The text of a spec sheet · part 3 of 5

POWERLINK AS Lighting Control System Catalog, pages 21 to 30

Pages 21 to 30 of 49

The original document is the PDF (2.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D AS42C and Schneider AS42C

Page 21

Electronic Components Control Modules Graphical Display Control Module

A - LCD Screen B - Selection Keys C - Contrast Control D - Reset button E - RS-232 Communications Port

Figure 4–Graphical display control module

The graphical display control module (AS42CM and AS42CM-T), shown in figure 4, displays system status and program information using an LCD screen (A). System configuration and programming are performed using the module selection keys (B). Screen contrast can be adjusted to the desired value using the module’s contrast control (C). The control module can be reset manually by depressing the reset button (D) with a paper clip or similar tool. This will restart operation without affecting system configuration. In addition to the network connection, a temporary link is available using the RS-232 (serial) communications port (E).

Note: If using the RS-232 port on the control module, serial communications cable #AS42CM-SC is required.

Entering the Program You can program the graphical display control module in one of three ways: 1) Local desktop mode (see page 35): Requires:

Power supply - AS42CM-DPK

Procedure:

Use the 24-button keypad on the control module to enter setup information.

2) Local desktop mode (see page 35): Requires:

Power supply - AS42CM-DPK Serial cable - AS42CM-SC Software - PLK-101 or CMS 1000 installed on a personal computer or workstation.

Procedure:

Use AS42CM-SC cable to connect a personal computer to the RS-232 communication port on the control module. You can then download configuration information from POWERLINK software to the control module.

3) Network mode: Requires:

Power supply - A control module plugged into an energized POWERLINK panelboard. Software - POWERLINK PLK 101 or CMS 1000 installed on a remote personal computer or workstation.

Procedure:

Set up the communications options in the control module (i.e., network address and baud rate). Connect the personal computer and the POWERLINK panelboard to the network. Then use POWERLINK software to download configuration information to the control module.

Events Circuit breakers are turned on or off based on an event. A control module will accept up to 256 programmed events. Events can be on automatic control, such as time-of-day, or signalled by an input change (e.g., moving a light switch from on to off). Output signals are sent from the control module to the circuit breakers via the power interface module.

Overrides An override changes the state of an output independent of the control module program. Three types of overrides may be initiated from the control module: • Override Breaker–selects an individual circuit breaker • Override Zone–selects a group of circuit breakers • Override All Breakers–selects all POWERLINK AS circuit breakers 22

SQUARE D

9/98

Page 22

Electronic Components Control Modules Override conditions may be selected as temporary, which will be in effect until the next event, or continuous, which remains in effect until released. Individual circuit breakers have the switching mode selector switch, which takes priority over overrides initiated from the control module.

Operating Modes There are three modes of operation: 1. Run - System responds automatically to events. All system features and functions are working. Single-event, on-line programming is allowed. 2. Manual - All circuit breakers are turned on, and events are not processed. All remote and network data is ignored. 3. Hold - Control signals are not processed, but events are logged. Outputs are updated when the mode of operation is returned to RUN. Overrides, diagnostics, and local programming are allowed.

Access Codes The control module uses a four-digit access code to control program security. There are three levels of security, each level requiring its own access code. If no key is pressed for five minutes, an access code will “time out,” and it must be re-entered.

Table 6 Access Codes Permissible Access Level Main Screen

Sub Screen

■

Status Setup

None

Clock/Calendar (AS42CM-T)

Operator

Master

■

■

■

■

■

■

■

■

■

■

■

■

■

Define Zones Access Codes

Supervisor

Sunrise/Sunset (AS42CM-T) Input Type

■

Panel Data

■

Communications

■ ■

Global Values Program

Override

Diagnostic

■

■

Program

■

■

View

■

■

Delete

■

■

Breakers

■

■

Zones

■

■

All Breakers

■

■

Operating Mode

■

■

Control Module

■

■

■

Interface Module

■

■

■

Expansion Unit

■

■

■

Non-Responding Breaker

■

■

■

Software Versions

■

■

■ ■

Clear Memory

SQUARE D

9/98

23

Page 23

Electronic Components Control Modules Names

Table 7 Access Codes

For control modules programmed with a PC, an operational 12-character alphanumeric name tag can be assigned to individual circuit breakers or zones of circuit breakers within a panelboard. Name tags will not actually appear unless a name has been entered for that item, using a PC and PLK-101 or CMS-1000 software.

