Page 65
TSX 17B 1428 BATIBUS Micro-PLC - Follow-up Sheet
Apart from the specific product features indicated on this follow-up sheet, the general instructions for installing the TSX 17B 1428 Micro-PLC are the same as those given in the TSX D11 000E Installation Manual.
1
Planning the Installation (see Section 1 in TSX D11 000E)
1.1
Description of TSX 17B 1428 PLC
These systems comprise: • a 110/240 VAC power supply that provides a 24 VDC, 250 mA supply output for 24 VDC sensors connected to the TSX 17, • a CPU with programming port and status display ,
1
3
2
4
• an internal 24 Kbyte RAM program memory (and 2 Kbytes of data) that can be backed up. The battery is located in and has a 1 year service life. • a location for a plug-in EEPROM or EPROM memory cartridge for saving user programs, • a location for a PL7-2 software cartridge containing the BATIBUS function, • 14 discrete I/O with front panel status display : - 12 isolated 24 VDC inputs - 2 relay outputs
5
6
(
8
9
7
"
9
• a BATIBUS network with front panel status display , • a 15 V, 150 mA power supply energizing the BATIBUS network, • a 9-pin I/O bus extension connector , • 2 removable terminal strips with captive screw terminals, • a ground connector .
é
§
3
'
§ 1
8
2
(
&
é
7
6
'
" 45
é
9
&
7
E N G L I S H
Page 66
1.2
0
BATIBUS Network Status Display
DEF
1
NET
DATA
ON
BUS
MD
SORTIES OUTPUTS ENTREES 4 digit readout
E N G L I S H
INPUTS 0
1
2
3
4
5
6
7
8
9
10
11 Contents of SW 16
DEF
This LED comes on when there is a BATIBUS fault
NET
This LED comes on when one of the system components is faulty, i.e. no acknowledgement or BATIBUS interface problem
DATA
This LED flashes during transmission or reception
ON
This LED comes on when the line is energized by 15 V. It thus permits detection of line short-circuits and of a cross-connected module.
Important The contents of word SW16 can be displayed in 4 digit BCD format by setting SY 14 to state 1 through PL7-2 programming. In this case the status display of both outputs (0,1) and of the BATIBUS network (DEF, NET, DATA, ON) is no longer active.
2
Mounting
• Basic PLC/extension compatibility: as for TSX 172 3428 (see Section 2.3 in TSX D11 000E Manual) • overall dimensions: as for TSX 172 3428 (see Section 2.4 in TSX D11 000E Manual)
8
Page 67
TSX 17B 1428 BATIBUS Micro-PLC - Follow-up Sheet
3
Wiring (see Section 3 - TSX D11 000E)
Power supply 110 to 240VAC
~
24 to 240VAC or 24VDC outputs
+ - + or or ~ ~
C N L C 0 0 1 1 110V 240V
BATIBUS line powered by internal 15 V
+ -
- +
POW 15 V
BUS
Connect shielding to PLC side
E N G L I S H
50/60Hz
0V 0 1 2 3 4 5 6 7 8 9 10 11 0,25 A 24 0V V 0 1 2 3 4 5 6 7 8 9 10 11
24 VDC inputs
4
Setting into Service - Maintenance
(See Section 4 in TSX D11 000E)
5
Technical Characteristics
5.1
Power Supply Characteristics: the same 110/240 V power supply as for TSX 172 3428 (see Section 5.1 in TSX D11 000E)
5.2
24 VDC Input Characteristics: as for TSX 172 3428
5.3
Discrete Output Characteristics: relay outputs as for TSX 172 3428
5.4
BATIBUS Network Characteristics
5.4.1 Principle of Coding/Decoding The modules in the network are powered by 15 V supplied by the TSX 17B 1428 PLC. Modulation is achieved by pinching off the powered line. The physical layer transmits or receives the coded frames. Line at rest : 15 V (logic state of 0) Pinched line : 0 V (logic state of 1)
9
Page 68
5.4.2 15 V Power Supply Characteristics • No load voltage • Voltage under load • Pinch-off current • Isolation between mains and bus • Capacitance between line and mains
15.5 V ± 10% 13.8 V min. at 150 mA 300 mA ± 10% 4000 Vrms 50 pF
5.4.3 BATIBUS Line Characteristics E N G L I S H
• Transmitter Network - Voltage across line terminals at pinch-off - Leakage current on line at rest • Receiver Network - Input resistance - Line resistance - Line voltage drop - Line capacitance - Spurious capacitance at a point - Pinch-off-to-breakdown and breakdown-to-pinch-off switchover times - Modulation rate
1.5 V max. with 330 mA 50 µA at 18 V 500 K Ω max. 12 Ω max. between power supply and most distant point 3.6 V max. 250 nF max. 50 pF max. 2 µs min., 5 µs max. with no load on line 4800 bps (bits per second)
5.4.4 Recommended Cable • BATIBUS cable (P/N 63715) marketed by Merlin Gerin. Name
Area mm2
Isolation (1)
Type or shielding
Screen
I m
L m
R/km
BATIBUS
0.75
4 KV flexible yes
250
1900
46.2
BATIBUS
1.5
4 KV flexible yes
500
2500
24.2
BATIBUS
2.5
4 KV flexible yes
600
2500
15.2
I : L : (1) :
max. length from processor (or sub-station) to most distant BATIBUS point. max. length of overall BATIBUS network. isolation between the conductors and the screen or shielding when present; otherwise between the conductors and the outside surface of the wire.
