The text of a spec sheet · part 11 of 25
Modular electrical terminal CPX, pages 101 to 110
Pages 101 to 110 of 246
The original document is the PDF (8.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Festo CPX-EPL-EV
Page 101
Terminal CPX Technical data – Bus node CPX-M-FB35/CPX-M-FB41 General technical data Type
CPX-M-FB35
Fieldbus interface Baud rate Protocol Max. address capacity LED displays
[Mbps]
Inputs Outputs (bus-specific)
[byte] [byte]
(product-specific)
Device-specific diagnostics
Configuration support Parameterisation
Additional functions
Control elements Operating voltage
Nominal value Permissible range Intrinsic current consumption at nominal operating voltage Degree of protection to EN 60529 Temperature range Operation Storage/transport Housing material Note on materials Grid dimension Dimensions (incl. interlinking block) W x L x H Product weight
[V DC] [V DC] [mA] [°C] [°C]
[mm] [mm] [g]
-H- Note
-H- Note
Please observe the general limits and guidelines for the system when configuring the electrical modules.
Always use the correct screws for the interlinking block; this depends on whether the block is made of metal or polymer:
2018/04 – Subject to change
CPX-M-FB41
2x SCRJ push-pull socket, AIDA 1x SCRJ push-pull socket, AIDA 100 PROFINET RT PROFINET RT PROFINET IRT – 64 64 M/P = Maintenance/PROFIenergy NF = Network fault NF = Network fault TP1 = Network active port 1 TP1 = Network active port 1 TP2 = Network active port 2 M = Modify, parameterisation PL = Load supply PS = Electronic supply, sensor supply SF = System fault Channel and module-oriented diagnostics Undervoltage of modules Diagnostic memory GSDML file System parameters Diagnostic behaviour Signal setup Fail-safe response Forcing of channels Start-up parameterisation in plain text via fieldbus Fast start-up (FSU) Channel-oriented diagnostics via fieldbus Acyclic data access via fieldbus and via Ethernet System status can be displayed using process data Additional diagnostic interface for operator unit DIL switch, optional memory card 24 18 … 30 Typically 150 Typically 125 IP65, IP67 – 5… +50 –20 … +70 Die-cast aluminium RoHS-compliant 50 50 x 107 x 80 280
Self-tapping screws for polymer interlinking blocks
è Internet: www.festo.com/catalogue/...
Screws with metric thread for metal interlinking blocks
101
Page 102
Terminal CPX Technical data – Bus node CPX-M-FB35/CPX-M-FB41 Connection and display components
2
1 4
3
3
Pin allocation for the fieldbus interface Terminal allocation
1 Bus-specific status LEDs 2 CPX-specific status LEDs 3 Fieldbus connection (SCRJ socket, 2-pin) 4 DIL switch and memory card
Pin
Signal
Designation
1
TX
Outgoing
2
RX
Incoming
SCRJ socket
102
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 103
Terminal CPX Accessories – Bus node CPX-M-FB35/CPX-M-FB41 Ordering data Description
Part No.
Type
2x SCRJ push-pull socket, AIDA
548749
CPX-M-FB35
1x SCRJ push-pull socket, AIDA
3228960
CPX-M-FB41
SCRJ plug, 2-pin, push-pull
571017
FBS-SCRJ-PP-GS
Cover cap for bus connection
548753
CPX-M-AK-C
Cover cap for bus connection
2873540
CPX-M-AK-D
Cover for DIL switch and memory card
548754
CPX-M-AK-M
Memory card for PROFINET bus node, 2MB
568647
CPX-SK-2
Screws for attaching an inscription label to the bus node (12 pieces)
550222
CPX-M-M2,5X8-12X
5-pin M12 adapter for mini USB socket and controller software
547432
NEFC-M12G5-0.3-U1G5
Electronics manual, CPX bus node, type CPX-M-FB35/CPX-M-FB41
548759 548760 548761 548762 548763
P.BE-CPX-PNIO-DE P.BE-CPX-PNIO-EN P.BE-CPX-PNIO-ES P.BE-CPX-PNIO-FR P.BE-CPX-PNIO-IT
Bus node PROFINET bus node
Bus connection
User documentation
2018/04 – Subject to change
German English Spanish French Italian
è Internet: www.festo.com/catalogue/...
