For the Banner USDINT-2T2

Page 41

Troubleshooting and Maintenance

5.3.3 Cleaning The MICRO-SCREEN System control module is constructed of gray polycarbonate and is rated NEMA 1 (IP20). It may be dusted, but avoid contact with any liquids. The MICRO-SCREEN System emitter and receiver units are constructed of aluminum with a yellow painted finish and are rated NEMA 4, 13 (IP65). Lens covers are acrylic. Emitters and receivers are best cleaned using mild detergent or window cleaner and a soft cloth. Avoid cleaners containing alcohol, as they may damage the acrylic lens covers.

5.3.4 Warranty Service If it ever becomes necessary to return a MICRO-SCREEN component to the factory, please do the following: 1) Contact the Banner Factory Application Engineering group at the address or numbers listed below. Banner Engineering Corp. 9714 - 10th Avenue No. Minneapolis, MN 55441 Phone: 612.544.3164 Fax: 612.544.3213 They will attempt to troubleshoot the system from your description of the problem. If they conclude that a component is defective, they will issue an RMA (Return Merchandise Authorization) number for your paperwork, and give you the proper shipping address. 2) Pack the component(s) carefully. Damage which occurs during return shipping is not covered by warranty.

41

Page 42

Alignment and Checkout

6. Alignment and Checkout Study each procedure from beginning to end to make sure that you understand each step before you start. Refer all questions to the Banner Applications Engineering Department: Banner Engineering Corp. 9714 - 10th Avenue No. Minneapolis, MN 55441 Phone: 612.544.3164 Fax: 612.544.3213

Section 6.1 is a procedure for optically aligning a MICRO-SCREEN System. Sections 6.2, 6.3, and 6.4 are periodic performance checkout procedures for the MICRO-SCREEN System, and are performed according to the schedule given in Section 4.2. Emitter/receiver pairs from 102 to 1219 mm (4" to 48") long may be spaced from 15 cm to 9 m (6" to 30') apart. Emitter/receiver pairs 1422 to 1892 mm (56" to 72") long may be spaced from 15 cm to 6 m (6" to 20') apart. The maximum emitter/receiver separation distance is reduced if corner mirrors are used (see alignment information on page 45). The width and height so described are known as the defined area.

WARNING . . . Turn Machinery OFF Before Proceeding You may be working close to hazardous areas of your machinery while aligning the MICRO-SCREEN System. Doing so while the hazardous machinery is operational could result in serious bodily injury. The machinery that the MICRO-SCREEN System is connected to must not be operating at any time during the alignment procedure of Section 6.1.

6.1 MICRO-SCREEN System Alignment The System alignment procedure begins with the assumption that the MICRO-SCREEN System has been mechanically aligned as described in Section 3.3.

Operation Mode

Normal Operation

Power Up

Apply Power to Control Module LOCKOUT STATE

Follow the measures outlined below to maximize MICROSCREEN System excess gain. If there are reflective surfaces near the defined area, read alignment step #5 (pages 43-44) before proceeding further, to prevent possible reflection problems. Only a Qualified Person may align the MICRO-SCREEN System, as follows:

Turn Key to RESET Position

Key Reset Turn Key to RUN Position

1)Turn OFF power to the MICRO-SCREEN System and to the guarded machine. Leave power to the guarded machine OFF, and power-up only the MICRO-SCREEN System with the key in the RUN position. 2)The MICRO-SCREEN will power up into a power-up lockout condition (unless Auto Power-up is ON; then proceed to step #3). Remove all obstructions from the defined area and reset the MICRO-SCREEN System as follows: a. Turn the Key Reset switch clockwise to RESET position, and wait at least 1/2 second to allow time for internal system checks, then b. Turn the Key Reset switch counter-clockwise to RUN position.

