The text of a spec sheet · part 4 of 5
POWERLINK AS Lighting Control System Catalog, pages 31 to 40
Pages 31 to 40 of 49
The original document is the PDF (2.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Square D AS42C and Schneider AS42C
Page 31
Dimensions 20 in. (508 mm) Wide Enclosures NEHB Main Lug Panelboards (225 Ampere Maximum Main Lugs) 2.00
2.50
8.50
51
64
216
Flush Lock
Interior Trim
A
B
H
Flush Mounting H + 1.50 38
Surface Mounting H + .13 3
Directory Card Holder
2.50 64
TYPICAL FRONT
2.50
10.44 4.78
265
121
20.00
5.75
64
146
4.78 121
508
TYPICAL BOX SIDE VIEW
TYPICAL BOX WITH INTERIOR
3.06 78
7.69 195
Flush Mounting 21.50 546
3.06
1.38 TYP.
78
35 15 ( 1 2, 3 4 ) Concentric KO.
20.13
6 ( 1 2, 3 4 ) Concentric KO.
Surface Mounting 511
Concealed Trim Clamps 1 (11 4, 11 2, 2, 21 2, 3, 31 2 ) Concentric KO.
1 (11 4, 11 2, 2, 21 2, 3) Concentric KO.
Concealed Door Hinges
TYPICAL MOUNTING OF EH OR EHB BREAKERS
TYPICAL ENDWALL
Dimensions:
Note: Refer to page 34 for keyhole and endwall detail.
Maximum Maximum Main Lug Number of Ampere PowerLink Rating Circuits 125
225
32
Required Panel Interior Size
H Box Height
INCHES mm
A B Mounting Studs Mounting Holes
IN mm
IN mm
IN mm
12
18
29.00
737
24.00
610
25.00
635
24
30
35.00
889
30.00
762
31.00
787
24
30
35.00
889
30.00
762
31.00
787
36
42
41.00
1041
36.00
914
37.00
940
42
54
47.00
1194
42.00
1067
43.00
1092
S/N
TYPICAL WIRING DIAGRAM
SQUARE D
9/98
Page 32
Dimensions 20 in. (508 mm) Wide Enclosures NEHB Main Circuit Breaker Panelboards (250 Ampere Maximum Main Breaker) 2.00
2.50
8.50
51
64
216
B
A
H minus 7.22 183
Flush Lock
H
TYPICAL BOX SIDE VIEW
TYPICAL BOX WITH INTERIOR
Flush = H plus 1.50 38
Interior Trim
Surface = H plus .13 3
Directory Card Holder
2.50 64
12.68 2.50
10.44
64
265
4.78
78
TYPICAL FRONT
121
508
3.06
146
4.78
20.00
121
322
5.75
7.69 195
TYPICAL MOUNTING OF EH OR EHB BREAKERS
3.06
1.38 TYP.
78
35 15 ( 1 2, 3 4 ) Concentric KO.
6 ( 1 2, 3 4 ) Concentric KO.
Flush Mounting 21.50 546
20.13
Surface Mounting 511
TYPICAL ENDWALL Concealed Trim Clamps 1 (11 4, 11 2, 2, 21 2, 3, 31 2 ) Concentric KO.
1 (11 4, 11 2, 2, 21 2, 3) Concentric KO.
Dimensions:
Note: Refer to page 34 for keyhole and endwall detail.
Maximum Main Maximum Circuit Breaker Number of PowerLink Ampere Rating Circuits 125
250
Required Panel Interior Size
H Box Height
INCHES mm
A B Mounting Studs Mounting Holes
IN mm
IN mm
IN mm
12
18
38.00
965
33.00
838
34.00
864
24
30
44.00
1118
39.00
991
40.00
1016
24
30
47.00
1194
42.00
1067
43.00
1092
36
42
53.00
1346
48.00
1219
49.00
1245
42
54
59.00
1449
54.00
1372
55.00
1397
SQUARE D
9/98
Concealed Door Hinges
S/N
TYPICAL WIRING DIAGRAM
33
Page 33
Dimensions 20 in. (508 mm) Wide Enclosures NQOD and NEHB Keyhole and Endwall Detail 0.31 8
