Page 11
Electronic Components Remotely Operated Circuit Breakers UL HID Rating All POWERLINK AS circuit breakers have a UL Listed rating for use with high intensity discharge lighting. These lighting systems, which include high pressure sodium, metal halide, and mercury vapor, have inherently high inrush current characteristics, which require circuit breakers rated for such applications. UL Switching Duty Rating POWERLINK QO(B)-AS and EHB-AS circuit breakers are UL Listed for Switching Duty (SWD), making them suitable for switching 120Vac fluorescent lighting loads. This switching duty rating applies only to QO(B)-AS and EHB-AS 15A and 20A circuit breakers in 1-, 2-, and 3-pole versions. Switching Mode Selector Switch On the front of POWERLINK AS circuit breakers is a switching mode selector switch that places the circuit breaker in either AUTO or MANUAL switching mode. When the switching mode selector is in the down position (or AUTO mode) and the circuit breaker operating handle is in the ON position, the circuit breaker contacts may be remotely opened or closed via the internal 24Vdc motor and circuit breaker electronics. If the switching mode selector is in the out position (or MANUAL mode), the remote switching mechanism is disengaged, and the circuit breaker contacts default to the position as indicated by the circuit breaker operating handle. If the switching mode selector is initially in MANUAL mode, then depressed into the AUTO mode, the circuit breaker contacts default to the last state (open or closed) issued by the POWERLINK AS system control module. In the MANUAL mode, all POWERLINK AS circuit breakers are physically disengaged from the remote mechanism, which causes them to disregard signals from the POWERLINK AS system control module and operate the same as standard circuit breakers. When the circuit breaker operating handle is in the OFF or TRIPPED position and the switching mode selector is in either the AUTO or MANUAL mode, the circuit breaker cannot be remotely turned on or reset. When tripped, the circuit breaker must be reset using the circuit breaker operating handle. The following table describes switching conditions of POWERLINK AS circuit breakers.
Table 4 POWERLINK AS Circuit Breaker Switching Conditions CIRCUIT BREAKER INITIAL STATUS Switching Mode Selection Position AUTO or MANUAL AUTO AUTO AUTO AUTO MANUAL MANUAL AUTO or MANUAL
12
Circuit Breaker Handle Position OFF ON ON ON ON ON ON TRIPPED
ACTION
Initial Position of Circuit Breaker Input Command from Controller Contacts ON or OFF OPEN OPEN OPEN CLOSED CLOSED OPEN CLOSED OPEN
OFF ON ON OFF ON or OFF ON or OFF ON or OFF
CIRCUIT BREAKER FINAL STATUS Final Position of Circuit Breaker Contacts OPEN
Resulting Action None
OPEN CLOSED CLOSED OPEN CLOSED CLOSED OPEN
None Load ON None Load OFF Load ON None None
SQUARE D
9/98
Page 12
Electronic Components Remotely Operated Circuit Breakers Remote Circuit Breaker Endurance QO(B)-AS and EHB-AS circuit breakers have an electrical life of 200,000 remote operations (at 80% load and 0.8 power factor). The number of years the circuit breakers yield based on the number of operations per day.
Table 5 Calculated Electrical Endurance (Years) QO(B)-AS and EHB-AS Circuit Breakers Number of Estimated Operations per Day Endurance in Years 18 30 22 25 27 20 37 15 55 10 110 5 548 1 Note: One operation is defined as either from closed to open to closed, or from open to closed to open. Numbers are calculated estimates, based on operating 365 days per year.
Construction Standards for POWERLINK AS Circuit Breakers The POWERLINK AS system uses a remotely operated, thermal-magnetic circuit breaker to provide remote switching and overcurrent protection. For more detailed information on Square D thermal-magnetic circuit breakers, refer to the Distribution Product Catalog Class 601, Thermal-Magnetic/ Magnetic Only Molded Case Circuit Breakers.
SQUARE D
9/98
13
Page 13
Electronic Components Remotely Operated Circuit Breakers SELECTION DATA QO/QOB-AS Plug-on or Bolt-on Remotely Remote Controlled Operated Circuit Breakers - UL Listed
Plug-on Catalog No.
