1 Planning the Installation

1.8 Saving Programs and Data

If a power break occurs, the contents of the RAM memory of the micro-PLC (program, data and clock/calendar information) is retained for at least 1 hour. There are three ways of saving this data for longer periods: EEPROM and EPROM memory cartridges and a lithium battery.

EEPROM memory cartridges TSX MC70 E324 24K bytes Data storage life: Permanent Type of data stored: Program and configuration Installing the cartridge

[ Cartridges should only be inserted when the PLC is powered-down. |

Remove the factory fitted slot cover and insert the cartridge, pressing it firmly home and closing the removal tab/cover.

¢ Cartridge description: The user can select the required mode of operation by setting a two position micro switch @: l Os) EEPROM Oo? Saka © Cartridge Write/Read work Set the micro switch @ to the Work position for use when debugging the O- am program and writing to the cartridge.

e Cartridge Read Only Set the micro switch @ to the Master (Read Only) position to use a definitive stored program.

co

> EEPROM e Write/Read mode: The transfer from the PLC RAM to a EEPROM or from EEPROM to PLC RAM OCRESYESeereererrend always takes place with the cartridge ISX, PRM fitted in the PLC and the micro switch @ wena? ees [ - ] < - - + E#PROM| set to the Work position.

The transfer execution command is sent from a terminal in Transfer mode.

DodOGD0GG C00 Oo 900000000 000 000 000000000 000 0 000000000 000 000

1317 7 407 or T 607 V>3.1 e Using the cartridge to store a Program

Once the program has been transferred to the cartridge, move the micro switch @ left to the Master position.

In this position, whenever a power return occurs, the content of the memory cartridge is automatically transferred to the RAM memory of the PLC, if the content of the PLC RAM is different from the EEPROM.

Note: The EEPROM memory comprises the configuration and the user program. Data is always stored in the RAM memory of the PLC.

21

Page 22 read from a scan by OCR; it may hold reading errors

1 Planning the Installation

Saving Programs and Data (Cont'd)

EEPROM memory cartridges a "F5SSS55O OOO OOOO

Ref. No.: TSX MC70 E38 8K bytes TSX MC70 E324 24K bytes Data storage life: Permanent

Type of data stored: Program and configuration

Installing the cartridge

| Cartridges should only be inserted when the PLC is powered-down.

Remove the factory fitted slot cover and insert the cartridge, pressing it firmly home and closing the removal tab/cover.

Writing to the EPROM cartridge:

In PL7-1 language In PL7-2 language jal OCEXEEXXEESSEES EOE E ro-1 TSX t Internal Internal, » PLC RAM EN imternal Pr rexxirn > EEEXXKEND

TSX 17 ACCT 4)

CART. r=" internal T407 [ssi | | EPROM

1407 or T607 V>3.1 TSX 17 ACC6

Transfer from the PLC RAM memory to the EPROM is always performed with the cartridge fitted in the TSX 17 ACC6 adaptor and controlled by the TSX 1407 terminal in Transfer mode.

EPROM

7407 or T607 V>3.1 TSX 17 ACC6

Reading from the EPROM cartridge:

With the cartridge fitted in the TSX 17 ACC6 adaptor and controlled by a terminal in Transfer mode.

PL7-1 language PL7-2 language ‘al fal | CXEXEXEKERCEEEEEEOE) E fo CXEXESERESERESEEEE E =--1 TSX t - =1 TSX Internal, » igi Internal, - p» PLC RAM oo ~y PLC RAM 1h) ~\ CRREXEXEXES bE rE bpetesssse> Sct r TSX 17 ACC7 4

TSX 17 ACC7 i

[F=="tnternal T407 RAM

CART.

fq] EPROM

T 407 or T 607 V>3.1 TSX 17 ACC6

' ' EPROM bed

T 407 or T607 V>3.1 TSX 17 ACC6

22

Page 23 read from a scan by OCR; it may hold reading errors

1 Planning the Installation

Saving Programs and Data (Cont'd)

With the cartridge fitted in the PLC, controlled by terminal in Transfer mode.

PL7-1 language PL7-2 lanquage [-] - OOESESEEererIserres 3 “TSX, PRM internal, > |! | =) L EPROM Internal, > || EPROM

TSX 17 ACC7 TSX 17 ACC7 ooo Soooe 800 o lo00000000 000 000 000000000 000 000 900000000 000 0 lo00000000 000 0 log0e00000 000 000 1090000000 900 000.

1317 1407 or T607 V>3.1 1407 or T607 V>3.1 Reading programs stored in the cartridge:

Each time the PLC is powered-up (or on power return), the content of the memory cartridge is automatically transferred to the RAM memory of the PLC, if the content of the two memories are different.

Note: ¢ The EPROM memory is used to store the configuration and the user program. Data is always stored in the RAM memory of the PLC.