1.12 1.75 44
28
0.50 13
3.06 78
3.00
1.38 Typ.
76
1.38
24 (1⁄2, 3⁄4) Concentric KO
1 (3⁄4, 11⁄2, 2, 21⁄2) Concentric KO
35
7.69 195
3.06 78
35
1 (11⁄4, 11⁄2, 2, 21⁄2, 3, 31⁄2) Concentric KO
15 (1⁄2, 3⁄4) Concentric KO 9
⁄32 KO
14" Wide Endwall with Knockouts (Other Endwall is Blank)
6 (1⁄2, 3⁄4) Concentric KO
1 (11⁄4, 11⁄2, 2, 21⁄2, 3) Concentric KO
20" Wide Endwall with Knockouts (Other Endwall is Blank)
Keyhole Detail (2 Holes Typical)
Dimensions:
34
INCHES mm
SQUARE D
9/98
Page 34
Accessories Desktop Power Supply POWERLINK AS desktop programming power supplies allow POWERLINK AS control modules to be programmed without being installed in the panel. The desktop power supply operation is very similar to a standard calculator type power supply. Simply plug the power supply into a standard 120V, 60 Hz wall outlet, and insert the 9-pin connector into the back of the module. Desktop power supply connected to control module
When powering up, the control module will follow its initialization sequence, and then display the status screen. Since the control module is not installed in a panel, it will assume that 42 1-pole POWERLINK AS circuit breakers are present. This permits all 42 circuit breaker locations to be programmed. Multi-pole breakers can be programmed by selecting the pole number corresponding to the motor location (see figure 7 below). Desktop programming of the control module can be done by either of the methods listed below: Using application software: • Connect a PC directly to the RS-232 port on the control module via the AS42CM-SC cable. • Download programs from either PLK 101 or CMS 1000 software. From control module: • Program the control module by manually selecting the desired functions using the module’s 24-button keypad. (For more information, see the control module section on page 20.
Control module connected to PC via AS42CM-SC cable
After the control module is programmed, it is ready for installation in the panelboard.
AS42CM-SC Cable
Figure 7 - Motor Location (
Indicates motor pole)
SELECTION DATA Description Desktop Power Supply RS-232 Download Cable
Catalog Number AS42CM-DPK AS42CM-SC
SQUARE D
9/98
35
Page 35
Accessories Input Expansion Cabinet The POWERLINK system input expansion cabinet allows you to multiply the benefits of the POWERLINK AS remote power switching system without complicated installation or operation procedures. It provides as many as 48 additional inputs over the 16 inputs available within the POWERLINK AS system. The POWERLINK system input expansion cabinet is ideal for new or retrofit lighting applications. Its efficient design significantly reduces installation and maintenance time, while its low voltage switching (24V) provides safe and easy operation.
Input Expansion Cabinet
The input expansion cabinet provides 42 additional outputs and 48 additional inputs over the 16 inputs available within the
Installation costs are reduced because the system accepts low voltage Class 2 wiring, which typically requires no conduit. Inputs used with Class 2 wiring include low voltage switches, motion detectors, and photo cells, which can be 2-wire maintained, 2-wire momentary, or 3-wire momentary. In most lighting applications, low voltage switches operating at 24Vdc will be used. These switches can be conveniently programmed to provide a variety of tasks, including simple on/off switching, overriding a programmed event, or acting as a simple timer. The POWERLINK system input expansion cabinet is easily reprogrammed to meet a facility’s changing requirements without rewiring. Each of the 48 inputs can be individually activated by input control devices. And with the system’s superior design flexibility, there can be as few as one or as many as 48 inputs per zone. If your objective is to reduce energy costs and take advantage of remote low voltage switching, the POWERLINK system input expansion cabinet is your best solution.
POWERLINK AS COMPONENTS system. It’s a simple and low cost way to multiply your system’s capabilities.
AS48EXP • Input/output expansion cabinet • Accepts (2) AS24IN and (1) AS42OUT modules • Sources control power for dry contact type inputs and outputs AS24IN • Provides for 24 additional 2-wire maintained or 3-wire momentary contact inputs AS48OUT • Provides for 42 additional outputs • 115 mA maximum current per output • Total current load not to exceed 1.65 A on all outputs
36
SQUARE D
9/98
Page 36
Accessories Input Expansion Cabinet SELECTION DATA Description
Catalog Number
Input Expansion Chassis, accepts up to two AS24IN and one AS42OUT Modules
AS48EXP*
Input Module, contains provisions for 24 inputs
AS24IN**
Output Module, contains provisions for 42 outputs
AS42OUT
Expander Enclosure
MH26-BEPL
Surface Cover for AS48EXP
MHC26PL-S
Flush Cover for AS48EXP
MHC26PL-F
* Input Expansion Cabinet includes power supply, interior, and serial communication board for connection to the power interface module.