42

Run

Defined Area Is Clear

Symbol Definitions Indicator OFF

Indicator ON steadily Indicator single-flashing Indicator double-flashing

Indicator Status BLOCKED Red

CLEAR Green

RESET Yellow

Red

Green

Yellow

If Auto Power-up is ON when power is applied to the MICRO-SCREEN System, the controller will perform an automatic Reset after passing an internal system checkout (Key Reset not needed). Auto Power-up is discussed in Section 3.4. Red

Internal System Fault (LOCKOUT)

Yellow

*Green will flash if blanking is ON. Red

Defined Area Is Blocked

Green*

Green

Yellow**

**Yellow will be OFF if the System is powered up without alignment. Red

Green

Figure 25. Operating status indicator conditions

Yellow

Page 43

Alignment and Checkout 3) Upon completion of the Key Reset (step #2), the MICRO-SCREEN will indicate either a BLOCKED or a CLEAR condition: a)

A BLOCKED condition is indicated by the red indicator ON steadily and the yellow indicator flashing at a rate which is proportional to the number of beams which are aligned and unblocked. Go to step #4. The 2-digit Diagnostic Display on the control module will also indicate the total number of blocked beams.

b) A CLEAR condition is indicated by the red indicator OFF and the green and yellow indicators ON steadily. (NOTE: The green status indicator will flash if floating blanking is ON.) Further alignment is not necessary. 4) A BLOCKED condition after Reset indicates that one or more of the beams is misaligned or interrupted. When this occurs: a)

Check carefully for any obstructions in the path of the beams within the defined area (the limits of which are indicated by the ends of the windows of the emitter and receiver; see Figure 15).

b) If the defined area is completely clear of obstructions, loosen the four slotted hex M3 screws which fasten the receiver to its mounting brackets. Slowly rotate the receiver first to the right and then to the left while watching the status indicators at the base of the receiver. c)

If the green indicator does not come ON, regardless of angular position of the receiver, then loosen the emitter and rotate both sensors relative to each other until the green indicator comes ON. Secure the emitter and receiver in the center of the area of rotation where the yellow and green indicators are ON steadily. (NOTE: The green status indicator will flash if floating blanking is ON.)

d) If the green indicator still fails to come ON, then re-check the sensor mounting per the procedure in Section 3.3, and re-align per this alignment procedure. 5) Trip test the MICRO-SCREEN System for object detection capability using the test piece(s) supplied with the control module. To perform this test, the Key Reset switch must be in the RUN position and the green and yellow indicators (only) must be ON steadily. (NOTE: The green status indicator will flash if floating blanking is ON.) Perform a Key Reset, if necessary, to attain this condition (see step #2).

Appropriate Test Pieces for Trip Test Floating Blanking Program

Standard Series Emitters and Receivers

V-Series Emitters and Receivers

Floating blanking OFF

19.1 mm (0.75") diameter Model STP-2

31.8 mm (1.25") diameter Model STP-4

1-beam floating blanking ON

31.8 mm (1.25" ) diameter Model STP-4

57.5 mm (2.25") diameter Model STP-5

2-beam floating blanking ON

44.5 mm (1.75") diameter Model STP-3

82.6 mm (3.25") diameter Model STP-9

43

Page 44

Alignment and Checkout Perform the trip test as follows: Pass the appropriate specified test piece downward through the defined area at three points (see Figure 27), taking care to hold the test piece perpendicular to the defined area: a) Close to the receiver, b) Close to the emitter, and c) Midway between the emitter and receiver. In each case, the red status indicator must come ON and remain ON for as long as the test piece is within the defined area. The green status indicator should come ON only when the test piece is withdrawn from the defined area. If the green status indicator comes ON at any time when the test piece is within the defined area, check for reflective surfaces or unguarded areas created because fixed blanking is in use (see Warnings, page 49). Do not continue until the situation is corrected.

Figure 27. MICRO-SCREEN trip test

44

WARNING . . . If Trip Test Indicates a Problem If the MICRO-SCREEN System does not respond properly to the trip test, do not attempt to use the System. If this occurs, the System cannot be relied upon to stop dangerous machine motion when a person or object enters the defined area. Serious bodily injury or death could result.

