For the Banner USDINT-2T2

Page 31

System Installation and Alignment

Fixed Blanking Notes A) Fixed blanking must be set within 4 minutes of turning the Program/Run switch to PROGRAM (left), or a lockout will occur, and the procedure must be restarted. B) Floating blanking can be selected to eliminate nuisance lockouts resulting from unstable clear beams at the edge of fixed objects. C) Any fixed object in the defined area must occupy the entire width (from emitter to receiver) of the defined area. Otherwise, hard guarding must be added to fill any opening in the defined area created by fixed blanking (see warning below). D) The green status indicators will flash to indicate use of fixed and/or floating blanking.

WARNING . . .

4) Fixed blanking (control module model USDINT-2T2 only). The fixed blanking feature may be programmed if beams are blocked by one or more fixed objects. Fixed blanking requires an emitter/receiver pair with 16 or more beams (see page 59). Fixed blanking is limited to 30% of the total number of beams up to a maximum of 12 beams (see chart below). Contact factory Applications Department if your application requires fixed blanking of a greater number of beams. Programming of fixed blanking involves a simple “teaching” process; it is accomplished using the Diagnostic Display and the configuration (program) switches located on the controller board (Figure 20). To prepare for programming: 1) Remove all power from the control module (and from the machine to be controlled, if the system is already wired to the machine). 2) Make sure that Auto Power-up and Floating Blanking configuration switches (also located on the controller board, Figure 20) are all turned to OFF. 3) Make sure that the Program/Run switch (Figure 20) is in the RUN (right) position. Apply power to the control module (only). The yellow status indicator will doubleflash to indicate that the system is ready for a Key Reset (do NOT perform a Key Reset at this time). Move the Program/Run switch on the controller to the PROGRAM (left) position (Figure 20). The Program Mode LED will flash and the Diagnostic Display will indicate the total number of beams blocked.

Hard Guarding May Also be Required

Simulate any mechanical vibration or shock which might be encountered in the application and verify that the readout of beams blocked remains stable. Take steps to eliminate any intermittent beams.

If any object that is to be ignored by fixed blanking does not, itself, completely prevent access to the danger point(s), you must install hard guarding to prevent access past the object.

When satisfied that the number of beams blocked is stable, push the Program switch push button on the controller (Figure 20) for 1/2 to 2 seconds and release. If the programming is accepted, the Program Mode LED will stop flashing and glow steadily. Programming will be rejected if the Program/Run switch is held depressed too long, or not long enough.

Openings in the hard guarding material must meet OSHA criteria (see OSHA 1910.217, Table O-10). Failure to hard guard any opening caused by fixed blanking or failure to adequately increase the separation distance will create an unsafe condition which could lead to serious injury or death.

If too many beams are blocked, programming is rejected and the Diagnostic Display will flash error code 10. If this occurs, check sensor alignment and valid blanking criteria (see chart below). Beams in Light Screen

8

16

24

32

40 to 96

Maximum Fixed Blanked Beams

0

4

7

9

12

NOTE: See page 59 for number of beams per defined area.

Turn the Program/Run switch to the RUN (right) position. The Program/Run LED will go OFF. Now perform a Key Reset. The yellow status indicators will come ON steadily, and the green status indicators should be flashing to indicate that blanking is in use. Remove power from the control module and reconfigure Auto Power-up and floating blanking as required for the application. Reapply power and perform a Key Reset (if Auto Power-up is not in use).

31

Page 32

System Installation and Alignment To clear fixed blanking, remove power from the control box and all objects in the defined area. Repeat step 4. See page 38 for error codes (most often 10, 11, 12) associated with programming. 5) Next, trip test the MICRO-SCREEN system for object detection capability using the specified test pieces supplied with the control module. To perform the trip test, the Key switch must be in the RUN (counterclockwise) position, the yellow status indicator must be ON steadily, and the green status indicator must either be ON steadily (to indicate blanking OFF) or flashing (to indicate blanking ON).

