1 Planning the Installation

TSX 17 Micro-PLC Description (Cont'd)

PLC status display

7 [esoocococcc[g soe]

FS SSSST SOOO OOOS

The results of the background self-tests that are run continually by the basic PLC units are displayed on the front panel by four LED indicators.

@ Indicator on CS) Indicator blinking ~ “e PLC running PLC stopped CPU PROG e@ r) CPU fault Program watchdog fault vo MEM @ e I/O fault RAM memory fault BATT r @) Battery fault

I/O status display

355000500000 0008

In addition to providing a continuous display of the status of the inputs, two output status display functions are also available, depending on the state of system bit SY14 and on the programming language used.

State of PL7-1 language PL7-2 language SY 14 0 Display the status of the outputs. (default state) 1 Display the state of Display the contents internal bits: of word SW16 on B248 to B255 on TSX 172 2012/4012 TSX 171 2028/2002 TSX 172 2028/3428 B240 to B255 on TSX 171 4002 - TSX 172 2044/3444 TSX 172 2012/4012/171 3428 TSX 172 2028/3428 TSX 172 2044/3444 ‘SORTIES OUTPUTS, SORTIES OUTPUTS, or123 4567 o123 43867, - & o12345678 90 o1234567890N ENTREES INPUTS ENTREES INPUTS TSX 171 2028/2002 TSX 172 2012/2028/2044 SORTIES OUTPUTS, ‘SORTIES OUTPUTS, 9123 45687 89011 pac] O123 4567 8901 paws fo) 9123465678 9 0 1 12:13 14 15 6 17 18 19 20 21 012345678 9 0 11 12 19 16 15 16 17 18 19 20 21 22 23 ENTREES INPUTS ENTREES, INPUTS:

TSX 171 3428 - TSX 172 3428/3444

TSX 171 4002 - TSX 172 4012 ani

Page 12 read from a scan by OCR; it may hold reading errors

1. Planning the Installation

TSX 17 Micro-PLC Description (Cont'd)

1/O status display (cont’d) Elements | Status |Language}0123 4567 891011 12131415 displayed | SY14 (1) Outputs [0 PL7-1 00,00-- 00,04-- 00,08-- 00,12-- PL7-2 Internal 1 PL7-1 B255-- B251-- B247-- B243-- bits Word 1 PL7-2 4th 3rd 2nd 1st SY16 nibble, _ nibble nibble nibble

(1) The state of system bit SY 14 is displayed on the front panel by the MD indicator: SY14 = 0 MD indicator off (state taken by default), SY14 = 1 MD indicator on.

TSX 17 ACC 2 - Digital display module for use with the basic TSX 17-20 PLC, for PL7-2 language programming

This display module is plugged in as a : Orz se SS TES ON RBM IS direct replacement for the standard

SORTIES OUTPUTS, display module fitted to the TSX 17-20. In addition to the 1/O status display, this module comprises a 4 digit BCD display showing the content of word SW 16, if SY 14=1.

DSTOSSSSOO OOO OCS

ENTREES INPUTS

0123.45 6 7 8 9 10 It 12 13 14 1h 6 17 18 19 20 21 2223

Depending on the program, the content displayed can be the value of a counter, timer, step number, etc. (refer to the example in sub-section 7-2).

SY 14 status | 4 digit display Output status display 0 Inactive Active 1 Active Inactive Fitting the display module

@ Use a screwdriver to remove the @ Insert the digital display unit and original display unit. press down firmly.

These steps should only be performed with the PLC powered-down. |

12

Page 13 read from a scan by OCR; it may hold reading errors

1 Planning the Installation

1.2 Discrete |/O Extension Blocks

TSX DMF 342 A extension block 34 discrete I/O, 24VDC inputs, relay outputs. AC power supply.

This extension block comprises:

e a 110/240VAC power supply @ that provides a 24VDC, 250mA sensor supply output @),

© 34 discrete I/O with a front panel status display ©, - 22 isolated 24VDC inputs ©, - 12relay outputs @,

© an/|/O bus connection or extension block fault LED © e a15-pin I/O bus input connector ©, e a9-pin I/O bus output connector ®, e 2 removable terminal blocks with captive screw-terminals ®, © aground connector @,

Maximum extension configurations: e 2 extension blocks on a TSX 17-10 or TSX 17-20 using PL7-1 language, e 3 extension blocks on a TSX 17-20 using PL7-2 language.