Page 45

Alignment and Checkout Use of Corner Mirrors MICRO-SCREEN sensors may be used with one or more MSM Series corner mirrors for guarding along more than one side of an area. The Accessories section lists the 12 available lengths of corner mirrors for sensors up to 48" long (see page 61). (Corner mirrors are not available for sensors longer than 48".) These rear-surface glass mirrors are rated at 85% efficiency; sensing range (and therefore excess gain) is reduced when using mirrors. The following table lists the resultant range when from one to four MSM Series corner mirrors are used in either sensing path. Maximum Emitter and Receiver Separation Number of Corner Mirrors

1

Maximum distance between emitter and receiver

8.5 m (28')

2

3

7.8 m (25.5') 7.2 m (23.5')

4 6.7 m (22')

Mirrors should be securely mounted to a solid, vibration-free surface. Using a level, mount the mirror(s) exactly parallel to (in the same plane as) the sensors, with the midpoint of the mirror(s) directly in line with the midpoint of the sensors’ defined area. The upper and lower limits of the defined area of MICRO-SCREEN sensors are indicated by the ends of each sensor window, and are dimensioned in the chart on page 23. Adjust the corner mirror(s) so that the angle of incidence of light to the mirror equals the angle of reflection from the mirror. Referring to Figure 28 below, sight from behind one of the sensors directly towards the mirror (or the first mirror in line). When alignment is correct, you will see the straight and centered reflection of the lens of the other sensor in the mirror. Accessory laser alignment tool, model LAT-1, is available to greatly assist alignment (see page 60).

WARNING . . . Use with Supplemental Sensing Devices if Necessary

Use the yellow alignment indicator corresponding to the screen being aligned for final alignment. Also, the two-digit Diagnostic Display on the control module will indicate the total number of blocked beams. Refer to the data sheet (P/N 43658) packed with each MSM Series corner mirror for complete information on the use of corner mirrors.

Supplemental presence-sensing devices, such as safety mats, must be used if any space between either defined area and any danger point is large enough to allow a person to stand undetected by the MICROSCREEN System. Failure to observe this warning could result in serious injury or death.

Figure 28. Corner mirror alignment

45

Page 46

Alignment and Checkout

6.2 Commissioning Checkout (To Be Performed at Installation) This commissioning checkout must be done by a Qualified Person who possesses all of the manufacturer-provided information on the MICRO-SCREEN System and guarded machine and who, by possession of a recognized degree or certificate of professional training or who, by extensive knowledge, training, or experience, has successfully demonstrated the ability to solve problems relating to the installation, operation, and maintenance of optoelectronic machine guards. A copy of checkout results should be kept in the employer’s files; see OSHA 1910.217(e)(1). The Qualified Person must: 1) Examine the guarded machine to verify that it is of a type and design compatible with the MICRO-SCREEN System. See page 2 for a list of misapplications. 2) Verify that the minimum separation distance from the closest danger point of the guarded machine to the defined area is not less than the calculated distance (see Figure 29). 3) Verify that access to any dangerous parts of the guarded machine is not possible from any direction not protected by the MICRO-SCREEN System, hard guarding, or supplemental guarding, and verify that all supplemental guarding devices and hard guarding are in place and operating properly. 4) Verify that it is not possible for a person to stand between the defined area and the dangerous parts of the guarded machine. Or, verify that supplemental presence-sensing devices, such as safety mats, are in place and functioning properly in any space between the defined area and any danger point which is large enough to allow a person to stand undetected by the MICRO-SCREEN System. 5) Examine the electrical wiring connections between the MICROSCREEN output relays and the guarded machine’s control elements to verify the requirements stated in Section 3.5.6.

The formula used to calculate the separation distance is:

Ds = K x (Ts + Tr ) + Dpf where: Ds = the separation distance; K = the OSHA-recommended hand speed constant of 63 inches per second (NOTE 1, below); Ts

= the overall stop time of the machine measured from the application of the “stop” signal to the final ceasing of all motion (including stop times of all relevant control elements, measured at maximum machine velocity). See NOTE 2, below.

Tr

= the response time of the MICRO-SCREEN System: .038 Seconds

Dpf = the added distance due to depth penetration factor, as prescribed in OSHA 1910.217 and ANSI B11 standards:

Floating blanking OFF

4" to 48" 24" to 72" V-Series sensor pairs sensor pairs Dpf = 1.6" Dpf = 3.3"

1-beam blanking ON

Dpf = 3.3"

Dpf = 6.7"

2-beam blanking ON

Dpf = 5.0"

Dpf = 31.5"

Floating Blanking Program

WARNING . . . Shock Hazard A shock hazard exists while the control box door is open. Before continuing, verify that the door is closed and triped.