Bolt-on Catalog No.
Three-Pole 240Vac - 10,000 AIR Plug-on Bolt-on Catalog No. Catalog No.
QO115AS ●▲ QO120AS ●▲ QO130AS OQ130 ●
QO215AS ●▲ QO220AS ●▲ OQ230 ● QO230AS
QOB215AS ●▲ QOB220AS ●▲ QOB230AS OQB230 ●
QO315AS ●▲ QO320AS ●▲ OQ330 ● QO330AS
Ampere Rating 15 20 30
Two-Pole 120/240Vac - 10,000 AIR
One-Pole 120/240Vac - 10,000 AIR Plug-on Bolt-on Catalog No. Catalog No.
•
QOB115AS ●▲ QOB120AS ●▲ QOB130AS OQB130 ●
•
•
•
•
Lug Wore ire Size▼
QOB315AS ●▲ (1) #12-8 Al QOB320AS ●▲ (1) or (2) #14-10 Cu OQB330 ● QOB330AS
•
All are UL Listed as HACR type for use with air conditioning, heating, and refrigeration equipment having motor group combinations and marked for use with HACR type circuit breakers. ▲ UL Listed as SWD (switching duty) rated. Suitable for switching 120Vac fluorescent lighting loads. UL Listed for use with high intensity discharge lighting systems. ● HID rated as for HID use rated with high intensity discharge lighting systems. ▼ Suitable for use with 60°C or 75°C conductors.
POWERLINK QO(B)-AS Circuit Breakers UL Listed Mechanical Accessories - Class 690 Handle Accessories Breaker Prefix Number of Poles
Catalog Number
Handle Lock-off QO(B)
1, 2, 3
Handle Padlock Attachment QO(B) 1, 2, 3
HLO1
QOASPA
EHB-AS Bolt-on RemotelyControlled Operated Circuit Breakers - UL Listed
Ampere Rating
One-Pole 277Vac - 14,000 AIR 120Vac - 65,000 AIR
Two-Pole 480Y/277Vac - 14,000 AIR 120/240Vac - 65,000 AIR
Three-Pole 480Y/277Vac - 14,000 AIR 240Vac - 65,000 AIR
Catalog No.
Catalog No.
Catalog No.
EHB14015AS ●▲ EHB14020AS ●▲ EHB14030AS ●
EHB24015AS ●▲ EHB24020AS ●▲
EHB34015AS ●▲ EHB34020AS ●▲
15 20 30 ire Lug Wore Size▼ (1) #12-8 Al (1) or (2) #14-10 Cu
All are UL Listed as HACR type for use with air conditioning, heating, and refrigeration equipment having motor group combinations and marked for use with HACR type circuit breakers. ▲ UL Listed as SWD (switching duty) rated. Suitable for switching 120Vac fluorescent lighting loads. ● HID rated as for HID use rated with high intensity discharge lighting systems. UL Listed for use with high intensity discharge lighting systems. ▼ Suitable for use with 75°C conductors.
POWERLINK EHB-AS Circuit Breakers UL Listed Mechanical Accessories - Class 690 Handle Accessories Breaker Prefix Number of Poles
Catalog Number
Handle Lock-off 1, 2, 3
HLO1
Handle Padlock Attachment EHB 1, 2, 3
EHASPA
EHB
14
SQUARE D
9/98
Page 14
Electronic Components Control Bus Strips The POWERLINK AS system uses NQOD-ASB and NEHB-ASB control bus strips. The control bus strips provide interconnect wiring between POWERLINK AS circuit breakers and the power interface module. Specifically, they conduct 24Vdc switching power and control signals from the power interface to switch individual circuit breakers, and report circuit breaker status back to the control module. NQOD Control Bus (furnished in pairs)
Features Control bus strips, used in conjunction with the other POWERLINK AS modular components, eliminate external control wiring between POWERLINK AS circuit breakers and the power interface module, which simplifies installation and troubleshooting procedures.