Appropriate Test Pieces for Trip Test Floating Blanking Program

Standard Series Emitters and Receivers

V-Series Emitters and Receivers

Floating blanking OFF

19.1 mm (0.75") diameter Model STP-2

31.8 mm (1.25") diameter Model STP-4

1-beam floating blanking ON

31.8 mm (1.25" ) diameter Model STP-4

57.5 mm (2.25") diameter Model STP-5

2-beam floating blanking ON

44.5 mm (1.75") diameter Model STP-3

82.6 mm (3.25") diameter Model STP-9

Pass the specified test piece, very slowly, down the length of the defined area in three paths: close to the emitter, close to the receiver, and midway between the emitter and receiver (Figure 23). In each case, the red status indicator should come ON and remain ON for as long as the test piece remains in the defined area. When the test piece is removed from the defined area, the green status indicator must come ON (if floating blanking is ON, the green status indicator will be flashing). If the green status indicator comes ON at any time when the test piece is within the defined area, check for reflective surfaces and unguarded areas created by use of fixed blanking (see Warnings, page 49). Do not continue until the situation is corrected. If the MICRO-SCREEN System passes all of the checks in Section 3.5.5, go on to Section 3.5.6. If the MICRO-SCREEN System fails any of these checks, do not attempt to use the System or the guarded machine until the reason for the failure(s) is identified and all failures are corrected.

32

Figure 23. MICRO-SCREEN System trip test

Page 33

System Installation and Alignment

CAUTION . . .

3.5.6 Output Relay Connections

Shock Hazard Electrical shock hazard exists when the MICRO-SCREEN System control module is connected to the guarded machine. Use extreme caution to avoid electrical shock at all times. Always disconnect all power from the MICRO-SCREEN System and the guarded machine before making any connections or replacing any component.

WARNING . . . Final Switching Device

Output relay connections are made at the FSD1 (Final Switching Device 1), FSD2 (Final Switching Device 2), and SSD (Secondary Switching Device) terminals on the control module (Figure 21). These relays are energized (contacts closed) in normal operation when no obstructions are in the defined area. All relays become de-energized (their contacts open) in a lockout condition. Relays FSD1 and FSD2 (only) de-energize in a trip condition. Before continuing, read NOTICE Regarding MPCEs, below left. The FSD1 output relay connects to Machine Primary Control Element #1 (MPCE 1) on the guarded machine. MPCE 1 is an electrically powered element of the guarded machine that directly controls the normal operating motion of the machine; it must be last (in time) to operate when motion is either initiated or arrested. The output contact of relay FSD1 must be connected, as shown in Figure 24, to control power to Machine Primary Control Element #1. The switching capacity of relay FSD1 is 250V ac max., 4 amps max. (resistive load).

The output relays of the MICRO-SCREEN System must be the final switching devices for the machinery being guarded. Never wire an intermediate device (e.g., a programmable logic controller - PLC), other than a safety relay, between either FSD and the machine primary control elements (Reference ANSI B11.1-1988. Appendix B4). To do so could result in serious bodily injury or death.

The FSD2 output relay connects to Machine Primary Control Element #2 (MPCE 2) on the guarded machine. MPCE 2 is an electrically powered element of the guarded machine (in a different control path from MPCE 1) that directly controls the normal operating motion of the guarded machine; it must be last (in time) to operate when machine motion is either initiated or arrested. The output contact of relay FSD2 must be connected, as shown in Figure 24, to control power to Machine Primary Control Element #2. The switching capacity of relay FSD2 is 250V ac max., 4 amps max. (resistive load).

NOTICE Regarding MPCEs

As a result, MPCEs may be of several control types, including a wide variety of contactors and electromechanical valves. If your machine documentation leaves any doubt about the proper connection points for the MICRO-SCREEN System output relay contacts, do not make any connections. Contact the machine builder for clarification regarding connections to the MPCEs and MSCE.

Each of the two Machine Primary Control Elements (MPCE 1 and MPCE 2) must be capable of immediately stopping the dangerous machine motion, irrespective of the state of the other. These two channels of machine control need not be identical, but the stop time performance of the machine (Ts, used to calculate the separation distance) must take into account the slower of the two channels.