** AS24IN accepts either 2-wire maintained, 2-wire momentary, or 3-wire momentary input signals.
Selection Criteria Mounting Options • Expander can be mounted as a stand-alone cabinet up to 50 feet away from a POWERLINK panel. • Expander can also be mounted directly above or below the POWERLINK panel. Covers • Choice of flush or surface covers Modular Construction • Allows unit to be configured as needed. Either one or two input modules and be provided for 24 or 48 inputs. • Optional output card can also be easily installed. POWERLINK Input Expansion Cabinet Enclosure Dimensions NEMA Type 1 Enclosure (Indoor) W
H
D
20*
26*
5.75*
* Dimensions in inches
SQUARE D
9/98
37
Page 37
Network Options General Information Individual POWERLINK AS panelboards can be easily integrated into a single system, using a variety of flexible network options. Such systems combine the power of network communications with personal computers to provide centralized setup, monitoring, and control. POWERLINK AS panelboards can easily be integrated with Square D POWERLOGIC circuit monitors to form a complete power monitoring and control system. In addition, a number of third party building automation companies, including Honeywell, Johnson Controls, Landis & Stafa, and Siebe, have developed interface modules that will allow POWERLINK panels to be remotely operated directly from their systems.
Figure 8 - Configuration example: POWERLINK lighting control system using RS-485
Square D panelboards are designed to operate using either of two distinct protocols. The POWERLOGIC network provides an excellent system for controlling POWERLINK panels from Square D Circuit Manager or System Manager software. POWERLOGIC networks can support both POWERLINK AS panelboards and other POWERLOGIC compatible products. For additional information on POWERLOGIC networks, refer to the Power Monitoring and Control System Planning Guide Bulletin #3000CT9601. The POWERLINK AS lighting control system offers connection to Ethernet TCP/IP networks to make lighting control available over new and existing local and wide area networks. From a central location, you can now better manage your energy cost using Ethernet technology as well as the internet. Additional information on using Ethernet networks can be found in the Power Monitoring and Control System Catalog Bulletin 3000CT9701.
Figure 9 - Configuration example: POWERLINK lighting control system using Ethernet
The POWERLINK AS system also supports LONWORKS communications. This peer-to-peer protocol is quickly becoming the industry standard for building controls, as it ensures system flexibility and interoperability between devices connected to the network. Refer to page 39 for additional information on the LonWorks Gateway.
38
SQUARE D
9/98
Page 38
Network Options LonWorks Gateway What is LONWORKS? LONWORKS represents the future of field bus communication between intelligent devices. Past means of communicating between devices were usually developed by manufacturers of specific hardware products, and were highly proprietary. Equipment from one manufacturer usually could not communicate well with equipment made by another. In addition, older protocols were generally slow and often did not allow different pieces of equipment to communicate directly with each other as peers. In contrast, LONWORKS was independently developed and is completely open to all manufacturers. And LONWORKS takes advantage of the latest technology to provide high-speed, peer-to-peer communications.
LONWORKS Communication Module
The high speed peer-
The open LONWORKS protocol allows users to select and integrate the best equipment from each manufacturer. It allows manufacturers to concentrate on their expertise, rather than be diverted making proprietary interfaces, modems, and software.
LONWORKS Connections to-peer nature of
All new and existing POWERLINK AS panels can operate with the LONWORKS communication module, which connects directly to the POWERLINK AS power interface module’s RS-232 expander port. A POWERLINK AS control module may be needed for panel setup, but not for routine operation with LONWORKS.
LONWORKS makes many things possible. For example, an input
Network Setup/Programming switch in one panel
Logically connecting I/O and circuit breakers in different panels or devices is done through a process called “binding.” This process is accomplished using any number of third party software tools.
can control circuit breakers in any panel
Setup and programming within a POWERLINK AS panel is still performed using POWERLINK PLK-101 or CMS 1000 software, or the optional display control module.
on the network. A time-of-day control can control breakers
POWERLINK AS panels equipped for network communication can use the network for monitoring and programming while connected to LONWORKS for control.
in many panels. And
Configuration module in one panel
The remote-control circuit breakers and dry-contact switch inputs of the POWERLINK AS system are available for use as LONWORKS objects through the POWERLINK AS-to-LONWORKS network interface.
third party I/O and software can interface directly with POWERLINK AS inputs and breakers.
