5 Technical Characteristics

5.1

Power Supply Characteristics

Power supply for Type basic PLCs and: extensions blocks

TSX 171 2028/3428

TSX 171 2002 TSX 172 2012

TSX 172 2028/2044 TSX 171 4002 TSX 172 4012

TSX 172 3428/3444

TSX DMF 342A/344A TSX DMF 400 TSX DMF 401 Discrete inputs Power supply rated 110-240VAC 24VDC 24VDC voltage limit 96 to 264VAC 19.2-30V (1) 19.2-30V (1) Frequency _ - rated 50/60Hz : - limit 47 to 63Hz - -

Power basic PLC 42VA 16W 24W required ext. block 31VA - - Protected sensor 24VDC/0.25A - - supply Supply/ground 1500V eff./50Hz none 1500V eff./ isolation 50Hz Meets CEI standard 65A yes yes yes

5.2 Discrete Input Characteristics

24VDC Input characteristics.

Positive logic

Display of each input, PLC side

Sensors commoned to the +24V for DC inputs

Basic PLC units TSX 171 2028/3428 TSX 171 2002 TSX 172 2028/3428 TSX 171 4002 TSX 172 2012/4012 Ex ion blocks & dul TSX DMF 400 TSX DMF 342A/401 TSX DEF 812 Type not isolated isolated isolated Rated voitage 24VDC 24VDC 24VDC input © current 7mA 7mA 15mA values © sensor supply 192-30VDC(1) | 19.2-30VDC (1) _19.2-30VDC (1) Limit ¢ at1 voltage 211V = 11V %11V input current 2 25mA forU*11V 22.5mAforU=11V 2 6mA value © at0 voltage s5V &5V 25V current < 1.4mA S1.4mA &3V input impedance 32to3.7Kohms 3.2to3.7Kohms~ 1.5 to 1.7 Kohms Responsee from state 0 to 1 45 to 12ms 45 to 12 ms 6 to 18ms times ¢ fromstate 1 to0 45 to 12ms 45 to 12ms 4to 13ms Power dissipation per point at state 1 0.17W 0.17W 0.35W External ¢ line resistance < 5000hms & 5000hms = 5000hms line © leakage resistance = 30Kohms 2 30Kohms = 30Kohms Isolation ¢ between inputs 2% 10Mohms % 10Mohms and bus none at 500VDC at 500VDC @ type optical coupler optical coupler Meets CE! standard 65A Class 1 Class 1 Class 2 Compatible with 2- and 3- yes yes yes wire Telemecanique sensors

(1) Including ripple

51

Page 52 read from a scan by OCR; it may hold reading errors

5 Technical Characteristics

Discrete Input Characteristics (Cont’d)

110VAC Input characteristics

Display of each input, PLC side

Basic PLC units TSX 172 2044 TSX 172 3444 Extension blocks & modules TSX DMF 344A TSX DEF 804 Rated =e voltage 110VAC input © current 15mA values e frequency 50/60Hz

© sensor supply 88VAC to 132VAC Limit © at1 voltage > 74V input current > 6mA for U*74V values © at0 voltage <20V current < 4mA

© Frequency 47 to 67Hz Input impedance 5.8 to 9.5Kohms Responsee from state 0 to 1 33ms times, e from state 1 to0 50ms Power dissipation per point at state 1 0.2W External e line resistance < 1Kohms line e leakage resistance > 30Kohms lsolation e between inputs 1500Veff - 50/60Hz and bus e type optical coupler Meets CEI standard 65A Class 2 Compatible with 2- and 3- yes wire Telemecanique sensors

5.3 TSX 17-20 Event Triggered and Fast Counting Input Characteristics

Inputs Event trig. Fast counting

Rated ¢ voltage 24VDC 24VDC 5VDC values © current 15mA 15mA 38mA

Limit ° ati voltage 211V B11V meV input current 26mA, U«11V 26mA, U=11V z6mA, U=2V values e atO voltage <5V 35V s1Vv current = 3mA 8mA s3mA

Response ® from state 0 to 1 0.15 to ims maximum allowable frequency times © from state 1 to 0 0.3 to 1ms 2KHz 2KHz

Isolation © between inputs and bus > 10Mohms at 500VDC

Telemecanique sensors

2 © type optical coupler Meets CEI standard 65A Class 2 Class 2 Compatible with 2 and 3-wire yes yes

The I/O characteristics are given for a 60% load factor (number of I/O simultaneously at 1 in relation to the total number of I/O).