Many different types of mechanisms are used to arrest dangerous machine motion. Examples include mechanical braking systems, clutch mechanisms, and combinations of brakes and clutches. Additionally, control of the arresting scheme may be hydraulic or pneumatic.

The SSD output relay connects to the Machine Secondary Control Element (MSCE) on the guarded machine. The MSCE is an electrically powered element of the guarded machine (independent of the MPCEs) that is capable of removing power from the prime mover of the dangerous part of the machine in the event of an emergency. The output contacts of the SSD relay must be connected, as shown in Figure 24, to the Machine Secondary Control Element such that, if a lockout condition occurs, the motive power will be removed from the machine. The switching capacity of the SSD relay is 250V ac max., 4 amps max. (resistive load).

Some machines offer only one primary control element. For such machines, it is necessary to duplicate the circuit of the single MPCE to add a second machine primary control element. Refer to Figure 24 (page 34) or consult the machine manufacturer for additional information.

33

Page 34

System Installation and Alignment Figure 24 (below) shows output relay connections in a generic interfacing situation. The connections between the MICRO-SCREEN System outputs and the machine primary and secondary control elements must be direct, and arranged so that any single line fault or earth fault will not result in a circuit failure to a potentially dangerous state.

L (V ac) or + (V dc)

N (V ac) or Common (V dc)

Model USDINT-1T2 Control Module: Without Fixed Blanking Model USDINT-2T2 Control Module: With Fixed Blanking

Secondary Switching Device

SSD

Machine Control Circuit

Machine Secondary Control Element 24 25

MSCE

Arc Suppression (see (seewarning) wiring)

Final Switching Device #2

27

FSD 2

28

Machine Primary Control Element #2 MPCE 2 Arc Suppression (see (seewarning) wiring)

Final Switching Device #1

FSD 1

Machine Primary Control Element #1 30

MPCE 1

31

MPCE 1 MPCE 2

WARNING . . . Installation of MICROSCREEN Systems with Trip Output for Perimeter Guarding Applications The control modules described in this manual produce a “trip” output which automatically resets the output relays as soon as the defined area is clear. Use of a trip output is dangerous for perimeter guarding applications where it is possible for personnel to move through the defined area and locate themselves inside the guarded area of dangerous machine motion. Banner offers control modules with “latching” output response, which are designed for perimeter guarding applications. See the Banner Machine Safety Products catalog or contact the Banner Factory Applications Engineers for information on control modules with latching response. If a control module with trip output response is used for a perimeter guarding application, the following conditions must be met: 1)

The dangerous machine motion must be able to be initiated following an interruption of the defined area only after actuation of a Reset switch.

2)

The Machine Primary Control Elements (MPCEs) of the guarded machine must be wired so that the FSD outputs of the control module cause a latched response of the MPCEs.

3)

The MPCEs must be reset only by actuation of a Reset switch. The Reset switch must be located outside the area of dangerous motion, and must be positioned so that the area of dangerous motion may be observed by the switch operator during the Reset operation.

Arc Suppression (see (seewarning) wiring)

MPCE Monitor Contacts

MPCE 1 MPCE 2

+ (V dc)

38

- (V dc)

39 40

+24 V dc MICRO-SCREEN Control Module

Earth Ground dc Common

WARNING . . . Arc Suppressor Installation If arc suppressors are used, they MUST be installed as shown across the coils of the machine control elements. NEVER install suppressors directly across the contacts of the MICRO-SCREEN switching devices! It is possible for suppressors to fail as a short circuit. If installed directly across the contacts of a MICRO-SCREEN switching device, a short-circuited suppressor will create an unsafe condition.

WARNING . . . Output Contacts Necessary All MICRO-SCREEN System output contacts (FSD1, FSD2, and SSD) must be used. The generalized wiring configuration, shown here, is provided only to illustrate the importance of proper installation. The specific wiring of the MICRO-SCREEN System to any particular machine is solely the responsibility of the installer and end user.