SELECTION DATA Description
Catalog Number
LONWORKS Communication Module
ASLCM-F
SQUARE D
9/98
39
Page 39
Software Overview POWERLINK AS software makes controlling lighting and power intuitive and easy to understand. From small, stand-alone applications to complete power monitoring and control installations, graphical software from Square D helps you save time and money.
Ease of Use The two levels of POWERLINK AS system software are PLK 101 or Circuit Manager Software (CMS). Simple point-and-click icons and graphical panels mean that you do not need to understand lighting industry jargon. Just change the picture until it shows what you want to happen.
Point-and-click graphical screens make programming a cinch, especially for nonexperts.
POWERLINK AS software runs on a personal computer under either Windows® 3.1, 95, 98, or NT. A cable that comes with the software is used to connect the serial port of the PC directly to a control module’s RS-232 port. Or, for larger systems, the PC can be connected to the panels via a POWERLOGIC network. Of the two software platforms, CMS offers the more advanced functionality. CMS features allow you to: • View multiple panelboards simultaneously • Use system approach to panelboard setup • Remotely verify circuit breaker status • Remotely override circuit breakers and zones • Globally synchronize time clocks • Print panel schedules and directory cards • Enter password protection
Documenting Your Work Better than being there! Monitor circuit breaker, input, and panel status from a remote PC with CircuitManager or PLK software. Operate single circuit breakers or entire zones for temporary or permanent changes.
A practical problem with traditional hardwired control is that the wiring diagrams become lost or out of date. When changes later need to be made, the wiring must then be hand traced - or, in frustration, ripped out and new wiring installed. POWERLINK AS lets you leave those days behind. Square D software lets you save all of your panel configurations on a floppy disk. In addition, CircuitManager software can print out your programs, panel schedules, and more. Lost your program? No problem; just connect your PC to the panel and download it all. Because POWERLINK AS is completely integrated, there is a single panel schedule and control setup. POWERLINK AS offers the most programming options. Desktop mode allows programming to be done in the comfort of an office, with the module and program later snapped into place.
CircuitManager software allows you to print out all of your panel schedules, and system configuration information. In addition, PLK and CircuitManager software can store all of your data on a floppy disk.
40
SQUARE D
9/98
Page 40
Software Features (PLK/CMS) Software Feature Comparison Features
CircuitManager System Manager
PLK-101
Program panel
✔
✔
Future Version
Panel diagnostics
✔
✔
Future Version
Save programs on disk
✔
✔
Future Version
Print programs and schedules
✔
Future Version
Synchronize panel clocks
✔
Future Version
Monitor status
✔
✔
✔
Operate circuits
✔
✔
✔
Password protection
✔
✔
Multipanel systems
✔
✔
Integrate POWERLOGIC data
✔
Event Logging
✔
Alarms
✔ ✔
Custom graphics
System Requirements Operating system Operating System
PLK-101 Windows 3.1 Windows 95
RAM
Windows 95
VGA
VGA
VGA
VGA [Super VGA]
386 [486]
386 [486]
386 [486]
Pentium
4M [8M] 5M free space
4M [8M]
32M
5M free space
500M †
4M [8M] 5M free space
Hard Disk
Windows NT
Windows 95
Display Mode Model
Windows 3.1 System Windows 3.1 WindowsSystem 3.1 Windows 95 CircuitManager Manager Manager® Windows 95 Windows 95 Windows NT SMS-770 3000 (different versions) Windows 3.1 Windows 3.1
SY/LINK Card optional optional optional optional
RS-232 Port required required required required optional optional required required required required
Sound Card 3.5" Drive
Order Information Class
Type
Description
3080 3080 3080 3080 3080
PLK-101 CMS-1000 SMS-770 GFX-700 SMS-3000
POWERLINK AS Communications Software CircuitManager Software POWERLOGIC System Manager Software POWERLOGIC Interactive Graphics Module POWERLOGIC System Manager 3000 Software
SQUARE D
9/98
41