For the Allen-Bradley 1745-E101, Allen-Bradley 1745-E103 and Allen-Bradley 1745-E105

Page 1

PRODUCT DA TA

SLC”

I YY‘J

700 110 Expansion Units

Catalog Nos. 1745-EI01,-El02,-El03, -El04, -€IUS,-El06, -E107 e nit

SLC 100 expansion units can be used with either the SLC 100 processor of I/O circuits to a unit orSLC 150 processor unit to expand the number maximum of 112. Thisis explained in “AddressingI/O” on Page 6.

as the SLC 100 SLC 100expansion units have the same construction processor unit. Expansion units are available3 in I/O configurations. The basic unit has 10 input circuits and 6 output circuits. The relay output unit hasno input circuits and 12 output circuits. The analog input unit has 4 analog input circuits (2 set points per input) no output and circuits. Subjects covered in this product data sheet: Basic Expansion Unit Page 2 Relay Output Unit . . . . . . 3 Analog Input Unit . . . . . . 4 Installation Considerations 5 Mounting . . . . . . . . . . . 5 Addressing I/O . . . . . . . . 6 System Layout . . . . . , . . 8

Connection Cables. . . . . . . . . Page 9 Line Wiring Connections. . . . . . . . 11 Digital Input Wiring Connections . . 11 Analog Input Wiring Connections . . 12 Output Wiring Connections . . . . . . 14 Output Contact Protection. . . . . . . 15 Specifications. . . . . . . . . . . . . 16-19

Publication 1745-2.2 -January, 1987 Supersedes Publication1745-2.2Dated August,1986

40065-231-01(E)

Page 2

2

Expansion Units- SLC 100

Sic EXpanSiOn Unit

The basic unit, illustrated above, has 10 input circuits and 6 relay (hard contact) output circuits. The following features are pointed out. 1. Incoming line wiring terminals. Self-lifting pressure plates allow for easy wire insertion and secure connections: Terminals accept two #14 AWG wires. A hinged cover is provided (but not illustrated). The cover needn’t be removed togain access to the terminals.

2. Wiring terminalsfor 10 inputs. Same construction as line terminals. The hinged cover (not illustrated) has write-on areas for identification of external circuits. Cover is color-coded toidentify the circuit voltage level. The cover needn’t be removed to gain access to the terminals.

3. Wiring terminalsfor 6 outputs. Same construction as line terminals. Hinged cover (not illustrated) has write-on areas to identify external circuits. The cover needn’tbe removed to gain access to the terminals. 4. Diagnostic indicator: DC POWER (green LED) - Indicates that the expansion unitis energized and DC power is being supplied. 5 . Input power fuse (behind front cover).If line terminal voltage is present but theDC POWER LED is not lit, the fuse may blown. be

6. Input status indicators. Ten red LEDs, 1E thru 10E, correspond to is input device wiring terminals 1E thru 10E. When an input circuit energized, the corresponding status indicator will be lit. 7. Output status indicators.Six red LEDs, 11E thru 16E, correspondto a programmed output contact wiring terminals 11E thru 16E. When output instruction is TRUE, the corresponding output status indicator will be lit, and the corresponding output contact will close. 8. Expansion unit connection. The expansion unit is interconnected with the processor unit and other expansion units via ribbon cable. See Connection Cables, Page9.

Page 3

3

Expansion Units-SLC 100

Ut nit

The relay output expansion unit has the same construction features and dimensions as thebasic expansion unit except that the10 input circuits are replaced by 6 additional relay (hard contact) output circuits. Relay output expansion units have wiring terminals for 6 output circuits on the upper edge of the unit and wiring terminals 6for more output circuits on the lower edge of the unit. Write-on areas are provided for you to identify the first digit of the upper and lower addresses. The upper group always uses the lower number addressblock. For example, if address blocks 2 and 3 apply toa unit, the upper group of addresses mustbe 111-116(address block 2) and thelower group 211-216 (address block 3). This is illustrated in the diagram above.