* Refer to the compatibility rules on page 28.

9 1 @® 6 =, > elelelelelelelelslelelelslelelelelelaleleloleis®

{ik CALEEEEeeEe APPS Slelolelo|SiG|@|@ @ TL. \ _V 5 5S is era of ED)

13

Page 14 read from a scan by OCR; it may hold reading errors

1 Planning the Installation

Discrete I/O Extension Blocks (Cont’d)

TSX DMF 344 A extension block 34 discrete I/O, 110VAC inputs, relay outputs. AC power supply.

This extension block comprises:

© a 110/240VAC power supply @ that provides a 24VDC, 250mA sensor supply output @,

34 discrete 1/O with a front panel status display ©, - 22 isolated 110VAC inputs ©, ~ 12 relay outputs @, an I/O bus connection or extension block fault LED ©, a 15-pin I/O bus input connector ©, a 9-pin I/O bus output connector @, e 2 removable terminal blocks with captive screw-terminals ©), ® aground connector ©,

® acommon 110VAC input supply terminal ©,

Maximum extension configurations: @ 2 extension blocks on a TSX 17-10 or TSX 17-20 using PL7-1 language, © 3 extension blocks on a TSX 17-20 using PL7-2 language.

Refer to the compatibility rules on page 28.

14

Page 15 read from a scan by OCR; it may hold reading errors

4 Planning the Installation

Discrete 1/O Extension Blocks (Cont'd)

TSX DMF 400 - TSX DMF 401 extension blocks 40 discrete I/O, 24VDC inputs, transistor outputs. DC power supply. These extension blocks comprise:

two screw terminals for connecting a 24VDC power supply input @, e 40 discrete |/O with a front panel status display ©,

Extension 24 VDC inputs @ Transistor outputs @ blocks not isolated not isolated isolated isolated not protected| protected 1&2A 0.35A TSX DMF 400 24 - 16@ - TSX DMF 401 - 24 - 16

(1) points 0 to 3 (4 outputs): 2 amps, points 4 to 15 (12 outputs): 1 amp.

e anl/O bus connection or extension block fault LED ©, e a15-pin 1/O bus input connector ©, - e a9-pin I/O bus output connector ®, e 2 removable terminal blocks with captive screw-terminals © aground connector ©.

Maximum extension configurations: e 2 extension blocks on a TSX 17-10 or TSX 17-20 using PL7-1 language, e 3 extension blocks on a TSX 17-20 using PL7-2 language.

Refer to the compatibility rules on page 28.

9 $8 6

A LO AN

Oo slelelolaseeelelelslelslelelesleleleleieS 0), SACEEREReE DOS PAS|AWNS| PSM i

‘ sb

16

Page 16 read from a scan by OCR; it may hold reading errors

1. Planning the Installation

1.3 Discrete I/O Extension Modules

Extension modules - 8 discrete inputs or 6 discrete outputs TSX DEF 812 - TSX DEF 804 input modules

These modules comprise:

© 8isolated 24VDC inputs @ and @ with a front panel status display ©,

Modules Isolated inputs 24VDC 110VAC

TSX DEF 812 8 -

TSX DEF 804 - 8

¢@ a9-pin!/O bus input connector and its cable © to connect to the previous module,

@ a9-pin I/O bus output connector and its cable @ to connect to the next module, aground connector ©,

Maximum extension configurations:

© 2 extension modules on a TSX 17-10 or TSX 17-20 using PL7-1 language,

© 3 extension modules on a TSX 17-20 using PL7-2 language,

Refer to the compatibility rules on page 28.

TSX DSF 635 - TSX DSF 612 - TSX DSF 604 Output modules |

These modules comprise:

© 6 relay outputs @ and @ with a front panel status display ©, .

