For the Allen-Bradley 1745-E101, Allen-Bradley 1745-E103 and Allen-Bradley 1745-E105
Page 11
77
Expansion Units - S l C 100 Line Wiring Connections
TO Gruund
LO
HI
Make line connections to the expansion unit as follows:
TO
Hi
LO
Note: An N.E.C.Class [ I power supply IS required for Ut ltstmg.
TU
Bus
Expansion Unit Termtnals Expansion
Unit Termmais Expansion
CatalQg NOS.1745-EtOQ, -Et07 fatalogNoa1745-E101,-E102,-E103,-E105,-E106
Digital Input Wiring Connections terminals Unit
Wiring connections for digital input devices are shown below. Note that input ground terminals are common to each other.
1745-EI01, -E102
Input Wiring Terminals t
I Thtre Terminals Common DC
. I
Solid State Switch L52 put WiringTerminals
I
I These TerminalsCommon
1
Page 12
12 Expansion Units, SLC 100
Analog Input Wiring Connections
Wiring connections for the analog input expansion unit are shown below. These connection diagrams use a single analog input circuit, providing one or two programmable set points. If you require more than two set points per input circuit, use the connection diagrams on the next page.
Applied Vaitage
Set Point 2E yo 40mV ae” «hysteresis
Set Point 1E gy TUL x L
The tollowing applies to the diagram above:
Analog input circuit number 1 is. used, as in connection diagrams 1.and 2. Set points 1£ and 2£ apply. Arbitrarily, address block 3, addresses 201- 208 is assigned. Examine ON instructions 201 and 202 are programmed for set points 1£ and 2.
The “applied voltage” is V for connection diagram 1, or V1-V2 for diagram 2, When this voltage increases to set point 1E, instruction 201 goes TRUE. When the voltage increases to set point 2E, instruction 202 goes TRUE. When the voltage drops below these set point levels (note hysteresis), the respective instructions go FALSE.
Connected internally to chassis ground
[evi] +tr |-()| sh [com a move eS. | + | a Vv to o4 xX 1} ee ou Lod + a me we me ue V4 Floating
4. Voltage source, single ended connection.
Connected internally to chassis ground feva}+t |-()] sh [com]
+ Lerma a A.
f in| boy Vi wee { ! { i , t T 3 7
PoM2, _/ *- on xv +.
APPLICATION NOTES 1. + V must be 0-10 volts greater than { ~).
2. *Vand(~) must be kept within 3S volts of COM.
3. AICOM terminals of the expansion unit are connected together internally.
4, AHSH terminals are connected together internally, and are connected to chassis ground.
5. Important wiring recommendations will be found in Publication 1770-4.1, “Program- mable Controller Grounding and Wiring Guidelines”.
6. Adjustment: Use a screwdriver with a blade width of 0.1 inch or less. Procedure:
a) Apply the desired set point voltage or current to the input circuit. Measure the voltage or current, or simulate the condition for which the set point is to be adjusted.
b) Turn the adjustment potentiometer until the corresponding LED indicator lights. CW increases the setting. There are 18 turns between minimum and maximum setting.
¢) Verify the setting during controller Start Up procedures.
¢ Signal
Common Floating
2... Voltage source, differential connection.
Connected internally to chassis ground fevi ott [-(1) | SH icom|
Current Source www ts se se 7 NS “N + rt ry fie) aX tae g _ ae Lane. XN Fm me N74 Floating
3... Current source. Terminal + V.connected to terminal +1. COM not used.
CAUTION: if an open circuit exists at the source end of the input circuit, the input could oscillate around the set point, adversely affecting user program operation.
Page 13
13
Expansion Units- SLC 100 Analog h p U t Wiring Connections (continued)
In these connection diagrams,two analog input circuits of the expansion unit are interconnected, providingfour programmable set points (IE, 2E, 3E, and 4E in this case).
Connected mternally to chassis ground
Page 14
14
Expansion Units, - SLC 100
Output Wiring Connections
Wiring connections for output devices are shown below. Note that the diagram shows the internally-connected output contacts and parallel RC networks. The RC networks guard against possible damage by transients from external output devices.
External connections are shown for outputs 11, 15, and 16. We’ve added a suppressor in parallel with two of the external devices for the purpose of contact protection. Contact protection is discussed on Page 15.
Since the expansion unit output contacts are isolated from each other, each output circuit can be wired independently, with its own ground return. You can apply a different voltage in each output circuit, as your application might require. Power or ground wires can be jumpered between sets of terminals if desired.