• Internal interconnect wiring meets NEC and UL requirements for Class 1 control circuits. • Control bus strips meet NEC and UL requirements for maximum allowable gutter fill. • Installation is simplified since control bus strips reside on panelboard interior mounting channels without fasteners. • Alignment tool is included to speed installation. Control bus alignment tool holds two control bus strips in place on panelboard interior mounting channel, while POWERLINK circuit breakers are attached to interior. Tool may be removed after first circuit breakers are installed. • Top and bottom 25-pin connectors provide flexibility in mounting power interface modules. • External Class 1 control wiring is eliminated between circuit breakers and the power interface module, reducing installation time. • 6-pin connectors provide secure plug-in connections for circuit breakers and ensure that proper connections are made. • Each connector comes with a cover to protect the connection until needed. • Furnished in bi-directional identical pairs. No “left” or “right” devices to cause installation problems.
SQUARE D
9/98
15
Page 15
Electronic Components Control Bus Strips SELECTION DATA Type NQOD-ASB Control Bus for NQOD Panelboards Single Phase 100A and 225A Max. No. of Control Circuits
Required Panel Space (Interior)
Control Bus Catalog Number
14 24 36 42
20 Poles 30 Poles 42 Poles 54 Poles
NQOD214ASB NQOD224ASB NQOD236ASB NQOD242ASB
NEHB Control Bus (furnished in pairs)
Three Phase 100A and 225A Max. No. of Control Circuits
Required Panel Space (Interior)
Control Bus Catalog Number
18 24 36 42
20 Poles 30 Poles 42 Poles 54 Poles
NQOD218ASB NQOD224ASB NQOD236ASB NQOD242ASB
Control bus type NQOD-ASB is not suitable for use with NQOD 400A or 600A panels, NQOD column-width panels, panelboard interiors with 14” wide enclosures, or QO load centers.
Type NEHB-ASB Control Bus for NEHB Panelboards Three Phase 100A and 225A Max. No. of Control Circuits
Required Panel Space (Interior)
Control Bus Catalog Number
12 24 36 42
20 Poles 30 Poles 42 Poles 54 Poles
NEHB412ASB NEHB242ASB NEHB436ASB NEHB442ASB
Control bus type NEHB-ASB is not suitable for use with NEHB 400A, 600A, or NEHB column-width panels.
16
SQUARE D
9/98
Page 16
Electronic Components Power Interface Module Features • One power supply furnishes 24Vdc power for remote circuit breaker switching and 5Vdc power for the control module system electronics. • Sequencing operation with programmable stagger delay eliminates voltage sags when multiple circuit breakers are switched as a group. NEHB Power Interface Module
The power interface module provides voltage sources for POWERLINK AS circuit breakers and system electronics,
• On-board EEPROM retains input map, even in the event of a power outage. • Input terminal board accepts up to 16 external dry contact inputs with the following characteristics: – 2-wire maintained (16) – 2-wire momentary (16) – 3-wire momentary (8) • An RS-232 port provides the means for interfacing to an optional input expansion cabinet, LonWorks gateway, or remote dial-up connections. • RS-485 network option for connection to SY/LINK networks.
and reports the status
• Module can be mounted at either the top or bottom of the panelboard interior.
to the control module.
• Plugs directly to the panelboard interior; occupies only six pole spaces.
In addition, the
• Only one wire to connect: the neutral wire.
module contains input and communications terminations for connecting to external control devices.
The power interface module has capability for up to 16 two-wire inputs, 8 threewire inputs, or a combination of these types of inputs. These are numbered 1 through 8 [plus (+) to common (C)] and 57 through 64 [minus (-) to common (C)] on the interface module. Inputs 9 through 56 are available when the expansion cabinet is used.