¢ An EPROM memory cartridge is erased using a TSX EPE1/EPE2 UV cartridge eraser.

Lithium battery fsessssossssasseq Ref. No. TSX 17 ACC1 Data storage life: 1 year(*) SSSSSSESSSOSS Type of data stored: Program, data and clock/calendar information.

. IIIA

EEO

(*) The battery life can be longer if the operating temperature OA is less than 40 deg. C (refer to the definition of GA on Page 6/1).

Installing the battery

2) Q @ Release the cover, - > @® Remove the cover Plug-in the battery © Lock the cover @ Fit the batte: ° Re-install the cover

23

Page 24 read from a scan by OCR; it may hold reading errors

1 Planning the Installation

1.9 1/0 Addressing

1/O addressing eAddressing a discrete input or output:

lorO x , i

L Channel number: 00 to 23 for inputs

00 to 15 for outputs

Comma, - > Module number: ¢ 0 to 2 fora TSX 17-10/20 using PL7-1 language, © Oto 3 for a TSX 17-20 using PL7-2 language, 0 for the basic PLC unit, 1 for the 1st extension unit, 2 for the 2nd extension unit, 3 for the 3rd extension unit("*).

U - ______ - _ - _} | (Input) O (Output)

e Addressing the event triggered inputs 10,24 and 10,25, available on TSX 17-20.

Module identification in a TSX 17 configuration

Configuration examples:

= Basic TSX 17PLC. @

= 1st extension unit (extension block or tw © a a a module connected to {L ee the basic PLC).

= 2nd extension unit (extension block or Ko) : module connected to & a the 1st extension).

= 3rd extension unit (extension block or module connected to the 2nd extension).

(*) Only available when using PL7-2 language.

24

Page 25 read from a scan by OCR; it may hold reading errors

2 Mounting

2.1 Building a Configuration

Basic rules n SOTTO OOOO OOOO OS.

BSO5050000000006.

O P5TOSSOOSOOOOOO®

BSTSS OSS SO SO OOOO.

e The basic micro-PLCs can be expanded with: TSX 17-10/20, PL7-1 language: 1 or 2 discrete I/O extension blocks or modules, © TSX 17-20, PL7-2 language: 1, 2 or 3 discrete I/O extension blocks or discrete |/O and analog modules and 1 Uni-Telway module.

Starting with the basic micro-PLC (address 0), discrete I/O and analog extension blocks or modules can be installed in any order.

© Discrete I/O extension blocks: An extension block (address n) is connected to the preceding block or module (address n-1) by a connector cable selected for the installation.

Three different cables are available:

e TSX CBB 003: length 0.32 meters (‘“x” on Pages 26 and 27), e TSX CBB 009: length 0.90 meters (“y” on Pages 26 and 27), e TSX CBB 016: length 1.60 meters (“w” on Page 27).

Caution: The maximum length of the bus extension depends on the number of extensions to connect (refer to the table below for the cables to use).

Extension cables that can be used in a configuration

With 1 ext. block With 2 ext. blocks With 3 ext. blocks 0.32 m 0.32 m +0.32 m 0.32 m +0.32 m +0.32 m 0.90 m 0.32 m +0.90 m 0.32 m +0.32 m +0.90 m 1.60 m 0.32 m +1.60 m 0.32 m +0.32 m +1.60 m 0.90 m +0.90 m 0.32 m +0.90 m +0.90 m

© Discrete 1/O modules: The extension module is connected to the preceding block or module by a built-in cable. Therefore, additional modules are always located to the right of the preceding device,

© Analog extension and analog timer modules: These are installed in the same way as discrete I/O modules. :

¢ Uni-Telway adapter module: This adapter connects to the programming port of the PLC by a 0.90 meter cable (supplied with the adapter). It can be mounted in any position in relation to the basic PLC.

25

Page 26 read from a scan by OCR; it may hold reading errors

2 Mounting

Building a Configuration (Cont’d)

¢ End of line adapter for extension blocks or modules.

Elf The last extension block or module must be fitted with an end of line adapter on the connector located at the lower right of the front panel.

Sp The TSX 17 ACC 10 end of line adapter is supplied separately.

SO950T0050000

All cables (except for the terminal cables) should only be connected or disconnected with the PLC powered-down.

The male connectors on the extension cables and the end of line adapter must be attached to the female connectors on the TSX 17 modules using their retaining screws.