HIGHEST

Operating Mode (Run, Manual, Hold)

Default Action When No Controller (All On, All Off, N. C., Run Inputs)

Priorities

Continuous Override - From the Front panel Equal Priority - Over the Network

PRIORITY

In cases of conflicting commands, such as a time-based event telling a circuit breaker to turn on and an input event telling a circuit breaker to turn off, a priority system is used. Higher priority commands override lower priority commands. Refer to Table 7 to see how the POWERLINK AS system assigns priorities.

Screen Organization The control module organizes screens under five headings: Status, Setup, Program, Override, and Diagnostic. These are listed across the top of the screen (A) on all five main screens (see figure 5).

Priority Maintained (From inputs 1–8 and 57–64, Power Interface Module)

1. Status screen - shows the position, pole number, and status of all circuit breakers, indicating if the circuit breaker is on, off, or overridden. The screen also displays present operating mode, and time of day and date, (time-of-day control module only). This is the default screen on power-up. 2. Setup screens - used to set up the system configuration, communications, and global values. This must be completed before any programming functions can be performed.

Temporary Override - From the Front Panel - Over the Network - Time of Day Event Equal Priority - Special Date Event - Input Event - Sunrise/Sunset

LOWEST

3. Program screens - used to program the system for desired operation. 4. Override screens - used to override breaker position. 5. Diagnostic screens - used to evaluate system performance, and for troubleshooting.

B

Selection Keys The selection keys (B) on either side of the LCD are used for entering the program choices. The keys operate only if there is an arrow next to them.

D

C

A

E

Solid arrows indicate that the key will modify a choice on that screen. STATUS

SETUP PROGRAM OVERRIDE DIAGNOSTIC

Hollow arrows indicate that the key will advance you to a new screen.

11:00AM AM TU12/31/92 / 02/9895 11:00 0805/ 04/ OPERATING MODE = RUN 11:00 AMTU = ON BREAKER STATUS IS SHOWN BELOW = OFF = OFF BLINK = OVERRIDDEN = ON

The keys will stay in a neutral position until actuated and can be moved to a minus (-) or plus (+) position.

2 4 6

Access Codes Screens The control module displays the access code screen as necessary. If a screen with restricted access is requested by a user without access authorization, the module prompts the user to enter an access code before it displays the requested screen.

10 12

1 3 5 7 9 11 13

RESET

20 22 24 26 28 30 32 34 36 38 40 42

16 17

21

25 27 29 31 33

37

41

AS Figure 5 - Control Module Status Screen

Global Values Global values are set to affect all POWERLINK AS circuit breakers and all program items. BLINK NOTICE - sets the number of minutes prior to a change that the program will blink the lights, prior to a pending timed OFF event. Default value is 00 minutes prior to a change, (no blink notice), and blink notice may be user configured from 0–60 minutes. 24

SQUARE D

9/98

Page 24

Electronic Components Control Modules SEQUENCE TIME - sets the time period between circuit breaker switching operations, when multiple circuit breakers are switch simultaneously with an event. Default value is 0.25 seconds, and sequence time may be user configured to either 0.25, 0.5, 1.0, 5.0, or 10.0 seconds. DEFAULT ACTION IF NO CONTROL MODULE - defines the action by the system if control module is removed. Default action takes effect if the control module is removed from the system for more than one minute, or if no control module is present upon power-up. The available user-defined default actions are: ALL ON - All circuits forced on; no programs will execute. ALL OFF - All circuits forced off; no programs will execute. NO CHANGE - All circuits remain in current state; no programs will execute. RUN INPUTS - Circuits will continue to respond to input-based programs; time-based programs, special date programs, and input timers will not execute. This is the system default.

