MICRO-SCREEN Instruction Manual: For systems using control module USDINT-1T2 and USDINT-2T2 with Trip Output
Manual68 pagesPDF 1.5 MB
Instruction manual for the Banner MICRO-SCREEN safety light screen with USDINT-1T2 and USDINT-2T2 trip output control modules.
Covers · 1 model
The models it covers
Summary
What is in it
Banner Engineering's instruction manual for the MICRO-SCREEN System, a modular optoelectronic point-of-operation guarding light screen made of a USE Series emitter, a USR Series receiver and a control module (USDINT-1T2 without fixed blanking, or USDINT-2T2 with fixed blanking). It explains system operation (blanking, auto power-up, lockouts, indicators, diagnostic display, E-stop, output relays), installation and wiring, operation, troubleshooting and maintenance, and alignment and checkout, with specifications and models in the appendix.
Its parts
- MICRO-SCREEN System Introduction
- Overview of MICRO-SCREEN System Operation
- System Installation and Alignment
- Operating Instructions
- Troubleshooting and Maintenance
- Alignment and Checkout
From the manual
Key facts from this manual
Each line names its page in the PDF.
Instruction manual for Banner MICRO-SCREEN light screen systems built on control module USDINT-1T2 or USDINT-2T2 with trip output. It covers the controller, the Standard Series and V-Series emitters and receivers, and how to install, align, check out and troubleshoot the system. It also lists specifications, error codes, ordering numbers, accessories and replacement parts.
- What it is
- 24V dc MICRO-SCREEN control module with fixed blanking, part number 49785 p. 60
- Power
- 24V dc ±15%, 10% maximum ripple, 1.5 amps max. p. 58
- Fuse
- 2 amp, 250 V, 3 AG or 5 x 20 mm slow blow p. 58
- Safety outputs
- FSD1, FSD2 and SSD: forced-guided contact relays, 250V ac max., 4 amps max. (resistive load) p. 58
- Auxiliary output
- Non-safety reed relay, 125V ac or dc max., 500 mA max. (10VA maximum, resistive load) p. 58
- Operating environment
- 0° to +50°C (+32° to 122°F); 95% maximum relative humidity, non-condensing p. 58
- Emergency stop input
- Two normally closed contacts, able to switch 50 mA @ 30V dc p. 58
- Test input
- Close the terminals at least 0.05 seconds; switching device rated 15-50V dc at 20 to 100 mA p. 58
- Response time
- Light screens less than 38 milliseconds (all lengths); E-Stop less than 15 milliseconds p. 56
- Diagnostic display
- Two-digit numeric display showing the cause of a lockout and the total number of beams blocked p. 58
- Mounting
- Flat plate (hardware supplied) or 35 mm DIN rail p. 56
- Sensing range
- 15 cm (6") to 9 m (30'); V-Series 56" to 72" emitters and receivers: 15 cm (6") to 6 m (20') p. 56, 57
- Mating cables
- Straight QD connector cables QDU-515C 4.5 m (15'), QDU-525C 7.6 m (25'), QDU-550C 15 m (50') p. 60
- Minimum object size
- Standard Series 19.1 mm (0.75"); V-Series 31.8 mm (1.25"), with floating blanking off p. 56, 57
What this manual walks you through
- Finding the cause of a lockout and resetting with the key p. 38, 39
- Reading the diagnostic display error codes p. 11, 39
- Tracking down electrical and optical noise p. 40
- Testing and replacing the control module fuse p. 40
- Checking for lost power when no indicators are on p. 39
- Choosing emitters, receivers and cables to order p. 59, 60
- Corner mirrors, stands and lens shields p. 61
- Machines the system may and may not be used with p. 2
Good to know
- The system must never be used on full-revolution clutched machinery. p. 2
- It may not be used as a tripping device to start machine motion (PSDI) on mechanical power presses. p. 2
- The emitter and receiver have no field-replaceable parts; do not open their housings. p. 40
- Only Banner cables should be used; other cables may cause nuisance lockouts. p. 58
- After an internal fault, a key reset does nothing until the problem is corrected. p. 39
Questions this manual answers
What is the difference between the USDINT-1T2 and USDINT-2T2?
The USDINT-2T2 control module has fixed blanking; the USDINT-1T2 does not. p. 1
What power supply does the MICRO-SCREEN control module need?
24V dc ±15%, with 10% maximum ripple, drawing up to 1.5 amps. p. 58
What does error 5 on the MICRO-SCREEN diagnostic display mean?
Error 5 is an emitter error: check the emitter cable, or replace the emitter. p. 39
What does a flashing decimal point on the diagnostic display mean?
It shows electrical or optical noise near the system; check grounding, the sensor drain wires, wire routing and nearby light screens. p. 40