Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of TSX 17 Micro-PLC Installation Manual

Manual · Schneider

TSX 17 Micro-PLC Installation Manual

Manual70 pagesPDF 4.4 MB

Installation manual for TSX 17-10 and TSX 17-20 Micro-PLCs, including the TSX 172 3444 and TSX DMF 401 extension block.

Download the PDF4.4 MB

Covers · 6 models

The models it covers

Summary

What is in it

Installation manual for the TSX 17 Micro-PLC family: TSX 17-10 and TSX 17-20 base units, discrete I/O extension blocks such as the TSX DMF 400 and TSX DMF 401, and extension modules. It covers planning, I/O addressing, mounting and dimensions, wiring of power supplies, inputs and outputs, event-triggered inputs and the fast counter, power-up and troubleshooting with the indicator lights, technical characteristics and service conditions. Short sections cover the TSX 17B 1428 BATIBUS PLC and TSX DMF 242A extension. The text is OCR.

Its parts

  1. 1 Planning the Installation
  2. 2 Mounting
  3. 3 Wiring
  4. 4 Setting into Service - Maintenance
  5. 5 Technical Characteristics
  6. 6 Service Conditions
  7. 7 Appendix
  8. TSX 17B 1428 BATIBUS
  9. TSX DMF 242A I/O Extension for TSX 17

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

This is the TSX 17 Micro-PLC Installation Manual for the Telemecanique TSX 17-10 and TSX 17-20 micro-PLCs, their discrete I/O extension blocks and modules, and the analog and Uni-Telway modules. It walks through planning, mounting, wiring, first power-up, troubleshooting with the indicator lights, and the technical and service specifications. The site files it under the TSX172-3444 basic PLC and the TSX DMF 401 extension block.

Read for this summary: pages 1 to 4, 9, 13, 15, 19, 25, 28 to 29, 36, 39, 47 to 49, 51 to 54 and 59 to 61 of 70.

TSX172-3444 I/O
TSX172-3444: basic TSX 17-20 micro-PLC with 34 discrete I/O: 22 isolated 110VAC inputs, 12 relay outputs p. 9, 36
TSX172-3444 power
TSX172-3444: 110/240VAC power supply with a 24VDC, 250mA sensor supply output p. 9
TSX172-3444 memory
TSX172-3444: 24K byte internal RAM program memory (and 2K bytes of data in PL7-2), battery backed p. 9
Programming
TSX172-3444: PL7-1, or PL7-2 with the optional TSX P17 20 FA or TSX P17 20 FB software cartridge p. 1, 9, 19
Fast inputs
TSX172-3444: 2 event-triggered 24VDC inputs and a 2KHz fast counter/timer (5/24VDC inputs) p. 9
110VAC inputs
TSX172-3444: 110VAC, 15mA, 50/60Hz; sensor supply 88VAC to 132VAC; response 33ms (0 to 1), 50ms (1 to 0) p. 52
Relay outputs
TSX172-3444: 1 N/O contact per output; AC loads 24 to 240VAC, DC loads 24V p. 54
TSX DMF 401
TSX DMF 401: 40 I/O extension block, 24 isolated 24VDC inputs, 16 isolated protected 0.35A transistor outputs, 24VDC power input p. 15, 39
Fast discharge outputs
TSX DMF 401: outputs 0 and 1 have fast discharge circuits for short response times p. 53
Extension limit
2 extension blocks on a TSX 17-20 using PL7-1, 3 using PL7-2 p. 15
Extension cables
TSX CBB 003 (0.32 m), TSX CBB 009 (0.90 m), TSX CBB 016 (1.60 m); TSX 17 ACC10 end of line adapter p. 19
Memory cartridges
TSX MC70 E38 and TSX MC70 E28: 8K byte EEPROM; TSX MC70 E324 and TSX MC70 E224: 24K byte EEPROM p. 19
Battery
TSX 17 ACC1 lithium battery, 1 year service life p. 19
Environment
Operation 5°C to 55°C (local air); relative humidity 30 to 95% without condensation; altitude 0 to 2000 meters p. 59