WARNING . . . Calculate the Safety Distance Carefully

Failure to maintain appropriate separation distance can result in serious bodily injury or death.

NOTES: 1) The OSHA-recommended hand-speed constant K has been determined by various studies, and although these studies indicate speeds of 63 in/sec to over 100 in/sec, they are not conclusive determinations. The employer should consider all factors, including the physical ability of the operator, when determining the value of K to be used. 2) Ts is usually measured by a stop-time measuring device. If the specified machine stop time is used, we recommend that at least 20% be added as a safety factor to account for clutch/brake system deterioration. 3) Use of floating blanking will always cause the required Ds to increase.

Figure 29. Calculation of DS 46

Page 47

Alignment and Checkout 6) Test the effectiveness of the MICRO-SCREEN System with system power ON, as described in steps (a) through (d), below. The MICRO-SCREEN control module comes with three specified test pieces. Select the proper test piece based on system configuration, per the following chart: a)

Verify that the MICRO-SCREEN System is in RUN mode (green and yellow status indicators ON). See section 4.3 for the Key Reset procedure. The green indicator will flash if blanking is programmed.

Appropriate Test Pieces for Trip Test Floating Blanking Program

Standard Series Emitters and Receivers

V-Series Emitters and Receivers

Floating blanking OFF

19.1 mm (0.75") diameter Model STP-2

31.8 mm (1.25") diameter Model STP-4

1-beam floating blanking ON

31.8 mm (1.25" ) diameter Model STP-4

57.5 mm (2.25") diameter Model STP-5

2-beam floating blanking ON

44.5 mm (1.75") diameter Model STP-3

82.6 mm (3.25") diameter Model STP-9 b) With the guarded machine at rest, slowly pass the appropriate specified test piece downward through the defined area at three points, taking care to hold the test piece perpendicular to the defined area: close to the receiver column, close to the emitter column, and midway between the emitter and receiver columns (Figure 30). In each case, the red status indicator should come ON and remain ON for as long as the test piece is within the defined area. When the test piece is withdrawn from the defined area, the green status indicator should come ON. If the green indicator comes ON at any time when the test piece is within the defined area, check for reflective surfaces, or unguarded areas created by use of fixed blanking (see Warnings, page 49). Do not continue until the situation is corrected. (See section 3.2.2 and 3.2.4.) c)

Figure 30. Use of test piece in trip test

Initiate machine motion of the guarded machine and, during motion, insert the appropriate specified test piece into the defined area (perpendicular to the defined area). Do not attempt to insert the test piece into the dangerous parts of the machine. Upon insertion of the test piece into the defined area at any time during machine motion, the dangerous parts of the machine should come to a stop with no apparent delay. Upon removal of the test piece from the defined area, verify that the machine does not automatically restart, and that the initiation devices must be engaged to restart the machine.

WARNING . . . Do Not d) With the guarded machine at rest, insert the appropriate specified test piece into the defined area and verify that it is not possible for the guarded machine to be put into motion while the specified test piece is within the defined area.

Use Machine Until System Is Working Properly If all of the described checks cannot be verified, DO NOT USE the MICROSCREEN System/ guarded machine until the defect or problem has been corrected (see Section 5). Doing so could result in serious bodily injury or death.

7) Test the Emergency Stop switch (if one is connected to the system). With the machine running, engage the Emergency Stop switch (to open its contacts). Verify that the dangerous machine motion stops with no apparent delay. Test each Emergency Stop switch, individually, when two or more switches are series-connected to a MICROSCREEN control module. See Warning on page 27. 8) Remove electrical power to the MICRO-SCREEN System. All output relays should immediately de-energize, and should not be capable of being reactivated until power is re-applied and a Key Reset is performed (unless the Auto Power-up feature is ON). 9) Test the machine stopping response time using an instrument designed for that purpose to verify that it is the same or less than the overall system response time specified by the machine manufacturer. (NOTE: Banner’s Applications Engineering Department can recommend a suitable instrument.)