103
Page 104
Terminal CPX Technical data – Bus node CPX-FB36 Bus node for handling communication between the electrical terminal CPX and the EtherNet/IP network. The bus node is provided with system supply via the interlinking block and processes communication with the I/O modules. The status of the terminal CPX is displayed as a common message via 4 CPX-specific LEDs.
Industrial Ethernet EtherNet/IP IT services: Web
Application Bus connection The bus connection is established via an M12 plug, D-coded to IEC947-5-2 with IP65, IP67 protection.
EtherNet/IP is an open bus system based on the Ethernet standard and TCP/IP technology (IEEE802.3).
EtherNet/IP implementation The CPX-FB36 supports the two oper ating modes: remote I/O and remote controller. In remote I/O operating mode, all functions of the CPX valve terminal are directly controlled by the EtherNet/IP master (host). In addition to actuation via a bus system, it is possible to use IT technologies. An integrated web server enables diagnostic data to be visualised via HTML. Various programs support direct access to the data of the device from the automation network. The EtherNet/IP node for CPX supports the transmission technology that conforms to DIN EN 50173/CAT 5.
When combining a bus node with a control block (CPX-CEC, in fieldbus remote controller operating mode), the connected I/Os or valves, sensors and actuators are controlled via the CPX control block.
In this case, the bus node only provides the communication interface to the PLC. Communication between the control block and CPX bus node takes place via interlinking of the CPX modules and takes up the following address capacity in the CPX system: 8 byte outputs 8 byte inputs The following address capacity remains in the control block or CPX system for actuation of the peripherals: 56 byte inputs 56 byte outputs
104
è Internet: www.festo.com/catalogue/...
Points to note in connection with CPX-CEC
Subject to change – 2018/04
Page 105
Terminal CPX Technical data – Bus node CPX-FB36 General technical data Type Fieldbus interface Baud rates Protocol Max. address capacity, inputs Max. address capacity, outputs LED displays (bus-specific)
CPX-FB36 [Mbit/s]
[byte] [byte]
Device-specific diagnostics
Configuration support Parameterisation
Additional functions
Control elements Operating voltage
Nominal value Permissible range Current consumption (at nominal voltage, without MMI) Protection class to EN 60529 Temperature range Operation Storage/transport Materials Note on materials Grid dimension Dimensions (incl. interlinking block) W x L x H Product weight
[V DC] [V DC] [mA] [°C] [°C]
[mm] [mm] [g]
2x M12x1 socket, D-coded, 4-pin 10/100 EtherNet/IP Modbus TCP 64 64 MS = Module status NS = Network status TP1 = Network active port 1 TP2 = Network active port 2 Module and channel-oriented diagnostics Module undervoltage Diagnostic memory EDS file L5K export with CPX-FMT Diagnostic behaviour Fail-safe response Forcing of channels Idle mode characteristics Signal setup System parameters EtherNet/IP Quickconnect Ring topology (DLR) Acyclic data access via "Explicit Message" and Ethernet Integrated switch IP addressing via DHCP, DIL switch or operator unit Channel-oriented diagnostics via fieldbus Start-up parameterisation in plain text via fieldbus System status can be represented using process data Additional diagnostic interface for operator units DIL switches 24 18 … 30 Typically 100 IP65, IP67 –5 … +50 –20 … +70 PA reinforced RoHS-compliant 50 50 x 107 x 50 125
-H- Note Please observe the general limits and guidelines for the system when configuring the electrical modules.
