The text of a manual · part 7 of 8

TSX 17 Micro-PLC Installation Manual: TSX 17 MICRO-PLC. USER'S MANUAL, pages 61 to 64

Pages 61 to 64 of 70, from TSX 17 Micro-PLC Installation Manual

The original document is the PDF (4.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Telemecanique TSX172-3444, Telemecanique TSX DMF 401, Schneider TSX172-3444, Square D TSX172-3444, Schneider TSX DMF 401 and Square D TSX DMF 401

Page 61 read from a scan by OCR; it may hold reading errors

6 Service Conditions, 6.4 Safety, System Availability

Safety

A system is said to be totally safe if the appearance of faults can never lead to a dangerous situation.

The operational safety of a device is its ability to avoid the appearance of faults and to minimize their effects when they occur.

Aninternal fault in a control system can be classified as belonging to one of two types:

© passive if the fault results in an open circuit output (no signal sent to output devices), ° active if the fault results in a closed circuit output (signal sent to output devices),

Whether or not a given type of fault can be considered dangerous will depend on the function of the ouptut concerned. A passive fault is dangerous if the normal function of the signal is to control an alarm. An active fault is dangerous if it maintains an undesired signal.

Furthermore, it is important to appreciate the fundamental difference in behaviour between an electromechanical relay and an electronic component (Such as a transistor for example):

@ there is high probability that a fault in a relay will produce an open circuit (controlled circuit not powered), but there is an even probability that a fault in a transistor will produce an open circuit, it is just as likely to produce a closed circuit.

For this reason, it is important to correctly determine the nature and consequences of possible faults when designing an automated system controlled by a solid-state device such as a programmable controller.

The system designer should provide protection against any internal active faults inthe PLC which may not be indicated, or which may be dangerous for the application, by incorporating external protective devices. These protective devices may use several different technologies such as mechanical, electromechanical, pneumatic, hydraulic or electronic (for example, wiring a limit switch and emergency stop button to the coil of a motion control contactor).

System availability

The availability of a system is its ability to accomplish a required function at any given moment and during any given period, and includes considerations of reliability, maintainability and maintenance policy. System availability is therefore specific to each application, since it depends on:

@ the architecture of the automated systems,

© the reliability and maintainability of the hardware used (PLCs, sensors, actuators, machines, etc.), the user’s maintenance policy and logistic back-up (software structure, failure indication and warning systems, availability of spare parts, training of maintenance personnel, etc.).

61

Page 62 read from a scan by OCR; it may hold reading errors

7 Appendix

7.1 Isolation Transformer Equipped Power Supply

Although TSX Series 7 PLCs meet the electromagnetic interference standards defined in CE! 65A and NFC 63 850, in industrial applications where high levels of interference are encountered, it may be necessary to fit an isolation transformer to the power supply.

ifan isolation transformer is fitted, the wiring diagram shown on page 32 is changed to look like:

50/60Hz

(5) 275 V, 90 joule MOV peak limiting circuit to locate as close as possible after the KM and KA circuit breakers.

When a DC supply is used, refer to the connection diagram on page 31, and adda discharge diode protection circuit after the KM and KA circuit breakers.

High4impedance Grounded Neutral System

An isolating transformer is mandatory when using certain versions of TSX 17 PLCs with a high impedance grounded neutral system. The connection diagram is the same as that shown above.

The following TSX 17 PLCs are affected by this requirements:

e TSX 171 2028 software version Il < 06,

TSX 172 2028/3428 software version Il < 07,

@ TSX DMF 342A software version II < 05.

62

Page 63 read from a scan by OCR; it may hold reading errors

7 Appendix

7.2 TSX 17 ACC2 Display

Programming Example

Depending on the state of input 10,2, this routine will display eiter the value of word WO or the current value of counter CO,V.

weet _ 2 rr oper. ]

10.2 BCD CO,V-> SW16

Validate numerical display

Display word WO

Display current value of C0,V

Note: Refer to page 12 for instructions on how to intall the TSX 17 ACC2 display module. This display can be fitted to any TSX 17-20 PLC except TSX 172 2028/3428/201 2/4012 software version Il < 05.

63

Page 64 read from a scan by OCR; it may hold reading errors

TSX 17 Micro-PLC Installation Manual

Notes

64