Circuit Breaker Status Circuit breaker status is indicated at the bottom of many screens. All circuit breakers available to the system are shown as numbers (refer to figure 3).

#

A white number in a black box indicates that the circuit breaker is in the off position.

#

A black number in a white box indicates that the circuit breaker is in the on position.

#

A white number in a blinking black box indicates that the circuit breaker is in the continuous off position.

#

A black number in a blinking white box indicates that the circuit breaker is in the continuous on position.

#

A white number in a dotted blinking black box indicates the breaker is commanded by a priority maintained input to turn off. A dotted blinking black number in a dotted blinking white box indicates the breaker is commanded by a priority maintained input to turn on.

Multi-pole circuit breakers are indicated by connected boxes: A two-pole circuit breaker has two boxes with one number.

#

A three-pole circuit breaker has three boxes with one number.

#

Numbers represent the pole containing the internal 24Vdc motor and the 6pin plug-on control bus connector.

Status Screen The status screen is the default screen, which is displayed whenever the system is active. The control module returns to the status screen after five minutes of no activity. The status screen displays (refer to figure 2 on previous page): • Circuit breaker status (C), indicating if the circuit breaker is on (a black number in a white box, off (a white number in a black box), overridden on (a black number in a blinking white box), overridden off (a white number in a blinking black box), commanded by a priority maintained input to turn off (a white number in a dotted blinking black box), or commanded by a priority maintained input to turn on (a dotted blinking black number in a dotted blinking white box). SQUARE D

9/98

25

Page 25

Electronic Components Control Modules • The overridden legend (blinking white box) will appear only if one or more of the circuit breakers is overridden. • The operating mode (D) of the system (run, manual, or hold). • Internal time and date (E) (appears with optional time-of-day control modules only). If time does not include AM or PM, then the internal clock is using a 24-hour display.

Standard Control Module A C

B –

+

–

+

–

+

STATUS

SETUP

–

+

–

+

CPU

RX

ADDRESS

–

+

–

+

CLK

TX

K BAUD

–

+

–

+

–

+

COMMUNICATIONS

MODIFY

SELECT

–

+

–

+

+ -

AS

The standard control module (AS42C and AS42C-T), shown in figure 6, displays status and communication parameters using indicators (D, F, G) and an LED display (B). System configuration is done using selection keys (A). In addition to the network connection, a temporary link is available using the RS-232 (serial) communications port (E). The control module can be reset manually by depressing the reset button (C) with a paper clip or similar tool. This will restart operation without affecting system configuration. Entering the Program

G

F

E

D

A - Selection Keys B - LED Display C - Reset Button D - Display Mode Indicators E - RS-232 Communications Port F - Communications Activity Indicators G - Status Indicators

You can program the standard control module in one of two ways: 1) Local desktop mode (see page 35): Requires:

Power supply - AS42CM-DPK Serial cable - AS42CM-SC Software - PLK-101 or CMS 1000 installed on a remote personal computer or workstation.

Procedure:

Use AS42CM-SC cable to connect a personal computer to the RS-232 communication port on the control module. You can then download configuration information from POWERLINK software to the control module.

Figure 6–Standard control module

2) Network mode: Requires:

Power supply - A control module plugged into an energized POWERLINK panelboard. Software - POWERLINK PLK 101 or CMS 1000 installed on a remote personal computer or workstation.

Procedure:

26

Set up the communications options in the control module (i.e., network address and baud rate). Connect the personal computer and the POWERLINK panelboard to the network. Then use POWERLINK software to download configuration information to the control module.