You should provide appropriate fusing to protect the output devices and wiring from short circuits and overload conditions.
Output Contacts
(internal) RC Network ne F2fazpstiapoalsa|ispisfisfief nae 9
OC (-)
DC Voltage Suppressor
Suppressor OC (+)
Ht 230VAL ed L2{Lo)
L1 (Hi) L2 (Lo) Solenoid 11SVAC u Li (Hi)
Page 15
15
Expansion Units - SLC 700 QLctpUt Contact
Protection
Inductive output devices suchas motor starters and solenoids may require that you use some typeof surge suppression to protect the output contacts. Examples are shownbelow.
are connected directly across the output These surge suppression circuits device. The effect is to reduce arcing of the output contacts (arcing can be caused by the high transient voltagewhich occurs whena n inductive device is switched off). Suitable surge suppression methods for inductive AC output devices include a varistor, anRC network, and an Allen-Bradley surge suppressor. These components must be appropriately rated to suppress the switching transient characteristic of the particular inductive device. For inductiveDC output devices,a diode ora varistor is suitable. A 1N4004 diode is acceptable for most applications. A surge suppressor can also be used (Figure 18.4 in the User's Manual). as close as possible We recommendthat you locate the suppression device to the outputdevice.
Suppressors recommended for use with Allen-Bradley relays, contactors, and motor starters are listed in Figure of 18.4 the User's Manual.
Surge Suppressionfor Inductive AC Output f3evices
.-
. . .
Varistor
RC Network
1 Output Device I
Surge Suppressionfor Inductive OC Output Devices
Page 16
16
Expansion Units - SLC 100 General General specifications for the basic, relay output, and analog input %pecif/catjons expansion units are shown below.
Page 17
17
Expansion Units - SLC 100
Input Specifications -Basic Expansion Unit
Input specifications for the basic expansion unit are shown below. The 2 mA OFF state leakage current specification allows direct interface to solid state sensing devices and SLC 100 controller output circuits. Note that the2 mA OFF state leakage current for24VAC circuits applies to inputs 1 and 2 only. When required,you can also achieve a 2 mA OFF state leakage currentfor inputs 3 thru 10, as indicated in the specifications.
All input circuits include optical isolation as well as filtering and surge by transients from external input suppression to guard against damage devices.
Page 18
18 Expansion Units - SLC 100
In put Speci fications Input specifications for the analog input expansion unit are shown below. ~ Analog Input . Expansion Unit Voltage Inputs
Minimum isolation Between Input and Control Logic: .1500 volts. Input Type: Differential.
Input Impedance: +Vto( - ): > 1000 K ohms. +Vor{(-)to COM: > 500 K ohms.
Trip Point Repeatability over Time and Temperature: 25-35°C: 0.25% of full scale or 25 millivolts (typical). 1.00% of full scale or 100 millivolts (worst case). 0-60°C: 0.50% of full scale or 50 millivolts (typical). 1.50% of full scale or 150 millivolts (worst case).
Hysteresis: 10 millivolts.
Maximum Operating Range: +Vto(-): Oto + 10 volts. +Vor( - )}to COM:, 35to +35 volts.
Minimum Circuit Protection Range: +Vto( - -), +Vor(-)toCOM: + 50.0 volts.
Maximum Input Response Time: 3.5 milliseconds.
Current inputs Minimum Isolation Between Input and Controi Logic: 1500 volts. input Type: Differential.
Input Impedance: +Ito( - ): 2500hms £1.0%.
Trip Point Repeatability over Time and Temperature: 25-35°C: 0.50% of full scale or 0.10mA (typical). 1.75% of full scale or 0.35mA (worst case). 0-60°C: 1.00% of full scale or 0.20mA (typical). 2.75% of full scale or 0.55mA (worst case).
Hysteresis: 40 microamps.
Maximum Operating Range: +Ito(-): Oto 20mA. +Tor(~)to COM: ~35 to +35 voits.
Minimum Circuit Protection Range: +Ito(-):. + 40mA. +Lor(-}toCOM: + 50.0 volts.
Maximum Input Response Time: 3.5 milliseconds.
Page 19
79
Expansion Units- SLC 100 Output Specifications
Output specifications for the basic and relay output expansion units are shown below. Internal output circuitry includes surge suppression to guard against possible damageby transients from external output devices. We recommend that you also use some typeof contact protection when switching inductiveload devices. Refer to Pages14 and 15.
Page 20
G2) ALLEN-BRADLEY
ND 9 6 ROCKWELL INTERNATIONAL COMPANY
Industrial Control Group Milwaukee, Wisconsin 53204