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
105
Page 106
Terminal CPX Technical data – Bus node CPX-FB36 Connection and display components
1
2 3 1 Bus-specific status LEDs 2 CPX-specific status LEDs 3 Fieldbus connection (4-pin socket M12, D-coded) 4 Transparent DIL switch cover
4 3
Pin allocation for the fieldbus interface Pin allocation
Pin
Signal
Designation
1 2 3 4 Hous ing
TD+ RD+ TDRDFE
Transmitted data+ Received data+ Transmitted dataReceived dataScreening
M12 socket, D-coded
106
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 107
Terminal CPX Accessories – Bus node CPX-FB36 Ordering data Designation
Part No.
Type
EtherNet/IP bus node
1912451
CPX-FB36
Plug M12x1, 4-pin, D-coded
543109
NECU-M-S-D12G4-C2-ET
8040446 8040447 8040448 8040449 8040450 8040451 8040452 8040453 8040454 8040456 548757
NEBC-D12G4-ES-0.5-S-D12G4-ET NEBC-D12G4-ES-1-S-D12G4-ET NEBC-D12G4-ES-3-S-D12G4-ET NEBC-D12G4-ES-5-S-D12G4-ET NEBC-D12G4-ES-10-S-D12G4-ET NEBC-D12G4-ES-1-S-R3G4-ET NEBC-D12G4-ES-3-S-R3G4-ET NEBC-D12G4-ES-5-S-R3G4-ET NEBC-D12G4-ES-10-S-R3G4-ET NEBC-LE4-ES-5-D12G4-ET CPX-AK-P
Inspection cover, transparent
533334
AK-SUB-9/15-B
Inscription label holder for connection block
536593
CPX-ST-1
5-pin M12 to mini USB socket adapter and controller software
547432
NEFC-M12G5-0.3-U1G5
8024074 8024075 8024076 8024077 8024078 8024079
CPX-FB36-DE CPX-FB36-EN CPX-FB36-ES CPX-FB36-FR CPX-FB36-IT CPX-FB36-ZH
Bus node
Bus connection
Connecting cable, straight plug, M12x1, 4-pin, D-coded
Straight plug, M12x1, 4-pin, D-coded
Straight plug, RJ45, 8-pin
Open end, 4-wire Transparent cover for DIL switch and memory card
0.5 m 1m 3m 5m 10 m 1m 3m 5m 10 m 5m
Manual Electronics manual, CPX bus node, type CPX-FB36
2018/04 – Subject to change
German English Spanish French Italian Chinese
è Internet: www.festo.com/catalogue/...
107
Page 108
Terminal CPX Technical data – Bus node CPX-FB37 Bus node for operating the CPX valve terminal on EtherCAT. The bus node is provided with system supply via the interlinking block and processes communication with the I/O modules. The status of the terminal CPX is displayed as a common message via 4 CPX-specific LEDs. The fieldbus communication status is displayed via 4 bus-specific LEDs.
Application Bus connection Both connections are equivalent 100BaseTX Ethernet ports with integrated auto MDI functionality
(cross-over and patch cable can be used) that are brought together via an internal switch.
Maximum segment length 100 m Transmission rate 100 Mbps
The data bandwidth is sufficient to transmit both data types (real-time and non-real-time) in parallel. The bus node features LEDs for bus status and CPX peripheral information as well as switch elements and a dia gnostic interface. The bus node can be used as a remote I/O or remote con troller. All information relevant to the CPX can be read out and, dependent on the function, changed via an MMI/FMT.
The functions MDP (modular device profile) and CoE (CAN over EtherCAT) enable easy access to parameters and diagnostic data via EtherCAT.