Figure 24. MICRO-SCREEN System generic machine interface

34

Failure to observe this warning could result in serious bodily injury or death.

Page 35

System Installation and Alignment

3.5.7 System Power (Permanent Connection)

NOTICE Regarding MPCE Monitoring Hookup It is strongly recommended that one normally open and one normally closed auxiliary contact of each MPCE be wired (as shown in Figure 24, page 34) as MPCE monitor contacts. If this is done, any inconsistency of action between the two MPCEs will remove power from the MICRO-SCREEN System, causing a lockout condition†. MPCE auxiliary contacts must be used as MPCE monitor contacts in order to maintain redundancy. MPCE auxiliary contacts used for this purpose must be rated at 55 VA minimum. In order to maintain control reliability, the MPCE monitor contacts must be wired as described in section 3.5.6 and Figure 24, pages 33-34. †

NOTE: Assumes Auto Power-up feature is not in use.

After the initial checkout of Section 3.5.5 has been successfully completed, the power lines to the MICRO-SCREEN System must be re-routed to their permanent hookup through the MPCE monitor contacts of the guarded machine. This is important: it ensures that any inconsistency in action between the two MPCEs will remove power from the system. (See NOTICE Regarding MPCE Monitoring Hookup, left.) Connection of system power is at the +24V dc and dc common terminals of the control module (Figure 21). Do not operate the MICRO-SCREEN System without an earth ground connection. After power has been connected to the MICRO-SCREEN System and the output relay contacts have been connected to the machine to be guarded, the operation of the MICRO-SCREEN System with the guarded machine must be verified before the combined system may be put into service. To do this, a Qualified Person must perform the Commissioning Checkout Procedure, Section 6.2 on page 46.

3.5.8 AUX Non-Safety Output Contact The action of the AUX non-safety output contact “follows” the action of output relays FSD1 and FSD2. The AUX non-safety output contact is a light-duty contact used for control functions that are not safety-related. A typical use is to communicate with a programmable logic controller (PLC). The switching capacity of the AUX non-safety output is 125V ac or dc max., 500mA max. Connection to the AUX non-safety output contact is made at terminals 21 and 22 (Figure 21).

3.5.9 Remote Test Input Remote Test Input connects to the Test 1 and Test 2 terminals 7 and 8 (see Figure 21, page 28). When connected together (shorted) for a minimum of 50 milliseconds, these terminals provide the MICRO-SCREEN System with the equivalent of a BLOCKED beam condition, for testing purposes. The switch or switching device used to short the Test contacts must be capable of switching 15V dc to 50V dc at 20 mA dc to 100 mA dc.

35

Page 36

Operating Instructions

4. Operating Instructions 4.1 Security Protocol The MICRO-SCREEN control module must be installed inside a lockable enclosure with a NEMA 3 (IP54) or better rating. To prevent access by unauthorized personnel, and to ensure that all lockout conditions come to the attention of a person who is qualified to deal with them, the key (or combination or tool) to the locking mechanism must be kept in the possession of a Qualified Person as defined in ANSI/ASME B30.2-1983 (see Glossary). Only Qualified Persons should have access to the interior of the MICROSCREEN control module. The key to the Reset switch should be available to a Designated Person or persons. A Designated Person is one who is identified and designated in writing, by the employer, as being appropriately trained and qualified to perform a specified checkout procedure. A machine operator who meets these requirements may be a Designated Person.

4.2 Periodic Checkout Requirements In addition to the checkouts that are performed by a Qualified Person or persons at the time that the MICRO-SCREEN System is installed and put into service, the functioning of the MICRO-SCREEN System and the machine it guards must be verified on a regular periodic basis to ensure proper operation. This is absolutely vital and necessary. Failure to ensure proper operation can lead to serious injury or death. Checkouts must be performed according to checkout procedure 6.3, page 48, as follows: 1) By a Designated Person at every power-up of the MICRO-SCREEN System; 2) By a Qualified Person following the correction of every lockout condition; 3) By a Designated Person at every shift change or machine setup change; Checkouts must be performed according to checkout procedure 6.4, page 49, as follows: 1) By a Qualified Person semi-annually (every 6 months) following installation of the MICRO-SCREEN System.