5.4.5 Special Wiring Precautions Whenever possible keep the BATIBUS cable at least 20 cm away from power cables.
6
Service Conditions
(see Section 6 in TSX D11 000E)
10
Page 69
mee
~~
The general rules for installing a TSX DMF 242A /O extension block are the same as those described in the TSX 17 Micro-PLC Installation Manual (TSX D11000E). Specific differences that only apply to the TSX 171 2022 are described in this sheet.
1. Planning the Installation (see Section 1 TSX 17 Installation Manual).
Description 24 discrete 1/0, 110 VAC inputs, relay outputs, AC power supply.
This extension block comprises : * a 110/240VAC power supply © that provides a 24 VDC, 250mA sensor supply output @, * 24 discrete I/O with a front panel status display ©, - 8 isolated 110VAC inputs ©, - 16 relay outputs @, » an I/O bus connection or extension block fault LED ©, * a15-pin I/O bus input connector ©, * a9-pin 1/0 bus output connector @, * 2 removable terminal blocks with captive screw-terminals ©, * aground connector ©.
R 9 2 f
~ 0 Malgigigiaigileleeieilgialaeoleelalsilalaiel®
2. Mounting (see Section 2 TSX 17 Installation Manual). * Basic-PLC/Extension Compatibility : identical to TSX DMF 342 A (see Sub-section 2.3 TSX 17 Installation Manual),
* Dimensions : identical to TSX DMF 342 A (see Sub-section 2.4 TSX 17 Installation Manual).
Page 70
3. Raccordements (voir chapitre 3 TSX D11 000F)
Power supply
3. Wiring
(see Section 3 TSX 17 Installation Manual)
7 an - + = +H + ’ - | ta: Lo lial Ja Lalo Lelials Le [7 Lets [etswolss [re |es]ualss EEN LEI LAY LLL LEC pO WH EEMEIEIG ot ESER EN ERASE LILILLILTITIIt (((((t tf ZANDC Input
4. Mise en service - 4. Setting into Service - Maintenance Maintenance , (voir chapitre 4 TSX D11 OO0F) (see Section 4 TSX 17 Installation
Manual)
5. Conditions générales de 5. Technical Characteristics mise en oeuvre (see Sub-section 5 TSX 17 (voir chapitre 5 TSX D11 000F) Installation Manual)
* alimentation 110/240VCA : * 110/240VCA Power Supply : identique & DMF 342 A Identical to TSX DMF 342 A (voir chapitre 5.1 TSX D11 000F) (see Sub-section 5.1 TSX 17 ¥ Installation Manual)
entrées 24 VCC : * 24VDC Inputs : identique 4 TSX DMF 342 A Identical to TSX DMF 342 A (voir chapitre 5.2 TSX D11 000F) (see Sub-section 5.2 TSX 17 Installation Manual)
* sorties relais : * Relay outputs : identique a TSX DMF 342 A Identical to TSX DMF 342 A (voir chapitre 5.4 TSX D11 O00F) (see Sub-section 5.4 TSX 17
Installation Manual) 6. Conditions de service 6. Service Conditions
(voir chapitre 6 TSX D11 O00F)
(see Section 6 TSX 17 Installation Manual)