Modules Isolated outputs with Relays | Transistors,| Triacs| (protected 0.35A) TSX DSF 635 6 - - TSX DSF 612 - 6 - TSX DSF 604 - - 6

© a9-pin|/O bus input connector and its cable © to connect to the previous module, e a9-pin I/O bus output connector and its cable @ to connect to the next module,

® aground connector ©, Maximum extension configurations:

e 2 extension modules on a TSX 17-10 or TSX 17-20 using PL7-1,

© 3 extension modules on a TSX 17-20 using PL7-2 language.

Refer to the compatibility rules on page 28.

Page 17 read from a scan by OCR; it may hold reading errors

1 Planning the Installation

1.4 Mains Power Break/Return

Consequences of a Mains Break

The effect of a mains power break/return on TSX 17 PLCs is described in the PL7-1 Summary (TSX D12011E) and PL7-2 Summary (TSX D12002E) manuals. The table below summarizes the consequences of a power break/return depending on:

© whether or not the processor monitors the sensor power supply,

¢ the duration of the power break. If the duration of the power break is less than the autonomy of the power supply module, the PLC will continue to execute its program normally and to acquire inputs and update outputs.

Depending on the type of power break/return, even if the context is coherent, the user should for application safety reasons, ensure that the processor has not received any wrong inputs caused by the power break. This situation can occur when the processor is still running on its own autonomy while power supply to sensors has been lost. The table below summarizes the various situations:

Basic PLC Sensor PLC supply Hot restart with type supply autonomy input state errors Type 1 Built-in and 10 to 50 ms at No danger of 24 VDC inputs, monitored by 110 V rated input errors: 110/240 VAC mains CPU bit Sx,1 20 to 50 ms at sensor supply 220 V rated exceeds auto- nomy. Type 2 Not built-in, but | 10 to 35 ms at Danger of errors 24 VDC inputs, monitored by 24 V rated occuring on loss 24 VDC supply CPU bit Sx,1 of 24 VDC supply. Type 3 Not built-in and | 35 to 80 ms at Danger of error 110 VAC inputs, not monitored by] 110 V rated occuring on loss 110/220 VAC mains the CPU 50 to 75 ms at of 110 VAC 220 V rated supply.

Hot Restart with the Danger of Input Errors (Types 2 and 3)

On hot restart, the danger of input errors (input at 0 instead of 1 for example), is compatible with the level of safety required by the application. To avoid this danger, the PLC mustbe initialized at the start of its program by setting the cold restart bit SY00 to 1 and the output reset bit SY09 to 1. Refer to the examples on the next page.

Programming hint: To limit the danger of input errors after a hot restart, ensure that the automated system is only triggered by inputs at 1 (on rising edge).

17

Page 18 read from a scan by OCR; it may hold reading errors

Planning the Installation

Mains Power Break/Return (Cont'd)

PL7-1 Hot Restart Programming (for Types 2 and 3) S000 LSYO1_ if SY01 (hot restart), then set:

$001 S$ SY00 ¢ SY00 to 1 to perform a cold restart, $002 =SY09 e SY09 to hold the outputs at 0.

Bits SYOO and SYO9 are reset to 0 by the system at the end of the next cycle.

PL7-2 Hot Restart Programming (for Types 2 and 3)

L syo1 Sy00 g + {s Label LOOO: Ist. 0 contact network of the program. syo9 The same system bits are used as above.

Consequences of a Cold Restart

© All internal bits and /O bits are set to 0,

© Resetting to 0 of the current values of functions (PL7-1) and function blocks Ti,V, Mi,V, Ci,V etc. (PL7-2),

© Loss of function block values that had been modified by the terminal of the program. These blocks (Ti,P, Mi,P, Ci,P TXTix, etc.) return to their preset value defined in the configuration and (in PL7-2), internal words Wi and active time counters Xi,V and Di,V are reset to 0,

Reinitialization of registers, step counters and drum controllers, e Reinitialization the Grafcet (activation of initial steps),

© Cancellation of forced bits and breakpoints, e Execution restarts at the start of the scan cycle (inputs, program, outputs) and SYOO is reset to 0 by the system.

Constant words CWi and reai-time clock parameters are not changed.

e Important: Industrial safety standards require that the restarting of the system after a mains power break, must be manually initiated by the operator. By slaving the power supplies as described previously, these standards can be met.