36

WARNING . . . For Proper Operation The Banner MICROSCREEN System can do the job for which it was designed only if it and the machine it guards are operating properly, both separately and together. It is the user’s responsibility to verify proper operation, on a regular basis, as instructed in Section 4.2 and Section 6. If the MICRO-SCREEN System and the guarded machine do not perform exactly as outlined in the checkout procedures, the cause of the problem must be found and corrected before the system is put back into service. Failure to correct such problems can result in serious bodily injury or death.

Page 37

Operating Instructions

4.3 Normal Operation Power-up NOTE: Key must be in the RUN position at power-up. If the Auto Power-up feature is ON when dc power is applied to the MICRO-SCREEN System, the controller performs a system checkout and resets itself. If the Auto Power-up feature is OFF when dc power is applied to the System, it is normal for it to power up into a lockout condition and the Designated Person must perform a Key Reset: 1)Turn the key clockwise to the RESET position (yellow indicators go ON steadily). Wait at least one-half second, then 2)Turn the key counterclockwise to the RUN position. If the defined area is clear, the green and yellow indicators will go ON (red indicator goes OFF). (NOTE: The green status indicator will flash if floating blanking is ON.) If the emitter and receiver are misaligned, the red indicator will come ON. The yellow indicator will single-flash at a rate that indicates the relative number of light beams established. Also, the two-digit Diagnostic Display on the control module indicates the number of beams blocked. If the defined area is blocked and the emitter and receiver are aligned, the red indicator will come ON, and the yellow indicator will single-flash at a rate that indicates the relative number of light beams established. Also, the two-digit Diagnostic Display on the control module indicates the number of beams blocked. Fixed Blanking Operation (Control Module model USDINT-2T2) The fixed blanking feature allows the MICRO-SCREEN to be programmed to ignore permanent objects (e.g., brackets or fixtures) within the defined area. See page 7 for the description of fixed blanking. See page 31 for programming information. Note that up to 30% of the total number of beams in the array (to a maximum of 12 beams) may be fixed blanked. Contact the factory Applications Department if your application requires fixed blanking of a greater number of beams. Floating Blanking Operation The MICRO-SCREEN System allows disabling of either one or two beams, to allow objects such as workpiece materials to move undetected through the defined area. See page 7 for a description of floating blanking. See page 25 for information on how to enable floating blanking. Note that use of floating blanking increases the minimum object sensitivity of the light screen and requires the separation (safety) distance to be increased. Use of Emergency Stop Switch Both FSD output contacts open within 15 milliseconds, in response to actuation of an optional Emergency Stop (E-stop) switch. See page 27 for wiring information. The Diagnostic Display indicates error code “0” (zero). A Key Reset is required after re-arming (closing) the E-stop switch. NOTE: A lockout condition will occur (error code “9”) if the two contacts of the E-stop switch do not open simultaneously when the E-stop switch is actuated. This lockout condition requires removal and re-application of system power, plus a Key Reset (if Auto Power-up is not in use). This fault may indicate a defective E-stop switch. The E-stop switch (or switches) must be tested regularly (see section 6.3).

37

Page 38

Troubleshooting and Maintenance

5. Troubleshooting and Maintenance 5.1 Troubleshooting Lockout Conditions A lockout condition of the MICRO-SCREEN System causes all of its output relays to open, sending a “stop” signal to the guarded machine. A lockout condition will occur: Power-up/Power Interrupt Lockouts • Routinely upon power-up of the MICRO-SCREEN System (unless Auto Powerup is ON; see Figure 5, page 11); or • If power to the MICRO-SCREEN System is interrupted (unless Auto Power-up is ON; see Figure 5). Internal Lockout Conditions • If the control module Key switch is in the RESET position at power-up (with Auto Power-up ON); or if the Key switch is switched to RESET while the System is in the RUN mode; • If the Program/Run switch (Figure 20) is in the PROGRAM position at power-up; • If Floating Blanking switches are in the ON position when the Program/Run switch is switched to the PROGRAM position; • If both 1-beam and 2-beam Floating Blanking switches are in the ON position; • If fixed blanking is not set within approximately 4 minutes of moving the Program/Run switch to the PROGRAM position; • If Fixed Blanking has been programmed, and any fixed object is removed from or moved within the defined area;