EoE (Ethernet over EtherCAT): diagnostic data can be retrieved easily using a browser MDP (modular device profile): easy configuration using a module selection box Hot Connect, easy replacement of an EtherCAT CPX terminal DC (distributed clocks), timesynchronised data transmission
The bus connection is established via two M12x1 sockets, D-coded to IEC61076-2-101 with degree of protection to IP65, IP67. EtherCAT implementation The CPX-FB37 supports the EtherCAT protocol based on the Ethernet standard and TCP/IP technology to IEEE802.3. This guarantees a data exchange with a high data transmission rate, for ex ample I/O data from sensors, actuat ors or robot controllers, PLCs or pro cess equipment. Furthermore, non real-time critical information such as diagnostic information, configuration information, etc. can be transferred.
Specific EtherCAT functions: CoE (parameters and diagnostics or fail-safe mode): all module parameters can be set FoE (file over EtherCAT) makes it possible to download firmware easily
Points to note in connection with CPX-CEC When a bus node is combined with a control block (CPX-CEC, in the fieldbus remote controller operating mode), the connected I/Os and/or valves, sensors and actuators are controlled via the CPX control block.
In this case, the bus node only provides the communication interface to the PLC. Communication between the control block and CPX bus node takes place by
108
è Internet: www.festo.com/catalogue/...
interlinking the CPX modules and takes up the following address capacity in the CPX system: 8/16 byte outputs 8/16 byte inputs
The following address capacity remains in the control block or CPX system for activating the peripherals: 56/48 byte inputs 56/48 byte outputs
Subject to change – 2018/04
Page 109
Terminal CPX Technical data - Bus node CPX-FB37 General technical data Type Fieldbus interface Baud rates Protocol Max. address capacity LED displays
CPX-FB37 [Mbps] Inputs Outputs Bus-specific
[byte] [byte]
Product-specific
Device-specific diagnostics
Configuration support Parameterisation
Additional functions
Control elements Operating voltage Current consumption Degree of protection to EN 60529 Temperature range
Nominal value Permissible range
[V DC] [V DC] [mA]
Operation Storage/transport Housing
[°C] [°C]
Materials Note on materials Grid dimension Dimensions (incl. interlinking block) W x L x H Product weight
[mm] [mm] [g]
-H- Note
-H- Note
Please observe the general limits and guidelines for the system when configuring the electrical modules.
Always use the correct screws for the interlinking block; this depends on whether the block is made of metal or polymer:
2018/04 – Subject to change
2x M12x1 socket, 4-pin, D-coded 100 EtherCAT 64 64 Error = Communication error L/A1 = Network active port 1 L/A2 = Network active port 2 Run = Communication status M = Modify, parameterisation PL = Load supply PS = Electronic supply, sensor supply SF = System fault Channel and module-oriented diagnostics Undervoltage of modules Diagnostic memory ESI file System parameters Diagnostic behaviour Signal setup Fail-safe response Forcing of channels System status can be displayed using process data Additional diagnostic interface for operator units Emergency message Acyclic data access via fieldbus Diagnostic object Compatibility mode for the CPX-FB38 Modular device profile (MDP) Variable PDO mapping DIL switches 24 18 … 30 Typically 100 IP65, IP67 –5 … +50 –20 … +70 Reinforced PA RoHS-compliant 50 50 x 107 x 50 125
Self-tapping screws for polymer interlinking blocks
è Internet: www.festo.com/catalogue/...
Screws with metric thread for metal interlinking blocks
109
Page 110
Terminal CPX Technical data – Bus node CPX-FB37 Connection and display components
2
1
1 Bus-specific status LEDs 2 CPX-specific status LEDs 3 Fieldbus connection, input (M12x1 socket, 4-pin, D-coded) 4 Fieldbus connection, output (M12x1 socket, 4-pin, D-coded) 5 DIL switch
3
5
4
Pin allocation for the fieldbus interface Terminal allocation
Pin
Signal
Designation
1
TD+
Transmitted data+
2
RD+
Received data+
3
TD-
Transmitted data-
4
RD-
Received data-
Housing
FE
Screening
M12x1 socket, D-coded
110
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04