SQUARE D

9/98

Page 26

Panelboards General Information NQOD Panelboard Features: • Industrially-proven rugged construction. • Circuit breakers are multi-pole, multi-amp, HACR, HID, and SWD rated. • Maximum voltage: 240 Vac. • Maximum mains ampacity: 225 A main lug; 250 A main circuit breaker. • Maximum branch ampacity:, 30 A QO(B)-AS POWERLINK breaker., 125 A QO plug-on standard breaker., 150 A QO(B) bolt-on standard breaker., (1) 225 A sub-feed breaker. NEHB Panelboard Features: • Industrially-proven rugged construction. • Circuit breakers are multi-pole, multi-amp, HACR, HID, and SWD rated. • Maximum voltage: 480Y/277 Vac. • Maximum mains ampacity: 225 A main lug; 250 A main circuit breaker. • Maximum branch ampacity:, 30 A EHB-AS POWERLINK breaker., 60 A EH plug-on standard breaker., 100 A EHB bolt-on standard breaker., (1) 225 A sub-feed breaker. • UL listed, Class CTL panelboard meets paragraph 384-15 of the NEC. • Distributed phase bussing. Branch circuit breakers may be mounted in any position. Interiors: • Will accept plug-on or bolt-on branch circuit breakers. • Suitable for use as a service entrance (statement found on wiring diagram. • Top or bottom feed. • 65k AIR maximum standard branch circuit breakers (fully rated). • 200k AIR maximum when supplied by remote ILIMITER® circuit breaker (series rated). • 100 A and 225 A are suitable for use as service entrance with back-fed QO(B) circuit breaker. • Field installable sub-feed lug kits for 100–225 A interiors. • Factory installed main lugs on all interiors. • 225 A main lug interiors are convertible to main circuit breaker by adding a main circuit breaker and adapter kit. • Available with silver-plated copper or tin-plated aluminum bus (aluminum is standard). Tin-plated copper bus is an available option. Branch connector fingers are all tin-plated copper; silverplated branch connector fingers are optional.

Main Circuit Breakers: • 100 A main circuit breaker interiors consist of factory installed back-fed QO(B) main circuit breaker. • 225 A main circuit breaker interiors use:, Standard main lug interiors., Main circuit breaker adapter kit., Appropriate Q2L, Q2L-H, Q2LH, KAL, KHL, KDL, KGL, KCL, or KIL circuit breaker. Enclosures (NEMA Type 1) Boxes: • Galvanized steel with removable endwalls. One endwall is provided with knockouts and the other endwall is blank. • Size: 20 in. (508 mm) wide x 5.75 in. (146 mm) deep. • Box and interior mounting instructions are found in the information manual shipped with the interior. • Interiors mount directly to studs in the boxes. No interior mounting brackets are required. Fronts: • Finished with gray baked enamel electrodeposited over cleaned phospha-tized steel (ANSI 49). • Flush or surface mounted. • Door with flush lock. Uses NSR-251 key. • Directory card is located on the inside of the door. • MONO-FLAT® fronts on 100–225 A interiors mount to the interior trim with trim screws. Both trim screws and door hinges are concealed. Fronts are not removable with the door closed and locked. • Fronts 56 in. (1422 mm) high or more have sliding vault locks and 3-point latching. Enclosure Options for NQOD and NEHB Panelboards Types

Environment

Provides Protection Against

NEMA Type 1

Indoor

Contact with enclosed equipment

NEMA Type 3R

Outdoor

Rain, sleet, ice

NEMA Type 5

Indoor

Dust, dirt, liquids

NEMA Type 12

Indoor

Dust, dirt, liquids

SQUARE D

9/98

27

Page 27

Panelboards Series Ratings UL Certified Series Connected Ratings This page contains UL tested and certified series combination ratings for panelboards. These ratings apply to either an integral main located in the same enclosure or a remote main located in a separate enclosure.

Table 8 NQOD Series Ratings System UL Series Voltage Connected Rating (Maximum) (AIR)

Main

Branch

Type

Max. Amperes

Type

Amperes

Poles

QOB-VH

150

QO-AS, QOB-AS

Q2-H

225

QO-AS, QOB-AS

FC

100

QO-AS, QOB-AS

KC

250

QO-AS, QOB-AS

FI

100

QO-AS, QOB-AS

KI

250

QO-AS, QOB-AS

15–30 15–30 15–30 15–30 15–30 15–30 15–30 15–30 15–30 15–30 15–30 15–30 15–30 15–30 15–30 15–30 15–30 15–30

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

22,000

240Vac

100,000

POWERLINK AS panelboard with 1-, 2-, and 3-pole series-rated circuit breakers with high interrupting 250 amp main circuit breaker.