1 + - C 57
2 + - C 58
3 + - C 59
4 + - C 60
1 + - C 57
2 + - C 58
3 + - C 59
4 + - C 60
5 + - C 61
6 + - C 62
7 + - C 63
8 + - C 64
5 + - C 61
6 + - C 62
7 + - C 63
8 + - C 64
EXP
RS-485 (COMMS)
EXP
LED
TX RX SH IN- IN+ OUT- OUT+ SH
•
Input Terminal Compartment Power Interface Module (Standard)
Wiring
LED
•
Input Terminal Compartment Power Interface Module (Network)
2-wire switch + • C
RS-485 (COMMS)
TX RX SH IN- IN+ OUT- OUT+ SH
•
3-wire switch + • • C • –
Wiring Diagram
SQUARE D
9/98
17
Page 17
Electronic Components Power Interface Module SPECIFICATIONS Operating Voltage: NQOD242ASP(N) & Nominal Voltage Max. Operating Range NEHB242ASP(N) ............................................. 208 to 240Vac 187 to 264Vac (60Hz) NEHB342ASP(N) .......................................... 380Y/220Vac 342 to 418Vac (50/60 Hz) NEHB442ASP(N) ............................................... 480Y/277Vac 432 to 528Vac (60 Hz)
Power Interface Module with LV compartment cover removed
SELECTION DATA Power Interface Modules for NQOD Panelboards Module Type Standard Network
Voltage Range
Catalog Number
208Vac, 240Vac NQOD242ASP 208Vac, 240Vac NQOD242ASP-N
Power Interface Modules for NEHB Panelboards Module Type
Voltage Range
Catalog Number
Standard Standard Standard
208Vac, 240Vac 380Y/220Vac 480Y/277Vac
NEHB242ASP* NEHB342ASP NEHB442ASP
Network Network Network
208Vac, 240Vac NEHB242ASP-N* 380Y/220Vac NEHB342ASP-N 480Y/277Vac NEHB442ASP-N
* Special order only.
18
Wire Connections - Inputs: Number of Inputs ............................................... 16 points independent, ......................................................................... expandable to 64 points Input Types ................................. 2-wire maintained, 3-wire momentary, .............................................. or 2-wire momentary. No external control .................................................... voltage required. Mechanical contact ............................................................... input or solid state equivalent. Input Terminals ...................................................................... 3 per input Terminal Wire Range .................................................... #22-18 AWG Cu #18 AWG ............................................................ Maximum of 3000 feet #22 AWG ............................................................ Maximum of 1000 feet NEC Circuit Classification ................................ Class 2 Remote Control External control voltage .................................................. None required Network Port Specifications: Network Port Type [ASP(N) Models] .......... One RS-485 (Belden 8723) Number of Terminals ....................................................................... Five Terminal Wire Range .................................................... #22-18 AWG Cu NEC Circuit Classification ................................ Class 2 Remote Control Input Expansion Port Specifications: Port Type ............................................................................ One RS-232 Number of Terminals .................................................................... Three Terminal Wire Range .................................................... #22-18 AWG Cu NEC Circuit Classification ................................ Class 2 Remote Control Environmental Specifications: Operating Temperature (ambient) ................................... -5°C to +40°C Storage Temperature (ambient) ............................... -20°C to +85°C Operating Humidity ......................... 5% to 95% (non-condensating) Diagnostics LED: Blinking ....................................................................... Normal operation On (no blink) ................................ Program requires firmware download Off ..................................................................................... Check power
SQUARE D
9/98
Page 18
Electronic Components Class 2 Barrier Kit Features • UL Listed barrier tubing allows Class 2 conductors to occupy same gutter area as line-voltage conductors. • Accommodates Class 2 wiring from external control devices and RS-485 network cable in a common raceway. • Barrier tubing extends from panelboard tub endwall to the input terminal compartment on the power interface module. • No special mounting tools or fasteners. • Kits include: Class 2 Barrier Kit
– 0.75” tube in six-foot lengths – 0.75” box coupling compression fitting – Choice of straight-in or 90° power interface module fittings
The Class 2 barrier kit
• The six-foot tube may be cut to desired length and the compression fittings may be re-attached to the end of the tube.
includes a flexible, UL Listed barrier tube that
• Up to two barriers, one straight-in and one 90 degree, may be attached to input terminal compartment on power interface module. Meets requirements for 1996 NEC article 725-52.
separates Class 2 low-voltage external control wiring from line
.985 ± .010 Dia.
voltage conductors within the panelboard gutter. R .015 Max.
