Page 1 of SLC 100 I/O Expansion Units Product Data

Manual · Allen-Bradley

SLC 100 I/O Expansion Units Product Data

Manual20 pagesPDF 2.2 MB

Product data sheet for the Allen-Bradley SLC 100 I/O expansion units, catalog 1745-E101 to -E107: features, addressing, wiring, specs.

Download the PDF2.2 MB

Names · 3 models

The models it names

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

Allen-Bradley product data for the SLC 100 I/O expansion units, catalog numbers 1745-E101 through -E107, used with an SLC 100 or SLC 150 processor unit to expand the number of I/O circuits. It describes the basic, relay output and analog input expansion units, installation considerations, mounting and layout, addressing I/O by address blocks, the 1745-C2 and 1745-C3 interconnect cables, line, digital input, analog input and output wiring, output contact protection and specifications.

Its parts

  1. Basic Expansion Unit
  2. Relay Output Expansion Unit
  3. Analog Input Expansion Unit
  4. Installation Considerations
  5. Mounting
  6. Addressing I/O
  7. System Layout
  8. Connection Cables
  9. Line Wiring Connections
  10. Digital Input Wiring Connections
  11. Analog Input Wiring Connections
  12. Output Wiring Connections
  13. Output Contact Protection
  14. General Specifications
  15. Output Specifications

From the manual · read page by page

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

A product data sheet (publication 1745-2.2, January 1987), not a full user manual, for the Allen-Bradley SLC 100 I/O expansion units, catalog numbers 1745-E101 through -E107. It describes the basic, relay output and analog input expansion units and explains addressing, layout, interconnect cables and wiring. Several pages were read from scans, and the specification tables on pages 16, 17 and 19 have no readable text.

What it is
I/O expansion unit for an SLC 100 or SLC 150 processor unit p. 8
System I/O
112 I/O in 7 address blocks of 10 inputs and 6 outputs p. 6
Interconnect cable
1745-C2, 10-pin to 10-pin, supplied with each expansion unit p. 9
Cable length
18.5 inches (47 cm), for both 1745-C2 and 1745-C3 p. 9
Terminals
Self-lifting pressure plates; each accepts two #14 AWG wires p. 2
Cooling air
0 to 60 C inside the enclosure p. 8
Basic unit
10 input circuits and 6 relay (hard contact) outputs p. 2
Relay output unit
No inputs, 12 relay output circuits p. 1
Analog input unit
4 analog inputs, 2 adjustable set points per input, no outputs p. 4
Analog input range
0 to +10 volts or 0 to 20mA, differential; response time 3.5 milliseconds p. 18
Analog isolation
1500 volts between input and control logic p. 18
Input power fuse
Behind the front cover; suspect it if line voltage is present but DC POWER is dark p. 2
Output contacts
Isolated from each other with internal RC networks; each circuit wired independently p. 14
Basic unit inputs
2 mA OFF-state leakage allows direct interface to solid state sensors p. 17

What this manual walks you through

  • Assigning I/O addresses with address blocks p. 6, 7
  • Addressing the upper and lower groups of a relay output unit p. 3
  • Laying out units with spacing for convection cooling p. 8
  • Installing the interconnect cables p. 10
  • Making line wiring connections p. 11
  • Wiring digital input devices p. 11
  • Wiring analog inputs and adjusting set points p. 12
  • Joining two analog circuits for four set points p. 13
  • Wiring output devices p. 14
  • Protecting output contacts from inductive loads p. 15

Good to know

  • Do not use interconnect cables longer than the ones supplied. p. 9
  • An open circuit at the source end of an analog input can make it oscillate around the set point. p. 12
  • Analog voltage inputs must stay within -35 to +35 volts of COM. p. 18
  • The processor unit, expansion units and I/O device circuits should share one power source. p. 5
  • Fuse the output devices and wiring against shorts and overloads. p. 14

Questions this manual answers

How many I/O can an SLC 100 system have with expansion units?

Up to 112 I/O, in 7 address blocks; the SLC 100 processor uses block 1 and the SLC 150 uses blocks 1 and 2. p. 6

What cable connects a 1745 expansion unit to an SLC 100 processor?

The 1745-C2 cable, which comes with each expansion unit. p. 10

What is the 1745-C3 cable?

A 20-pin to 10-pin interconnect cable supplied with the SLC 150 processor unit. p. 9

How many inputs and outputs does the SLC 100 basic expansion unit have?

10 inputs and 6 relay outputs. p. 2

How do I adjust an analog set point on the SLC 100 analog input unit?

Apply the set point signal and turn the potentiometer until its LED lights; clockwise raises the setting, with 18 turns from minimum to maximum. p. 12

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1745-2.2, SLC 100 I/O Expansion Units1
    1. The Expansion Unit1
    2. Basic Expansion Unit2
    3. Relay Output Expansion Unit3
    4. Analog Input Expansion Unit4
    5. Installation Considerations5
    6. Mounting5
    7. Addressing I/O6
    8. System Layout8
    9. Connection Cables9
    10. Line Wiring Connections11
    11. Digital Input Wiring Connections11
    12. Analog Input Wiring Connections12
    13. Output Wiring Connections14
    14. Output Contact Protection15
    15. General Specifications16
    16. Input Specifications -Basic Expansion Unit17
    17. Input Specifications -Analog Input Expansion Unit18
    18. Output Specifications19
    19. Back Cover20

From the PDF’s own bookmarks.

The whole text · 2 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20

The file

Revision and size

RevisionPublication 1745-2.2, January, 1987
PublisherAllen-Bradley
Pages20
PDF2.2 MB
TextText from the PDF itself; pages 10, 12, 14, 18 and 20 are scans, read by OCR, which may hold reading errors.