Power Failures Power failures or other MICRO-SCREEN System lockout conditions should always be investigated immediately by a Qualified Person. With the exception of Power-up/Power Interrupt lockout conditions (listed at left), lockout is a positive indication of a problem and should be investigated at once. Attempts to continue to operate machinery by bypassing the MICROSCREEN System are dangerous and could result in serious bodily injury or death.

• If an FSD (Final Switching Device – see Glossary) relay does not “drop out” within its specified time;

CAUTION . . .

• If the SSD (Secondary Switching Device – see Glossary) relay has de-energized;

High Voltage

• If the control module switch settings are inconsistent with each other or if they are changed while the System is in RUN mode;

Dangerous voltages are present inside the MICROSCREEN System control module whenever ac power to the machine control elements is ON. Exercise extreme caution whenever ac voltage is or may be present!

• If the self-checking circuits of the microprocessor detect a component failure within the MICRO-SCREEN System itself; or • If either (or both) Emergency Stop switch contacts open. A lockout condition causes output relays FSD1, FSD2, and SSD to open, shutting down the MPCEs and MSCE of the guarded machine. An internal lockout condition (resulting from an internal system fault) is indicated by the red status indicator (only) flashing. Power-up/power interrupt lockouts (Auto Power-up OFF, conditions as described above, yellow indicator only double-flashing) are normal and require a Key Reset for operation to continue. Key Reset. To resume operation after a power interruption: 1) Turn the key clockwise to RESET position (yellow status indicator should light) and wait at least one-half second, then 2) Turn the key counterclockwise to RUN position. If the defined area is clear and the emitter and receiver are properly aligned, the green and yellow indicators will light. If the lockout condition was due to a momentary power interruption that has been corrected, the MICRO-SCREEN System will now operate normally. Upon recovery from a power interruption, checkout procedure 6.3 on page 48 must be performed. 38

WARNING . . .

Page 39

Troubleshooting and Maintenance A lockout condition resulting from an internal system fault is indicated by the red status indicators flashing, and an error code number appearing in the Diagnostic Display. In this case, the Qualified Person must note the error code and interpret the cause of the lockout from the table in Figure 25, below. This diagnostic table is also found inside the control module on the back side of the cover plate. The MICRO-SCREEN System will not operate if its self-checking circuits detect an internal problem. A Key Reset will have no effect until the problem has been corrected. Take the corrective measure(s) corresponding to the error code and then perform a Key Reset. If further assistance is required, contact your Banner field service engineer or the factory Applications Engineering Department. If no status indicators are ON, power to the system may have been lost. The green LED on the power supply board (remove module cover to view) indicates the presence (LED ON) or absence (LED OFF) of dc power at the power supply board. It is possible for power to be present at the input of the power supply even if the dc Power LED is OFF. Check for voltage across the +24V dc and dc common terminals 38 and 39. If voltage is not present, power to the MICRO-SCREEN System has been lost, and the cause is outside the system. If 24V dc is present, turn off the power to the control module and check the fuse. If the fuse is bad, replace it (Section 5.3.1). If the fuse is good, and 24V dc is present at terminals 38 and 39, an internal power supply failure has occurred. Noise Indicator

Diagnostic Display

Error No.

Error Type/Action

Error No.

System is OK

See Section 5.2 for further information about electrical and optical “noise.”

Error Type/Action

Error No.