47

Page 48

Alignment and Checkout

6.3 Shift Change, Power-up and Machine Setup Change Checkout Daily checkout and checkouts after tooling and machine changes must be performed by a Designated Person appointed and identified in writing by the employer. During continuous machine run periods, this checkout must be performed at intervals not to exceed 24 hours. A copy of checkout results should be kept on or near the machine: see OSHA 1910.217(e)(1). The Designated Person must: 1) Verify that access to the dangerous parts of the guarded machine is not possible from any direction not protected by the MICROSCREEN System, hard guarding, or supplemental guarding, and verify that all supplemental guarding devices and hard guarding are in place and operating properly. 2) Verify that the minimum separation distance from the closest danger point of the guarded machine to the defined area is not less than the calculated distance. See Section 3.2.1. 3) Ensure that it is not possible for a person to stand between the defined area and the dangerous parts of the guarded machine. Or, verify that supplemental presence-sensing devices, such as safety mats, are in place and functioning properly in any space between the defined area and any danger point which is large enough to allow a person to stand undetected by the MICRO-SCREEN System. 4) Verify that the enclosure for the MICRO-SCREEN control module is triped and locked. The key (or combination or tool) to the locking mechanism should be in the possession of a Qualified Person.

WARNING . . . Be Sure Lockable Enclosure is Closed Before Proceeding A shock hazard exists while the lockable enclosure is open (see page 24). Before continuing, verify that the lockable enclosure is closed and triped. 5) Test the effectiveness of the MICRO-SCREEN with power ON, as described in steps (a) through (d), below.

Appropriate Test Pieces for Trip Test Floating Blanking Program a)

Standard Series Emitters and Receivers

V-Series Emitters and Receivers

Floating blanking OFF

19.1 mm (0.75") diameter Model STP-2

31.8 mm (1.25") diameter Model STP-4

1-beam floating blanking ON

31.8 mm (1.25) diameter Model STP-4

57.5 mm (2.25") diameter Model STP-5

2-beam floating blanking ON

44.5 mm (1.75") diameter Model STP-3

82.6 mm (3.25") diameter Model STP-9

Verify that the MICRO-SCREEN System is in RUN mode (green and yellow Status Indicators ON). See Section 4.3 for Reset procedure. b) With the guarded machine at rest, pass the appropriate specified test piece downward through the defined area at three points, perpendicular to the defined area: close to the receiver column, close to the emitter column, and midway between the emitter and receiver columns (see Figure 30). In each case, the red indicator must come ON and remain ON for as long as the test piece is within the defined area. When the test piece is removed from the defined area, the green status indicator should come ON (if blanking is ON, the green status indicator will be flashing). If the green status indicator comes ON at any time when the test piece is within the defined area, check for reflective surfaces, or unguarded areas created by the use of fixed blanking (see Warnings, page 49). Do not continue until the situation is corrected. (See Section 3.2.2 and 3.2.4.) c) Initiate machine motion of the guarded machine and, during motion, insert the specified test piece into the defined area (perpendicular to the defined area). Do not attempt to insert the test piece into the dangerous parts of the machine. Upon insertion of the test piece into the defined area at any time during machine motion, the dangerous parts of the machine should come to a stop with no apparent delay. Upon removal of the test piece from the defined area, verify that the machine does not automatically restart, and that the initiation devices must be engaged to restart the machine. d) With the guarded machine at rest, insert the specified test piece into the defined area and verify that it is not possible for the guarded machine to be put into motion while the specified test piece is within the defined area. 6) Test the Emergency Stop switch (if one is connected to the MICRO-SCREEN System). With the machine running, engage the Emergency Stop switch (to open its contacts). Verify that the dangerous machine motion stops with no apparent delay. Test each Emergency Stop switch, individually, when two or more switches are series-connected to a MICRO-SCREEN System. See Warning on page 27. 48

Page 49

Alignment and Checkout 7) Check carefully for external signs of damage to the MICRO-SCREEN System, the guarded machine, and their electrical wiring. Any damage found should be immediately reported to management.

6.4 Semi-annual Checkout (To Be Performed at Six-month Intervals) This semi-annual checkout must be done by a Qualified Person. A copy of test results should be kept on or near the machine. The Qualified Person must: 1) Perform the Commissioning Checkout Procedure (Section 6.2). If any decrease in machine braking ability has occurred, make the necessary clutch/brake repairs, readjust Ds appropriately, and re-perform the checkout sequence of Section 6.2. 2) Examine and test the machine primary control elements (MPCEs) to ensure that they are functioning correctly and are not in need of maintenance or replacement. 3) Inspect the guarded machine to ensure that there are no other mechanical or structural problems that would prevent the machine from stopping or assuming an otherwise safe condition when signalled to do so by the MICRO-SCREEN System. 4) Examine and inspect the machine controls and connections to the MICRO-SCREEN System to ensure that no modifications have been made which adversely affect the system.

