Manual · Allen-Bradley
SLC 100 I/O Expansion Units Product Data
Manual20 pagesPDF 2.2 MB
Product data sheet for the Allen-Bradley SLC 100 I/O expansion units, catalog 1745-E101 to -E107: features, addressing, wiring, specs.
Names · 3 models
The models it names
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Allen-Bradley product data for the SLC 100 I/O expansion units, catalog numbers 1745-E101 through -E107, used with an SLC 100 or SLC 150 processor unit to expand the number of I/O circuits. It describes the basic, relay output and analog input expansion units, installation considerations, mounting and layout, addressing I/O by address blocks, the 1745-C2 and 1745-C3 interconnect cables, line, digital input, analog input and output wiring, output contact protection and specifications.
Its parts
- Basic Expansion Unit
- Relay Output Expansion Unit
- Analog Input Expansion Unit
- Installation Considerations
- Mounting
- Addressing I/O
- System Layout
- Connection Cables
- Line Wiring Connections
- Digital Input Wiring Connections
- Analog Input Wiring Connections
- Output Wiring Connections
- Output Contact Protection
- General Specifications
- Output Specifications
From the manual · read page by page
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
A product data sheet (publication 1745-2.2, January 1987), not a full user manual, for the Allen-Bradley SLC 100 I/O expansion units, catalog numbers 1745-E101 through -E107. It describes the basic, relay output and analog input expansion units and explains addressing, layout, interconnect cables and wiring. Several pages were read from scans, and the specification tables on pages 16, 17 and 19 have no readable text.
- What it is
- I/O expansion unit for an SLC 100 or SLC 150 processor unit p. 8
- System I/O
- 112 I/O in 7 address blocks of 10 inputs and 6 outputs p. 6
- Interconnect cable
- 1745-C2, 10-pin to 10-pin, supplied with each expansion unit p. 9
- Cable length
- 18.5 inches (47 cm), for both 1745-C2 and 1745-C3 p. 9
- Terminals
- Self-lifting pressure plates; each accepts two #14 AWG wires p. 2
- Cooling air
- 0 to 60 C inside the enclosure p. 8
- Basic unit
- 10 input circuits and 6 relay (hard contact) outputs p. 2
- Relay output unit
- No inputs, 12 relay output circuits p. 1
- Analog input unit
- 4 analog inputs, 2 adjustable set points per input, no outputs p. 4
- Analog input range
- 0 to +10 volts or 0 to 20mA, differential; response time 3.5 milliseconds p. 18
- Analog isolation
- 1500 volts between input and control logic p. 18
- Input power fuse
- Behind the front cover; suspect it if line voltage is present but DC POWER is dark p. 2
- Output contacts
- Isolated from each other with internal RC networks; each circuit wired independently p. 14
- Basic unit inputs
- 2 mA OFF-state leakage allows direct interface to solid state sensors p. 17
What this manual walks you through
- Assigning I/O addresses with address blocks p. 6, 7
- Addressing the upper and lower groups of a relay output unit p. 3
- Laying out units with spacing for convection cooling p. 8
- Installing the interconnect cables p. 10
- Making line wiring connections p. 11
- Wiring digital input devices p. 11
- Wiring analog inputs and adjusting set points p. 12
- Joining two analog circuits for four set points p. 13
- Wiring output devices p. 14
- Protecting output contacts from inductive loads p. 15
Good to know
- Do not use interconnect cables longer than the ones supplied. p. 9
- An open circuit at the source end of an analog input can make it oscillate around the set point. p. 12
- Analog voltage inputs must stay within -35 to +35 volts of COM. p. 18
- The processor unit, expansion units and I/O device circuits should share one power source. p. 5
- Fuse the output devices and wiring against shorts and overloads. p. 14
Questions this manual answers
How many I/O can an SLC 100 system have with expansion units?
Up to 112 I/O, in 7 address blocks; the SLC 100 processor uses block 1 and the SLC 150 uses blocks 1 and 2. p. 6
What cable connects a 1745 expansion unit to an SLC 100 processor?
The 1745-C2 cable, which comes with each expansion unit. p. 10
What is the 1745-C3 cable?
A 20-pin to 10-pin interconnect cable supplied with the SLC 150 processor unit. p. 9
How many inputs and outputs does the SLC 100 basic expansion unit have?
10 inputs and 6 relay outputs. p. 2
How do I adjust an analog set point on the SLC 100 analog input unit?
Apply the set point signal and turn the potentiometer until its LED lights; clockwise raises the setting, with 18 turns from minimum to maximum. p. 12
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1745-2.2, SLC 100 I/O Expansion Units1
- The Expansion Unit1
- Basic Expansion Unit2
- Relay Output Expansion Unit3
- Analog Input Expansion Unit4
- Installation Considerations5
- Mounting5
- Addressing I/O6
- System Layout8
- Connection Cables9
- Line Wiring Connections11
- Digital Input Wiring Connections11
- Analog Input Wiring Connections12
- Output Wiring Connections14
- Output Contact Protection15
- General Specifications16
- Input Specifications -Basic Expansion Unit17
- Input Specifications -Analog Input Expansion Unit18
- Output Specifications19
- Back Cover20