200,000

Table 9 NEHB Series Ratings System UL Series Voltage Connected Rating (Maximum) (AIR)

240Y/ 277Vac

480Y/ 277Vac

28

Main

Branch

Type

Max. Amperes

Type

FC

100

EHB-AS

KC

250

EHB-AS

FI

100

EHB-AS

KI

250

EHB-AS

Class J Fuse

200

EHB-AS

65,000

100,000

Amperes

Poles

15–30 15–20 15–20 15–30 15–20 15–20 15–30 15–20 15–20 15–30 15–20 15–20 15–30 15–20 15–20

1 2 3 1 2 3 1 2 3 1 2 3 1 2 3

SQUARE D

9/98

Page 28

Dimensions 20 in. (508 mm) Wide Enclosures NQOD Main Lug Panelboards (225 Ampere Maximum Main Lugs)

Surface Mounting W + 0.12 3

10

266

Interior Trim Flush Lock H

A B C Solid Neutral

Main Lugs

D

Flush Mounting H + 1.50 38

10.44

76

Flush Mounting W + 1.50 38

0.375 Dia.

Surface Mounting H + 0.12 3

3.00

E

2.50 (20" Wide Box)

0.25 Mounting

64

6

20.00

5.75

Typical Box with Interior

Typical Box Side View

508

Typical Front

Hole Emboss

146

Concealed Door Hinges

Typical Mounting of QO, QOB Circuit Breakers

Indoor - NEMA Type 1 Outdoor - NEMA Type 3R

Interior Mounting Studs

2.50

6.50

H minus 1.20 30

64

165

Typical Mounting of QO, QOB Circuit Breakers

H

B

4.78 121

1.00 25

2.50

20.00

0.50

64

508

13

Typical Endwall

Typical Side View with Mounting Provisions

Typical Front View

Dimensions:

Note: Refer to page 34 for keyhole and endwall detail.

Maximum Maximum Required Main Lug Number of Panel Ampere PowerLink Interior Rating Size Circuits

100

225

H Box Height

INCHES mm

E D C A B Deadfront Length Mounting Studs Mounting Holes MLO Wire Bending S/N Wire Bending

IN mm

IN mm

IN mm

IN mm

IN mm

IN mm

14

20 ▲

23.00

584

17.90

455

18.00

457

18.88

480

6.89

175

5.46

139

18

24 ■

23.00

584

17.90

455

18.00

457

18.88

480

6.89

175

5.46

139

24

30 ■

26.00

660

20.90

531

21.00

533

21.88

556

6.89

175

5.46

139

24

30

32.00

813

26.90

683

27.00

686

27.88

708

11.43

290

10.00

254

36

42

35.00

889

29.90

759

30.00

762

30.88

784

8.43

214

7.00

178

42

54

41.00

1041

35.90

912

36.00

914

36.88

937

8.43

214

7.00

178

▲ 1φ3W only. ■ 3φ4W only. SQUARE D

9/98

29

Page 29

Dimensions 20 in. (508 mm) Wide Enclosures NQOD Main Circuit Breaker Panelboards (100 Ampere Maximum Main Circuit Breaker) 3.00 76

Flush Mounting W + 1.50 38

0.375 Dia.

10.44

Surface Mounting W + 0.12 3

10

266

Flush Lock Solid Neutral

A B C

H

Flush Mounting W + 1.50 38

Surface Mounting W + 0.12 3

Interior Trim

17.46 443

D E

2.50 (20" Wide Box)