WARNING . . . Do Not Use Machine Until System Is Working Properly If all of the described checks cannot be verified, DO NOT USE the MICROSCREEN System-guarded machine until the defect or problem has been corrected (see Section 5). Doing so could result in serious injury or death.

WARNING . . . Hard Guarding If any object that is to be ignored by fixed blanking does not, itself, completely prevent access to the danger point(s), you must install hard guarding to prevent access past the object, or increase the separation distance.

WARNING . . . Reflective Surfaces It may be possible for a highly reflective surface (a shiny machine surface or a shiny workpiece) to reflect sensing light around an object in the defined area, preventing that object from being detected. This potentially dangerous condition is discovered using the trip test as described in the Initial Checkout Procedure (Section 3.5.4), the Alignment Procedure (Section 6.1), and the periodic checkout procedures (Sections 6.2, 6.3, and 6.4). When this condition is discovered, eliminate the problem reflection(s). If possible, relocate the sensors to move the defined area away from the reflective surface(s), being careful to retain at least the required separation distance (Section 3.2.1). Otherwise, paint, mask, or roughen the interfering shiny surface to reduce its reflectivity. Repeat the trip test to verify that these changes have eliminated the problem reflection(s). See Section 3.2.4. NOTE: If the workpiece is especially reflective and comes close to the defined area, perform the trip test with the shiny workpiece in place.

Openings in the hard guarding material must meet OSHA criteria (see OSHA 1910.217, Table O-10). Failure to hard guard any opening caused by fixed blanking or failure to adequately increase the separation distance will create an unsafe condition which could lead to serious injury or death. See Section 3.2.2.

49

Page 50

Glossary

Glossary of Terms Terms shown in italics in the definitions below are themselves defined elsewhere in the glossary. ANSI (American National Standards Institute): An association of industry representatives which develops technical standards, including safety standards. These standards represent a consensus from a variety of industries on good practice and design. ANSI standards relevant to application of the MICRO-SCREEN System include ANSI B11.1 (mechanical power presses), ANSI B11.2 (hydraulic power presses), and ANSI/RIA R15.06 (industrial robots and robot systems). See page 62. Auxiliary monitor or Alarm contact: A low-load-capacity, non-safety-related relay contact within the MICRO-SCREEN System whose primary purpose is to communicate system status to a PLC. Auto Power-up: A feature of the MICRO-SCREEN control module which, when switched ON, enables the MICRO-SCREEN to be powered up (and recover from a power interruption) without the necessity of a Key Reset. When Auto Power-up is ON, the MICRO-SCREEN control module automatically begins internal diagnostics upon powerup, and automatically resets the system if it passes the diagnostic check. With Auto Power-up OFF, a manual Key Reset is required. Blanking: (See fixed blanking and floating blanking.) Control reliability: A method of ensuring the performance integrity of a control system. Control circuits are designed and constructed so that a single failure or fault within the system does not prevent the normal stopping action from being applied to the machine when required, or does not create unintended machine action, but does prevent initiation of successive machine action until the failure is corrected. Control module: Contains the circuitry (internal to the MICRO-SCREEN System) that provides the proper voltages to the system, controls the sensing units, receives and processes information from the sensing units and the safety monitoring means, and provides outputs to the Final Switching Devices (FSD1 and FSD2), the Secondary Switching Device (SSD), and the Auxiliary Monitor Relay. Controller board: A removable printed circuit board, located within the MICROSCREEN System control module, which contains the microprocessors and related electronic circuits. Defined area: The “light screen” or “curtain of light” generated by the MICRO-SCREEN System. When the defined area is interrupted by an opaque object of a specified cross section or larger, a trip condition results (see Figure 1). Designated Person: A person or persons identified and designated in writing, by the employer, as being appropriately trained and qualified to perform a specified checkout procedure.