Page 4

4

Expansion Units - SLC 100 l'?a/CXJlnput sion u n i t

The analog input unit, illustrated above, has 4 input circuits andno output circuits. Each input circuit has 2 adjustable set points which can be individually programmed. The following features are pointed out. 1. Incoming line wiring terminals. Self-lifting pressure plates allow for easy wire insertion and secure connections. Terminals accept two #14 AWG wires. A hinged cover is provided (but not illustrated). The cover needn't be removed to gain access the to terminals.

2 and 3. Wiring terminalsfor 4 input circuits. Same construction as line terminals. The hinged cover (not illustrated) has write-on areas for identification of external circuits. Thecover needn't be removed to gain access tothe terminals.

4. Diagnostic indicator: DC POWER (green LED) - Indicates that the expansion unit is energized and DC power is being supplied.

5. Input power fuse (behind front cover). If line terminal voltageis present but theDC POWER LED is not lit, the fuse may be blown. 6. Set point status indicators (red LEDs). The 8 set points (2 per input circuit) are labeled 1E thru 8E. When an input circuit setispoint reached, the corresponding status indicator will be lit. 7. Set point adjustment potentiometers.

8. Protective transparent cover. Hinged to allow access to the adjustment potentiometers. 9. Expansion unit connection. The expansion unit is interconnected with the processor unit and other expansion units via ribbon cable. See Connection Cables, Page9.

Page 5

5

Expansion Units - SLC 100 /nsta//ation Considerations

Refer to the User’s Manual for details on the following important installation considerations: The enclosure should be adequate (NEMA approved) for the environmental conditionsof the particular application. The processor unit, expansion units, and inputloutput device circuits should have the samepower source. The processor and expansion units should be properly grounded. Include a n electrical disconnect in the enclosure. An isolation transformer may also be required. A master control relay circuit should be included to permit disabling of the I10 devices independentof the processor and expansion unit power supply circuit. One or more emergency-stop switches should also be included. Follow the recommendationsfor component spacing within the enclosure, to help keep the controller temperature within specified the limits. Wiring should be routed to minimize electrical noise effects. Surge suppressors shouldbe used for inductive loads in series with hard contacts andfor other noise-generating equipment. Fusing should be provided to protect loads and wiring from short circuits or overloading.

Page 6

6

Expansion Units - S l C 100 To obtain theI/O combination best suited to your application, you can use various combinationsof SLC 100 expansion units and SLC 150 expansion units. Assigning addressesis simple, once you understand how processor “address blocks” are allocated.

Address Blocks - The I/O image tableof the SLC100 and SLC150 processor unit consists of 112 I/O, divided into7 address blocks(10 input addresses and6 output addresses perblock). The SLC100 processor unit uses block 1. The SLC 150 processor unit uses blocks1 and 2. In either case, the remainingblocks are available to you for addingI/O expansion units. The figurebelow identifies the address blocks and summarizes the address block requirements for the various processor and expansion units.

SLC I f 0 High Speed lnput Module

Connection Examples - The following examples indicate how you might interconnect expansion units with a n SLC 100 processor unit and a n SLC 150 processor unit. Note that example2 includes a n HSI module. SLC 100 Processor 1016 110 Block 1

-

SLC 100 Basic 1016 I10 Block 2

SLC 150 SLC 100 SLC 100 - Analoglnput - Relay Output - Expansion at0 vo

0112 I10

20112 I10

Block 3

Blocks 4,s

Blocks 6,7

EXAMPLE 1: All 7 address blocks are used. The configuration provides 84 110:40 digital inputs(blocks1,2,6,7-addresses1-10,101-110,501-510,601-610); 8analogsetpoints (block 3 -addresses 201-208); and 36 outputs(blocks 1,2,4,5,6,7 -addresses 11-16,

111-116,311-316,411-416,511-516,611-616).