0.25 Mounting

64

20.00

6

5.75

508

Typical Front

Hole Emboss

146

Typical Box Side View

Typical Box with Interior

Concealed Door Hinges

Typical Mounting of QO, QOB Breakers

Indoor - NEMA Type 1 Outdoor - NEMA Type 3R Interior Mounting Studs

2.50

6.50

64

165

H minus 1.20 30

Typical Mounting of QO, QOB Circuit Breakers B

H

4.78 121

1.00 25

Typical Endwall

2.50

20.00

64

508

0.50 13

Typical Front View

Typical Side View with Mounting Provisions

Dimensions: INCHES mm

Note: Refer to page ___ for keyhole and endwall detail. Maximum Main Maximum Required Panel Number of Circuit Breaker PowerLink Interior Ampere Rating Circuits Size 100 FAL ★, FHL ★

100 FIL ★ ▲ 1φ3W only.

30

H Box Height

D (from Center Line of CB) E (from Line Lugs of CB) C A B Mounting Studs Mounting Holes Deadfront Length Top Feed Bottom Feed Top Feed Bottom Feed

IN mm

IN mm

IN mm

IN mm

14

20 ▲

35.00

889

30.00

762

30.88

784

29.90

759

18

24 ■

35.00

889

30.00

762

30.88

784

29.90

759

24

30 ■

38.00

965

33.00

838

33.88

860

32.90

836

14

20 ▲

35.00

889

30.00

762

30.88

784

29.90

759

18

24 ■

35.00

889

30.00

762

30.88

784

29.90

759

24

30 ■

38.00

965

33.00

838

33.88

860

32.90

836

■ 3φ4W only.

IN mm

IN mm

IN mm

IN mm

11.82

300

10.06

256

8.08

205

8.08

205

10.08 256

10.08

256

7.08

180

7.08

180

★ Factory assembled only.

SQUARE D

9/98

Page 30

Dimensions 20 in. (508 mm) Wide Enclosures NQOD Main Circuit Breaker Panelboards (250 Ampere Maximum Main Circuit Breaker)

Surface Mounting W + 0.12 3

10

266

Flush Lock

Solid Neutral H

A B C

Interior Trim

Flush Mounting H + 1.50 38

10.44

76

Flush Mounting W + 1.50 38

0.375 Dia.

Surface Mounting H + 0.12 3

3.00

22.00 559

D E

0.25 Mounting

2.50 (20" Wide Box) 64

6

5.75

20.00

Typical Front

Hole Emboss

146

508

Typical Box Side View

Typical Box with Interior

Concealed Door Hinges

Typical Mounting of QO, QOB Circuit Breakers

Indoor - NEMA Type 1 Outdoor - NEMA Type 3R Interior Mounting Studs

2.50 64

6.50

H minus 1.20 30

165

Typical Mounting of QO, QOB Circuit Breakers

B H

4.78 121

1.00 25

2.50

20.00

Typical Endwall

64

508

0.50 13

Typical Front View

Typical Side View with Mounting Provisions

Dimensions:

Note: Refer to page 34 for keyhole and endwall detail. Maximum Main Maximum Required Panel Circuit Breaker Number of PowerLink Interior Ampere Rating Size Circuits 225 Q2L Q2L-H, Q2LH 225/250 ▲ KAL, KHL, KDL KGL, KIL

H Box Height IN

INCHES mm

D (from Center Line of CB) E (from Line Lugs of CB) A B C Mounting Studs Mounting Holes Deadfront Length Top Feed Bottom Feed Top Feed Bottom Feed mm

IN mm

IN mm

IN mm

24

30

44.00

1118

39.00

991

39.88

1013

39.90

1013

36

42

50.00

1270

45.00

1143

45.88

1165

44.75

1137

42

54

56.00

1422

51.00

1295

51.88

1318

50.75

1289

24

30

44.00

1118

39.00

991

39.88

1013

39.90

1013

36

42

50.00

1270

45.00

1143

45.88

1165

44.75

1137

42

54

56.00

1422

50.00

1295

51.88

838

50.75

1289 mm

IN

16.89 432

15.66 398

IN mm mm

IN mm

15.88

393 13.66

347

12.79 325

15.66

398

12.05

306

12.05 306

IN

▲ 250 A available factory-assembled only. SQUARE D

9/98

31