What this manual walks you through

  • Building a configuration with extension blocks and cables p. 25
  • Wiring the TSX 172 3444 110VAC inputs and relay outputs p. 36
  • Wiring the TSX DMF 401 inputs and transistor outputs p. 39
  • Powering up the PLC for the first time p. 47
  • Checking the I/O connections from a terminal p. 48
  • Troubleshooting with the indicator lights p. 49
  • Power supply, input and output characteristics p. 51, 52, 53, 54

Good to know

  • Before checking the I/O, remove the motor drive power supply fuses and disconnect pneumatic and hydraulic lines. p. 48
  • The protective cover should be in place during wiring. p. 47
  • The basic PLC's 24VDC sensor supply can serve only one extension module; with more, an external 24VDC supply is needed. p. 28
  • The system designer should add external protective devices against internal active faults in the PLC. p. 61
  • The manual states the TSX 17 conforms to standards including UL 508. p. 59

Questions this manual answers

How many inputs and outputs does the TSX 172 3444 have?

34 discrete I/O: 22 isolated 110VAC inputs and 12 relay outputs. p. 9

What does the I/O/MEM light mean on a TSX 17?

It reports uninitialized memory or an input/output fault. The checks listed include the battery, the extension cables, the end of line adapter on the last extension, and the 24VDC sensor supply. p. 49

Which cartridge is needed to program a TSX 17-20 in PL7-2?

The TSX P17 20 FA, or the TSX P17 20 FB, which adds a clock/calendar function. p. 19

What battery does the TSX 17 use?

The TSX 17 ACC1 lithium battery: 1 year service life, or 2 years if the surrounding temperature does not exceed 40 degrees C. p. 19

How many extension blocks can a TSX 17-20 take?

Two when programmed in PL7-1 language, three in PL7-2. p. 15

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. TSX 17 MICRO-PLC. USER'S MANUAL1
    1. TSX 17 MICRO-PLC1
    2. 1 Planning the installation4
    3. 2 Mounting25
    4. 3 Wiring31
    5. 4 Setting into Service - Maintenance47
    6. 5 Technical Characteristics51
    7. 6 Service Conditions59
    8. 7 Appendix62
  2. TSX 17B 1428 BATIBUS65
    1. 1 Planning the Installation65
    2. 2 Mounting66
    3. 3 Wiring (see Section 3 - TSX D11 000E)67
    4. 4 Setting into Service - Maintenance67
    5. 5 Technical Characteristics67
    6. 6 Service Conditions68
  3. TSX DMF 242A I/O EXTENSION FOR TSX 1769
    1. 1. Planning the Installation69
    2. 2. Mounting69
    3. 3. Wiring70
    4. 4. Setting into Service - Maintenance70
    5. 5. Technical Characteristics70
    6. 6. Service Conditions70

From the PDF’s own bookmarks.

The whole text · 8 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. TSX 17 MICRO-PLC. USER'S MANUAL, pages 1 to 101-10
  2. TSX 17 MICRO-PLC. USER'S MANUAL, pages 11 to 2011-20
  3. TSX 17 MICRO-PLC. USER'S MANUAL, pages 21 to 3021-30
  4. TSX 17 MICRO-PLC. USER'S MANUAL, pages 31 to 4031-40
  5. TSX 17 MICRO-PLC. USER'S MANUAL, pages 41 to 5041-50
  6. TSX 17 MICRO-PLC. USER'S MANUAL, pages 51 to 6051-60
  7. TSX 17 MICRO-PLC. USER'S MANUAL, pages 61 to 6461-64
  8. Pages 65 to 7065-70

The file

Size and text

Pages70
PDF4.4 MB
TextThe pages are scans; their text was read by OCR, which may hold reading errors.

The first pages · 3 of 70

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 70
Page 2
Page 2of 70
Page 3
Page 3of 70

More documents · 1