2.2 Configuration Examples

Example 1: TSX 17-10 Example 2: TSX 17-20 - PL7-2 mabnian on nnaacaanear | fg. (olsartetetets 2

(REE ETAT

26

Page 27 read from a scan by OCR; it may hold reading errors

2 Mounting

Configuration Examples (Cont’d)

Example 4: TSX 17-20 - PL7-2 Example 5: TSX 17-20 - PL7-2

\ x< W

TSX CBB 003 cable, length 0.32 meters,

TSX CBB 009 cable, length 0.90 meters,

< i)

= u

TSX CBB 016 cable, length 1.60 meters,

N Ul}

TSX 17 ACC 10 end of line adapter, supplied separately,

27

Page 28 read from a scan by OCR; it may hold reading errors

2 Mounting

2.3. Basic PLC/Extension Compatibility

The TSX 17 compatibility table below shows which units and modules can be used together to build complete configurations. All configurations used must follow the guidelines given in the table to ensure optimum performance from all operational features. In addition, this ensures that isolation standards are met and power supply load levels not exceeded.

Basic Max. | Discrete 1/0 Discrete and analog UNI micro- & of. ext. blocks 1/0 ext. modules TEL- F exten saan DMF DEF soo DTF | AEG | ASG | WAY S| © [g42a} 400 | 401 | 812 | 612 | 635 | 400. | 411. | 200. Jaccsl TSX 171 2028 TSX 171 3428 |PL71] 2 | X X)X |X| xX) xX TSX 171 2002 |PL7-1| 2 X;|XIX {XxX x TSX 171 4002 |PL7-1] 2 X|Xi1X]XxX{xX x PL7-1| 2 xX X|X)X]X/]X TSX 172 2028 TSX 172 2044 x |x PL7-2] 3 x X|XiX]xX}xX 1x (4) | 3) PL7-1| 2 » 4 X|XI]XI]xX]xX TSX 172 2012 x PL7-2] 3 4 X|X}]XI1X]xX|xX] xX (3) PL7-1| 2 xX XiX1X]X]xX 4 xX |X PL7-2| 3 Xx xX |X]X x |X (2) (4) | (3) PL7-1] 2 x X|X]xX1X]xX TSX 172 4012 x PL7-2| 3 4 X|X/]X]xX}]X]x]xX (3)

(1) Except for the TSX ACC 5 Uni-Telway communication module,

(2) The maximum number of TSX DSF 635 modules is restricted to 2,

(3) One module per basic PLC.

(4) The 24VDC sensor supply from the basic PLC can only be used to by one extension module. If more than one extension module is installed, an external 24VDC power supply must be used.

can be used together

[| cannot be used together

28

Page 29 read from a scan by OCR; it may hold reading errors

2 Mounting

2.4 Dimensions

Basic PLCs

TSX 171 2028 J TSX 171 2002

0000 100

185 NN 4 holes 5 mm dia.

110 (x)

r

TSX 172 2028 J ° elaigiaisia! BES B 2 TSX 172 2044 TSX 171 3428 TSX 172 3428 TSX 172 3444 TSX 172 2012 TSX 171 4002 a TSX 172 4012

°

100 yy

140 (*) t 270

Extension blocks

TSX DMF 3424 TSX DMF 3444

TSX DMF 400 TSX DMF 401

110 (*)

Extension modules 8 Mounting dimensions ~ BB slice enlarged view of A

12

2

TSX DEF 804 roy TSX DEF 812 TSX DSF 604 [

112 a | a 100

TSX DSF 635 TSX DSF 612 TSX DTF 400

TSX AEG 41. AN Boo AB TSX ASG 20.. 4

TSX 17 ACCS 122 40

(") 122 mm with connector (TSX CBB extension cable or TSX 17 ACCS end of line adapter).

All dimensions given in mm.

29

Page 30 read from a scan by OCR; it may hold reading errors

2 Mounting

2.5 Mounting Considerations

On AM1-BA slotted plate On 2000 mm zinc-chromed rails

137 (») 125,

=:

Mounting by 04 screws Mounting by 04 screws Slot-in mounting. @ M4 clip-on nut AF1-EA4 @ 35mm wide combined rail AM1-ED200 with nut AF1-CF34 M4x16 AF1-VA416_ screws and M4 x 16 screw AF1-VA416 with captive washer @ 35mmwide omega rail AM1-DE200 with nut AF1-CG4 and (*) Dimensions of the basic PLC or M4 x 16 crew AF1-VA416 extension block with TSX CBB - @) 32 mm asymmetrical rail DZ5-MB201 with nut DZ5-ME8 cable. Dimensions of TSX DEF, DSF, DTF, AEG, ASG, 17 ACC5 modules. and M4 x 16 screw AF1-VA416.

| Always ensure that the 4 mm dia. mounting screws are fitted with flat washers.

Mounting guidelines

@® Other device, enclosure or machine frame

® Cable duct or guide

@ Leave approx. 20 to 30 mm slack in the cabling to allow forinserting and removing the terminal block.

Important

Avoid locating the extension blocks or modules above other heat generating devices (transformers, power supplies, contactors, etc.).

30