the case of a Niobrara module (SPE4, EPE5, MEB), this number may be as high as 2048. The fourth column references the number of consecutive registers to be used in the module. The fifth column decides whether these registers are to be Inputs or Outputs. The last column displays the default values (displayed in HEX) of any Output registers.
38 Configuration Software SERISW32
5
SERI Manual
Page 39
Figure 5-4
SERI Mapper Editor oFfline The oFfline menu offers several choices for maintenance, storage, and retrieval of SERI configurations. The oFfline menu is shown in Figure 5-5. The oFfline menu items perform their operations using a copy of SERI setup parameters in the personal computer’s memory. This copy may not be related to the actual configuration in an SERI that may be connected oNline. Any changes made in the oFfline Editing that are needed to be transferred to a connected SERI must be done with the Send memory to module menu item.
Figure 5-5
SERI Manual oFfline menu
5
Configuration Software SERISW32 39
Page 40
Read from disk to memory This function reads an SERI configuration from disk into the computer’s memory. The file to be read should have been created by the "Write from memory to disk" function described below and must have a .SRM extension. When "Read from disk to memory" is selected, a window will open and ask for the name of the file to read. The bottom part of the screen will show a list of all files with the extension .SRM in the current directory. Any subdirectories, or drives, will be shown in square brackets. The parent directory (of which the current directory is a subdirectory) is shown by the word "parent" in square brackets. You may either type the name of the file to read or you may use the arrow keys to move the highlight to the desired filename. Pressing ENTER with the highlight on a filename will select that file for reading. Pressing ENTER with the highlight positioned on a directory name (either a subdirectory or [parent]) will change the current directory to that directory and will show the .SRM files in the new directory. If there are more files than will fit on the screen, pressing the right arrow with the highlight at the right edge of the screen will scroll the display sideways to show more files. Typing the ESC key will return to the offline function menu without loading a file. Write from memory to disk This function saves a copy of the memory file to a disk file. "Write from memory to disk" uses the same point and shoot file selection described for "Read from disk to memory" above. To create a new file you must type the name. The name should be a valid MS/DOS filename but should not include any path name or extension. The program will append an extension of .SRM to the name and the file will be placed in the directory which is shown in the bottom half of the screen. To create a file in a directory other than the current one, use the arrow and ENTER keys to traverse the directory tree until a listing of the desired directory is shown in the bottom half of the screen. Then type in the file name and press ENTER. If you specify (either by typing or by pointing) a file that already exists, you will be prompted for approval before that file is overwritten. Edit configuration in memory The Edit selection brings up a screen similar to the oNline Edit screen. Use the editor in the normal fashion to make changes to the memory file. Upon completion of the editing, it is advised that the work be saved using the "Write from memory to disk" routine. Upon exiting the editor, the main SERISW menu will appear. It is important to remember to save the file before exiting or the changes will not be made. edit Allowed master list The Allowed master list is similar to the oNline version of the same screen. Use the editor in the normal fashion to make changes to the memory file. Upon completion of the editing, it is advised that the work be saved using the "Write from memory to disk" routine. Upon exiting the editor, the main SERISW menu will appear. It is important to remember to save the file before exiting or the changes will not be made.
40 Configuration Software SERISW32
5
SERI Manual