52

Page 53 read from a scan by OCR; it may hold reading errors

5 Technical Characteristics

5.4 Discrete Output Characteristics

Transistor output characteristics

Positive logic Display of each input, PLC side Loads commoned to the - of the power supply

Basic PLC units TSX 172 2012 TSX 171 2002'TSX 172 4012 TSX 171 4002 TSX DMF 401 Extension blocks TSX DMF 400 TSX DSF 612 Extension modules Type of outputs Transistors Transistors not protected protected DC loads © rated voltage 24VDC 24VDC ¢ rated current 2A* 1A* 0.32A (refer to the diagram below) e rated current with 3.2A 1.6A 0.63A (refer to the diagram below) 2 outputs in parallel ¢ Tungsten filament 10W 8W indicator light Limit ¢ voltage (including 19.2-30VDC 19.2-30VDC values peaks Leakage current at 0 <1mA £0.1mMA Leakage current at 1 = 0.5V £13V for rated | Response © from state 0 to 1 100yus € 100ps time (1) ¢ from state 1 to 0 = 200us 500us Isolation ¢ between outputs & bus none 2 10Mohm at 500VDC © type - optical coupler Built-in © against shorting none thermal protection protection and overloading © against inductive yes yes overvoltages Compatible with TSX 17 24VDC yes yes inputs Meets CEI standard 65A yes yes

* Refer to Page 3/11 for the levels of the different outputs.

(1) In order to provide short guaranteed response times for fast applications, some transistor outputs are equipped with diode and zener diode fast discharge circuits, these outputs are: © outputs 0 and 1 of the TSX 172 2012/4012 and TSX DMF 401, ¢ all outputs of the TSX 171 2002/4002 and TSX DMF 400. With these outputs, the drop-out time of an actuator solenoid is: t » L/R, with L expressed in Henrys and R in ohms.

Power level of the protected transistor outputs

A

With 2 outputs “in parallel

-- With one output

Surrounding

1 n ! v tv

20 25

' 55°C temperature a 4 gt.

The I/O characteristics are given for a load rating of 60% (number of I/O at state 1 in relation to the total number of I/O).

53

Page 54 read from a scan by OCR; it may hold reading errors

5 Technical Characteristics

Discrete Output Characteristics (Cont’d)

Relay output characteristics

Display of each output, PLC side

1.N/O contact per output

Basic micro-PLCs TSX 171 2028/3428, TSX 172 2028/2044, TSX 172 3428/3444

Extension blocks and modules TSX DMF 342A, TSX DMF 344A, TSX DSF 635

Type of outputs Relay

AC loads © voltage 24 to 240VAC 24V 48Vv 110/240V

© permissible power 9VA 3x10® ops.10x10® ops.10x10° ops.

for AC11 duty 25VA 0.2x10® ops. 10° ops. 2x10® ops. (0.5Hz) 50VA 10° ops.

DC loads ® voltage 24V

® permissible power 10W for DC11 duty(0.5Hz)

Leakage current at state 0 S 1mA at 220V - 50Hz Response ¢ from state 0 to 1 % 10ms times © from state 1 to 0 & 20ms Isolation © between output groups 1500Veff - 50/60Hz

© between outputs and bus 1500Veff - 50/60Hz type Relays Built-in © against inductive MOV peak limiter on each output protection AC overvoltages Recommendede against shorting Each output is fitted with a quick-external and overloads acting fuse protection ¢ against inductive Discharge diode on the terminals of . DC overvoltages the output device

Compatibility with 24VDC PLC inputs yes

In future CEI standards, the AC11 duty cycle will become AC14 and DC11 will become DC13. The I/O characteristics are given for a load rating of 60% (number of I/O at state 1 in relation to the total number of I/O.

54

Page 55 read from a scan by OCR; it may hold reading errors

5 Technical Characteristics

Discrete Output Characteristics (Cont’d)

Triac output characteristics

Display of each output, PLC side

Extension module TSX DSF 604 Type of outputs Triac AC loads @ type Inductive

@ rated voltage 110 - 120V e rated current/point 1A (*)

e rated frequency 50/60Hz Max. values = @ voltage 93.5 - 132V

@ peak load when 10A over 2 cycles, triggered 1 time/sec.

© total module load 3A max. (*)

© frequency 47 - 63Hz Response © from state 0 to 1 1/2 period + 0.5ms times ¢ from state 1 to 0 < 1/2 period Current leak at 0 <3mA Loss current e¢ | rated > 50mA <3V

@ 25mA<I rated<50mA < 13V Built-in © against inductive MOV and RC peak limiter on each output protection AC overvoltages Recommendede against shorting ~ Each output is fitted with a quick acting fuse, external and overloads rated < 3.15A protection

Compatible with TSX Series 7 PLC 110VAC PLC inputs yes

- Meets international standards

CEI 65A, NFC 63850, UL, CSA

Isolation © between outputs 1500Veff 50/60Hz e between outputs and bus 1500Veff 50/60Hz e type optical coupler

(") temperature derating if OA = 40 degrees C:

© per point: 0.017A/deg,C © in the module: 0.007A/deg.C

I/point = 1-0.017 x (QA-40) (/point = 3-0.007 x (@A-40)

The 1/O characteristics are given for a load rating of 60% (number of I/O at state 1 in relation to the total number of 1/0).