Acold restart usually requires returning the physical part of the application to its initial position (either manually of automatically). This procedure is not detailed in this manual.

18

Page 19 read from a scan by OCR; it may hold reading errors

1. Planning the Installation

1.5 Catalog Information (Accessories)

Intelligent Modules for TSX 17 Micro-PLCs

Ref. No. Purpose : Manual Language TSX DTF 400 4 analog timers TSX D12010E (PL7-1) TSX D12005E (PL7-2) TSX AEG 4110 4+10 V analog TSX D12005E (PL7-2) inputs TSX AEG 4111 44-20 mAanalog TSX D12005E (PL7-2) inputs : TSX ASG 2000 2 +10 V analog TSX D12005E (PL7-2) outputs TSX ASG 2001 24-20 mAanalog TSX D12005E (PL7-2) outputs TSX 17 ACCS Uni-Telway (slave) TSX D24006E (PL7-2) : adapter TSX SCG 116 Uni-Telway (master/ TSX D24007E (PL7-2) (under development) slave) module TSX SCG 113 1 channel, TSX D23009E (PL7-2) (under development) asynchronous serial communication module

PL7-2 Software cartridge

Ref. No. Function

TSX P17 20 FA("*) Enables the programming of TSX 17-20 PLCs in PL7-2 programming language TSX P17 20 FB(*) Identical to TSX P17 20 FA with Clock/Calendar function

Memory storage / Ref. No. Type Storage TSX MC70 E38 8K byte EEPROM User program (1K instructions in PL7-1) TSX MC70 E324 24K byte EEPROM User program (3K instructions in PL7-1) TSX MC70 E28 8K byte EEPROM User program » (1K instructions in PL7-1) TSX MC70 E224 24K byte EEPROM User program (*) ; (3K instructions in PL7-1) TSX 17 ACC1 Lithium battery User program, 1 year service life("") real-time clock/calendar Cables and Accessories Ref. No. Type Length TSX CBB 003 Connection to DMF.. extension 0.32 meter TSX CBB 009 Connection to DMF.. extension 0.90 meter TSX CBB 016 Connection to DMF.. extension 1.60 meter TSX CCB 020(*) Fast counter connection cable 2 meter TSX 17 ACC10 End of line adapter

(*) For TSX 17-20 PLCs only, ("*) 2year service life if the surrounding temperature does not exceed 40 degrees C.

19

Page 20 read from a scan by OCR; it may hold reading errors

1 Planning the Installation

1.6 Specific 1/O

Input/Output: Run/Stop - Alarm

A feature of the TSX 17 basic PLC allows input 10,00 and output 00,00 to each be assigned a specific function.

Of [ooo teeny eo

OER

Run/Stop input: [0,00

Normal (nor): Operates in the same way as all other basic PLC discrete inputs. Run/Stop (R/S): e at 1 this input sets the PLC to Run,

© at 0 this input sets the PLC to Stop.

The actual Run/Stop input on the PLC has priority over a Run/Stop from a connected terminal.

Alarm output: 00,00

Normal (nor): Operates in the same way as all other basic PLC discrete : inputs. Alarm: © at 1 if the PLC is Running with no faults, © at 0 if the PLC is Stopped or Running but a fault is present.

Output 00,00 is used for safety systems that are external to the PLC. It can be used to cut-off the power to PLC outputs (refer to Sub-section 3.1).

Configuration of the specific I/O

Input 10,00 and output 00,00 are configured by default to normal mode. These I/O can be configured separately and respectively for Run/Stop and Safety modes using the terminal (in Configuration mode).

1.7 PL7-2 Software Cartridges

These cartridges can only be used in TSX 17-20'micro-PLCs and are required for PL7-2 language programming.

The user has a choice of two cartridges:

TSX P17 20 FA TSX P17 20 FB e _ - - | | aE Vv Vv PL7-2 language only PL7-2 language with Clock/Calendar function Inserting the cartridge

Cartridges should only be inserted when the PLC is powered-down.

Remove the factory fitted slot cover and insert the cartridge, pressing it firmly home and close the removal tab/cover.