Manual · Telemecanique
TSX 17 micro-PLCs: TSX 17-10/20 micro-PLCs
Manual12 pagesPDF 194 KB
Catalog pages for the Telemecanique TSX 17-10 and TSX 17-20 micro-PLCs: selection, characteristics, references and wiring.
Names · 3 models
The models it names
Filed with · 3 models
Also filed with these models on the old site
Summary
What is in it
Catalog pages for the Telemecanique TSX 17-10 and TSX 17-20 micro-PLCs and their extensions. They cover model selection, the front panel, memory backup, special I/O, the fast counter and real-time clock, discrete and analog timer extensions, compatibility and layout rules, environment, power supply, input and output characteristics, references with weights, dimensions and mounting, and connection diagrams for PLC bases such as the TSX 172 3444 and the extension blocks.
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
A catalog section for the Telemecanique TSX 17-10 and TSX 17-20 micro-PLCs, their discrete extension blocks and modules, and the TSX DTF 400 analogue timer module. It covers selection, characteristics, order references, dimensions and wiring for these bases, including the TSX 172 3444; it does not describe a TSX 07 PLC. It lets the reader pick a base and extensions, check electrical ratings and wire the terminals.
- TSX 172 3444 I/O
- TSX 172 3444: 110...240 V, 50/60 Hz supply, 22 isolated 110 V inputs, 12 relay outputs p. 12
- Internal memory
- TSX 17-20: 24 K byte internal RAM; TSX 17-10: 8 K byte internal RAM p. 1, 2
- Programming language
- TSX 17-20: PL7-1 Boolean language; PL7-2 by adding a TSX P17 20Ei language cartridge p. 2
- Communication port
- TSX 17-20: RS 485 port for a programming terminal, UNI-TELWAY multidrop bus or communication peripheral p. 2
- Relay outputs
- TSX 172 3444 and the other relay models: 1 N/O contact per channel, 3 A thermal current, 24...240 V loads p. 7
- Operating temperature
- +5 to +55 °C (storage -25 to +70 °C) p. 6
- Memory backup
- TSX 17 ACC 1 lithium battery; RAM backup 2 years with battery, 1 hour without p. 2, 10
- Memory cartridges
- TSX MC70 E38, TSX MC70 E324, TSX MC70 E48, TSX MC70 E424 (EEPROM or EPROM, 8 or 24 K bytes) p. 9
- Extensions
- PL7-1: 2 extension blocks or modules; TSX 17-20 with PL7-2: 3, plus 1 UNI-TELWAY adaptor module p. 5
- Extension cables
- TSX CBB 003 (0.32 m), TSX CBB 009 (0.90 m), TSX CBB 016; total length not over 2.20 m; TSX 17 ACC 10 end of line adaptor p. 5, 10
- Fast counter
- TSX 17-20: 10000 point counter, up to 2 kHz, 24 V or 5 V inputs on a 9-way connector; TSX CCB 020 cable p. 3
- Event-triggered inputs
- TSX 17-20: 2 dedicated 24 V inputs, I0,24 and I0,25, filter under 1 ms p. 3
- Real-time clock
- TSX 17-20 with PL7-2 cartridge TSX P17 20FB/FD1; drift under 4 seconds per day p. 3
- Numerical display
- TSX 17 ACC 2 4-digit display for TSX 17-20 running PL7-2, shows system word SW16 p. 3
What this manual walks you through
- Choosing a TSX 17-10 or TSX 17-20 base by supply, inputs and outputs p. 1, 2
- Using the RUN/STOP input, alarm output, event inputs and fast counter p. 3
- Checking which extension blocks and modules can be combined p. 5
- Laying out extension blocks and connecting cables p. 5
- Setting the TSX DTF 400 analogue timer ranges p. 4, 8
- Input, relay, transistor and triac output ratings p. 6, 7, 8
- Ordering bases, cartridges, extensions and separate parts p. 9, 10
- Wiring power supply, inputs and outputs of the bases and extension blocks p. 11, 12
Good to know
- For outputs not protected against short circuits, fit a fuse in series with each load. p. 11
- Relay outputs: one quick blow fuse of less than 3 A on each output is the recommended external protection. p. 7
- The 24 V sensor supply of a base or block can feed only one extension module; several modules need an external 24 V supply. p. 5
- The last extension block or module must carry a TSX 17 ACC10 end of line adaptor, and the TSX FPG 10 module must always be last. p. 5
Questions this manual answers
What inputs and outputs does the TSX 172 3444 have?
It runs on a 110...240 V supply and has 22 isolated 110 V inputs and 12 relay outputs. p. 12
How much memory does a TSX 17-20 micro-PLC have?
Each TSX 17-20 base has a 24 K byte internal RAM; program backup cartridges hold 8 or 24 K bytes. p. 2
Which battery backs up the TSX 17 memory?
The TSX 17 ACC 1 lithium battery backs up the RAM (program and data). p. 10