Page 7

7

Expansion Units - SLC 100 Addressing 110 (continued)

SLC 150 Processor 20ll2 I10 Blocks 1,2

SLC 150 SLC 150 - Expansion - SLCHSI150 - Expansion -

SLC 100

Module

20112 I 10

20112 110

Basic 1016 I10

None

Blocks 3,4

Blocks 5,6

Block 7

EXAMPLE 2: All input and outputaddresses of all 7 address blocksare used. The configuration provides 112 I10 (70 inputs, 42 outputs). It also provides 1 high speed input circuit.

Page 8

8

Expansion Units - S l C 100 Ut

The figure below shows acceptable layouts. Follow the recommended minimum spacing toallow for convectioncooling within the enclosure. Cooling air in the enclosure must be kept withina range of 0" to 60°C. Note that SLC 100 and SLC 150 expansion units can be interconnected with either anSLC 100 or a n SLC 150 processor unit. High speed input 150 processor unit only. modules can be used with the SLC

Page 9

9

Expansion Units - SLC 100 Connection Cables

Two cables are used for interconnectingprocessor and expansion units: Interconnect cable 1745-C2 is a 10-pin to 10-pin cable supplied with each expansion unit. Interconnect cable 1745-C3is a 20-pin to 10-pin cable supplied with theSLC 150 processor unit. Both cables are 18.5 inches (47 cm) long.See the figurebelow for cable connector details. Important: Do not use cables longer than those provided. Longer cables could affect the integrityof data communications between the processor and expansion units, possibly causing unsafe operation.

Page 10 read from a scan by OCR; it may hold reading errors

10

Expansion Units, SLC 100

Connection Cables (continued)

The figure below explains how to install the interconnect cables.

A- Connecting expansion units to an SLC 100 processor unit

White key

1745-C2 cable

\

S eumemend

+

Keysiot ee ae een ee

HEH Facing eres Mit: Tit] direction [Fs of units Cable socket. Access door removed. 41745-C2 cable SLC 100 processor unit SLC 100 expansion unit

B ~ Connecting expansion units to an SLC 150 processor unit a meme Facing direction of units

Keyslot

Cable socket. Access door removed, 1745-3 cable

White key

SLC 150 processor unit or high speed input module

Connecting an expansion unit to. an SLC 100 processor unit:

Use cable 1745-C2, supplied with the expansion unit.

1. Open the access doors.

2. Refer to illustration A. Align the cable connector having the keyslot with the socket on the processor unit. Push gently; tabs will lock the connector in place.

3.. Align the connector having the black key with the expansion unit socket having the keyslot. Push gently; tabs will lock the connector in place.

4. Close the access doors.

see ® ene

SLC 150 expansion unit

1745-C2 cable

+ «|| 1745-C2 cable we

$LE.150 expansion units

Connecting an expansion unit toan SLC 150 processor unit or high speed input module:

Use cable 1745-C3, supplied with the SLC 150 processor unit.

1. Openthe access doors.

2.. Refer to illustration B. Align the 20- pin cable connector with the socket on the pracessor unit (or high speed input module). Push gently; tabs will lock the connector in place.

3. Align the 10-pin connector with the expansion unit socket having the keyslot. Push gently; tabs will lock the connector in place.

4. Clase the access doors.

To remove cable: Move tabs on socket outward; the connector will pop out.

Natt

$LC. 100 expansion unit

Connecting one expansion unit to another:

Use cable 1745-C2, supplied with the expansion unit.

1.. Open the access doors.

2. Refer to illustrations A and B. On the expansion unit already connect- ed to another unit: Align the cable connector having the keysiot with the socket. Push gently; tabs will lock the connector in piace.

3. On the other expansion unit: Align the connector having the black key with the socket having the keyslot. Push gently; tabs will lock the connector in place.

4. Close the access doors.