55

Page 56 read from a scan by OCR; it may hold reading errors

5 Technical Characteristics

5.5 Compatibility with Telemecanique Sensors

This page presents a selection of the most frequently used Telemecanique sensors which are directly compatible with the 24VDC and 110VAC inputs of the TSX 17. For other Telemecanique products which are also directly compatible, consult the specialized catalogs available from your local Telemecanique Sales and Service Office.

Ranges (Sn) for inductive sensors are given in mm.

Inductive proximity sensors

XSB

Cylindrical sensors form A

Conforming to Cenelec standards EN 50040 (2-wire) EN 50008 (3-wire)

Series Voage Type Sa. O45 and65 Sn PESN BIZDSH oe DIB SH 30 Metal OC 2ewire. ee 2 ‘xSAcozri2 5 XSACOSTID 10 XSA-C10713 case Swire 1 -HO13" 1 XSAHO2SI S XSAHOS712 10. XSAH10713 - - “ $ XSA-H05713B 10XSA-H10773B AS Qwire : 5. XSA-A0S10 10 XSA-A10071 Plastic. Soir, < _JS..XSP-HO131 4 XSP-HO431 8. XSP-H0831 10. XSP-H11531 case AC 2ewire soe : 4 XSP-A0491 € | XSPLAOSOTO 15 _XSP-ATSOTI Short DC. 2ewire. mos : <2: MGM-CO2TI3 § _XSM-CO5713 70_XSM-C10713 = Sewire. 08. XSL-HO83t ~ 2 XSM-HO2713 5 XSM-H05713 70 XSM-410713 G8 _XSM-H0831 - 4 -XSM-HO4713 & XSM-HO8713 15. XSM-H15713 Rectangular sensors forms C and D Conforming to Cenelec standards EN 50025 and 50026 Type. Voltage Sa Form C Sn Form D. Sn Form D (adj ¢ range) 2wite OC 15 XSC-CIS7139 40 XSD-C407139 30 to 60 XSD-C607130._ Swire 1$ XSC-H157339 40 XSD-H407339 : gwire 20 XSC-H207339 2wire AC 76 XSC-A1S0519 40 XSD-A400519 60 XSD-A600ST9

Sensors for special applications, 2-wire with plastic case (except for XSG, 3-wire with sensing face on edge).

Compact. with terminals Compact, with loads Compact, plug-in:

Detection voltage Sr Shieided Vonage Sa DetectionVoltage Sr gad face DC 40 XSE-C107130 yos: DC, - 2. XSG-HO2B100 end face OC = «-13._ - « XSB-C10710 aide face 10 XSE-C107133 no 4 XSG-H043100 side face 25 XSB-C25730 yes AG. 2 XSG-A020110 onctace AC 13. SXB-A10571 00 &. XSG-A040110 side face 28 XSB-A25611

56

Page 57 read from a scan by OCR; it may hold reading errors

5 Technical Characteristics

Compatibility with Telemecanique Sensors (Cont'd)

Photo-electric sensors

Ranges (Sn) are given in meters. Barrier type sensors require both transmitter and receiver, reflex sensors require reflectors only.

Type Vetage Sn cylindrical, Sr Sn guisr, St ss lar, short range short range MeCnsm rage jong range Bamer OC & XUP-+H043736 6 XUH-H0631346 & XUG-H063134 3 XUE-H307534

XUB G, ag 3. __XUP-H043134 LP és) AC. XUB-ANOTIS ~ -

Reflex... OC 2. XyB-HO2313 2 XUH-H02313..4 XUG-HO4313 30 XUE+10753

AC 2 __XUB-A0291% 2. XUH-F02531 Bo XVE-A10053 Proximity DC 0.08 XUP-HOBS135 0.2. XUP-H203136 03 __ XUG-H303135 1.5 XUE-HO37535 AC: 0.08, XUB-A089215 ~ woe OB. XUG

Incremental encoders

- The output signals from the Telemecanique incremental encoders listed below are

| directly compatible with the built-in 24V fast counter input of the TSX 17-20 XCO-H.H, 9 (PNP rransistor output), 24VDC supply KCO=HURJ (NPN sransistor. ovtput), 24V0C supply _ XC. S. NPN transistor output), SVDC not supplied by the PLC

The other numbers in the reference number represent the diameter of the axis, the connection position and the resolution: refer to the Telemecanique catalog for further information.