Error Type/Action

9

E-Stop Input Error • Check E-Stop Circuit • Replace Controller • Replace Relay/Power Supply

4

Receiver Error • Check Receiver Cable • Replace Receiver

0

E-Stop Open • Check E-Stop Circuit • Replace Controller • Replace Relay/Power Supply

5

Emitter Error • Check Emitter Cable • Replace Emitter

10

1

Relay Signal Error • Replace Relay/Power Supply • Replace Controller

6

Communication Error • Check Cable Connections • Observe Noise Indicator • Replace Emitter/Receiver

11

2

Key Input Error • Check Key Position • Invalid Key Reset • Replace Key Switch

7

DIP Switch Error • Check Switch Settings • Replace Controller

3

Controller Error • Replace Controller

8

CPU Error • Replace Controller

–

12

System Error • Check Fixed Beams Power Up Error • Check Prog/Run Switch Programming Error • Too Much Time • Floating Blanking ON

NOTE: Flashing decimal point indicates noisy environment

Figure 25. Interpretation of Diagnostic Display

39

Page 40

Troubleshooting and Maintenance

5.2 Effects of Electrical and Optical Noise

Electrical and Optical Noise

The MICRO-SCREEN System is designed and manufactured to be highly resistant to electrical and optical noise and to operate reliably in industrial settings. However, serious electrical and/or optical noise may cause a random trip condition. In very extreme cases, a lockout is possible. In order to minimize the effects of transitory noise, the MICRO-SCREEN System will respond to noise only if the noise is detected on multiple consecutive scans. The decimal point of the Diagnostic Display will flash to indicate the presence of electrical or optical noise. This indicator can be used to track down particularly offensive noise sources (see sidebar at right). Simply observe the decimal point indicator while shutting down or isolating the suspected sources.

Check the following if the red decimal point of the Diagnostic Display is flashing: • Poor connection between control module and earth ground • Drain wire of emitter and/or receiver not connected to terminal 20 (see Figure 21) • Sensor wires or output wires routed too close to “noisy” wiring

5.3 Servicing and Maintenance

• Optical interference from adjacent light screens or other photoelectrics

5.3.1 Fuse Testing and Replacement Turn OFF power to the control module and the machine being guarded before proceeding. The MICRO-SCREEN System control module fuse is located in a fuseholder on the power supply board, immediately beneath the removable top cover plate. Remove the control module cover plate by gently prying it up and off using a flat-blade screwdriver or similar tool (see Figure 19, page 25). Remove the fuse from the holder. Visually inspect the fuse and/or test its conductivity using an ohm meter or a continuity tester. The fuse is a 3AG or 5x20 mm slow-blow type (see specifications, page 58).

5.3.2 Controller Board and Relay/Power Supply Replacement MICRO-SCREEN Systems are designed for reliability. While replacement of the controller or relay/power supply boards is not normally required, these components have been designed to be easily replaceable as a convenience to the customer. See the instructions included with the replacement board. To maintain control reliability, use only Banner-supplied replacement relays with forced-guided contacts. See Replacement Parts, page 61.

NOTE: Do not open the emitter or receiver housing. The emitter and receiver contain no field-replaceable components. If repair is necessary, return the unit to the factory. Do not attempt to repair an emitter or receiver yourself.

40

WARNING . . . Use Only Genuine Banner Replacement Parts If replacement parts are ever required, always use only genuine Banner-supplied replacement parts (see page 61). Do not attempt to substitute parts from another manufacturer. To do so could impair the operation of the MICRO-SCREEN System and could result in serious bodily injury or death.

WARNING . . . Shut Down Machinery Before Servicing Servicing the MICROSCREEN System while the hazardous machinery is operational could result in serious bodily injury or death. You may be working close to a hazardous area of your machinery while servicing the MICRO-SCREEN System. The machinery that the MICRO-SCREEN System is connected to must not be operating at any time during this procedure.

CAUTION . . . Dangerous Voltages Dangerous voltages are present inside the MICROSCREEN System control module whenever ac power to the machine control elements is ON. Exercise extreme caution whenever ac voltage is or may be present! Always disconnect all power from the MICROSCREEN System and the guarded machine before making any wire connections or before replacing any component. The control box should be opened and/or serviced only by a Qualified Person (see Section 4.1).