R .125 ± .015
.215 ± 0.15
SELECTION DATA
1.400 ± .015 Dia.
Description
Catalog Number
Barrier with straight-in coupling Barrier with 90 degree coupling
ASBK-S ASBK-B
.200 ± 0.15
ASBK-B ASBK-B 9090DEGREE COUPLING DEGREE COUPLING Same Inside Diameter As 931-021 Compression Fitting
End View
.75 ± .010 1.400 ± .015 Dia.
R .200 ± .015
.985 ± .010 Dia. R .125 ± .015
Hose
R .015 Max.
ASBK-S ASBK-S STRAIGHT-IN COUPLING STRAIGHT-IN COUPLING SQUARE D
9/98
19
Page 19
Electronic Components Control Modules The control module provides optional network communications, multichannel time clock functions, 365 day calendar control, and optional local display operations. Each POWERLINK AS panelboard requiring any of these functions needs a control module. The control module serves as a programming tool for input-based control such as LV matrix switching. For these applications, only one control module is required to program all the POWERLINK panels on a job site. Control modules are easy to install and do not require any tools. Simply open the trim front door and plug the control module onto the power interface module.
Standard control module (top) and graphical display control module
The intelligence of the
The control module can be configured at your desk by using a small AC adapter. Once the panelboard is in service, the configuration can be completed at the panel or over the communications network. There are two types of control modules: the graphical display control module (models AS42CM and AS42CM-T) and the standard control module (AS42C and AS42C-T). Both are described in the following pages.
POWERLINK AS
SPECIFICATIONS system comes from its resident microprocessor-based control module, which directs and simplifies the operation of the system. An optional time-of-day control module makes it possible to schedule automatic switching of lighting and electrical equipment for
General: Screen ..................................................... LCD with contrast adjustment ........................................................... (graphical display modules only) Environmental: Operating Temperature (ambient) ................................... -5°C to +40°C Storage Temperature (ambient) .................................... -20°C to +85°C Operating Humidity .............................. 5% to 95% (non-condensating) Memory: EEPROM ....................................... For configuration/command storage Super Capacitor ................... For 30 days time clock and status backup Port: DB-9 ................................................................. For communication with ......................................................................... power interface module ........................................................................... (or receive power from ........................................................................... desktop power supply) Serial .......................................................... One RS-232 for connection ............................................................................ to IBM-compatible PC individual circuits.
20
SQUARE D
9/98
Page 20
Electronic Components Control Modules Features System Features
SELECTION DATA Standard AS42C AS42CT
Graphic Display AS42CM AS42CMT
Hardware Graphics display with contrast adjustment LED screen 24 button keypad RS232 programming port RS-485 Network port EEPROM for configuration/ program storage Super capacitor for 30 days time clock & status backup Manual reset
X
X
X X X
X X X
X
X
X X X X
X X X X
X X
X
Description
Catalog Number
Standard Standard time of day Graphic Display Graphic Display Time of day
AS42C AS42C-T AS42CM AS42CM-T
X X
X
X
X
X
X X X X
Monitor Mode Breaker status Setup Mode Input/breaker assignments 12/24 hour clock format 7 day repeating calendar 365 day calendar with leap year correction Daylight savings Sunrise/Sunset with select offset Zone setup Password Input type Panel data Communications settings Adjustable stagger delay Blink notice Input time
X*
X* X* X* X* X* X*
X*
X*
X* X* X
X* X* X X* X* X*
X X X X X X X
X X X X X X X X
Program Mode Time-based programming Input-based programming Special date programming
X* X* X*
X X X
Override Mode Breaker override Zone override Run/Stop/Hold modes
X* X* X*
X* X* X*
X X X
X X X
X* X*
X X* X* X* X* X* X
X X
X X X X X X X
Diagnostic Mode Memory Communications Event log Access log Reset Clear program Downloadable firmware
X* X* X
X X X
* Requires POWERLINK software for configuration SQUARE D
9/98
21