57

Page 58 read from a scan by OCR; it may hold reading errors

5 Technical Characteristics

5.6 Compatibility with Telemecanique Actuators

All of the selected actuators listed on this page are directly compatible with the relay and transistor outputs of TSX 17 programmable controllers. To allow the use of actuators that are not compatible, the Telemecanique LA1 range of electromechanical and electronic interfaces is available. For further information refer to the Telemecanique catalog.

Electromechanical output devices

Integral 32 and 63-Contactors-Auxiliary contactors-Relays_ oa CA2-D1 CAZENT Ee 1

Pneumatic output devices

Electrically controlled pneumatic distributors - Electrovalves Low power consumption modular electro-pneumatic interfaces

Device Olstributors Plug-in interface us" 1/8°-1/4" 1/4" 3/8" 1/2" __electrovalves___ 3mm passage’

AC switching PVA-F101 PVA-G101 PVA-E101 | PS1-E£1301 PSL-ETO1 devices. : PRS-M101 :

Relay 24- outputs __ 240VAC outputs 140VAC

DC switching PVA-F102B PVAGIOOBPVAEI0@B, -«~PS1-E10008 ~~ PST-F1.028

Variable speed drives

ALTIVAR variable speed drives for standard 3-phase asynchronous motors Types of drives. Use of relay outputs 220v SO/G0HE 3 g

58

Page 59 read from a scan by OCR; it may hold reading errors

6 Service Conditions

6.1 Standards

The TSX 17 programmable controller conforms to all the principal national and international standards and recommendations concerning industrial electronic control equipment, including:

oes | France: NFC 63 850 U.S.A: UL 508 > eS: UL 746C = _ International : CEI 664 UL 94 | . CEI draft standards NEMA ICS 3 304 i t? ot for PLCs 4 20 tl is 65A, 68 and 69 Canada: CSA 22.2 n° 142 a

6.2 Environment - Normal Service Conditions

Climatic environment

Vibrations

Normal temperature conditions TSX 17 TSX 7317 © A for operation 5°C 10 55°C = 5°C to 40°C ' © A for storage =25°C to 70°C -25°C to 70°C

© A: temperature of local air (see diagram), not to be confused with © R: ambient temperature outside the enclosure.

Normal conditions of relative humidity and altitude ‘Relative humidity (without condensation) 30 to 95% Altitude 0 to 2000 meters

The vibration tests described below have been carried out on the TSX 17 only and not on it’s peripherals, mounting frame or enclosure.

Sinusoidal frequency along 3 axes 5SHz 57Hz 150Hz Test values

Amplitude 75um constant

Acceleration 1g constant Test values

Amplitude 15m constant

Acceleration 0.29 constant

Qualification tests effected in sweeps of 5 to 150Hz, 10 sweeps per axis at 1 octave per minute.

Mechanical shocks

The term mechanical shocks includes jolting, hammering, knocking over, dropping and impacts. For definitions refer to CEI draft standards on programmable controllers 65A, 68 and 69.

Nominal Operating Frequency Harmonic Micro-cuts:

voltage range range distortion duration repetition 410 to 240VAC 90 to 264VAC 47 to 63Hz 10% 40ms THz 24VDC 19.2 to 830VDC (1)

(1) Including ripple

59

Page 60 read from a scan by OCR; it may hold reading errors

6 Service Conditions

6.3 Reliability

Reliability

The TSX 17 micro-PLC is designed and built by Telemecanique to the highest standards of safety, reliability and maintainability possible using state of the art technology.

The reliability of a device is its ability to accomplish its required function in defined conditions during a given time. Irrespective of the manufacturer and the number of precautions that are taken (selection of components, systematic testing, quality control, high temperature burn-in etc.), the failure rate is never zero. A certain number of failures must therefore be expected to occur during the life of a programmable controller. Consequently, the necessary precautions should always be designed into an application so as to reduce the possibility of faults occuring and to limit the consequences of any failure, particularly where safety is concerned.

Built-in self-tests

Diagnostic aids

2

The TSX 17 is equipped with a series of built-in self-tests capable of detecting the majority of internal failures and operator errors that can occur during start-up, normal operation and maintenance of the automated system. These tests are performed at power-up, or during one or more scan cycles, and mainly concern:

e the processor: operational monitoring of the microprogram, the internal RAM memories (checksum), and the watchdog,

@ the user RAM memory: check of contents before and after the power break, if the configuration is fitted with a memory cartridge, its contents are transferred to the RAN if a test of their contents shows them to be different.

the I/O: check extension block power supply presence and data exchange on the 1/0 bus.

The results of these self-tests, depending on their importance, are

¢ indicated by LEDs on the front panel of TSX 17 components,

© available to the user program through the system bits,

. Byecty if they cause the PLC program scan cycle to stop and reset the outputs (if =1).

It is also recommended that the full power of the PL7 software be used to provide automated assistance with troubleshooting (especially to find problems caused by failures external to the PLC, these account for 90 % to 95 % of such failures.

60