Page 121

Terminal CPX Technical data – Bus node CPX-FB40 General technical data Type Fieldbus interface Baud rates Protocol Max. address capacity LED displays

CPX-FB40 [Mbps] Inputs Outputs Bus-specific

[byte] [byte]

Product-specific

Device-specific diagnostics

Configuration support Parameterisation

Additional functions

Control elements Operating voltage

Nominal value [V DC] Permissible range [V DC] Protection against incorrect polarity Current consumption (at nominal voltage, without MMI) [mA] Degree of protection to EN 60529 Temperature range Operation [°C] Storage/transport [°C] Materials Note on materials Grid dimension [mm] Dimensions (incl. interlinking block) W x L x H [mm] Product weight [g]

2x M12x1 socket, D-coded, 4-pin 100 Ethernet POWERLINK V2 64 64 BE = POWERLINK error BS = POWERLINK status L/A1 = Link/activity port 1 L/A2 = Link/activity port 2 M = Modify, parameterisation PL = Load supply PS = Electronic supply, sensor supply SF = System fault Module and channel-oriented diagnostics Undervoltage of modules Diagnostic memory XDC file XDD file Diagnostic behaviour Fail-safe response Forcing of channels Signal setup System parameters Acyclic data access via "SDO" and Ethernet Integrated hub IP addressing via DHCP, DIL switch or operator unit Channel-oriented diagnostics via fieldbus Start-up parameterisation in plain text via fieldbus System status can be displayed using process data Additional diagnostic interface for operator units DIL switches 24 18 … 30 For operating voltage Typically 100 IP65, IP67 –5 … +50 –20 … +70 PA reinforced RoHS-compliant 50 50 x 107 x 50 125

-H- Note Please observe the general limits and guidelines for the system when configuring the electrical modules.

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

121

Page 122

Terminal CPX Technical data – Bus node CPX-FB40 Connection and display components

1

2 3 1 Bus-specific status LEDs 2 CPX-specific status LEDs 3 Fieldbus connection (M12x1 socket, 4-pin, D-coded) 4 Transparent DIL switch cover

4 3

Pin allocation for the fieldbus interface Terminal allocation

Pin

Signal

Designation

1 2 3 4 Hous­ ing

TD+ RD+ TDRDFE

Transmitted data+ Received data+ Transmitted dataReceived dataScreening

M12x1 socket, D-coded

122

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 123

Terminal CPX Accessories – Bus node CPX-FB40 Ordering data Description

Part No.

Type

Ethernet POWERLINK bus node

2474896

CPX-FB40

M12x1 plug connector, 4-pin, D-coded

543109

NECU-M-S-D12G4-C2-ET

8040446 8040447 8040448 8040449 8040450 8040451 8040452 8040453 8040454 8040456 548757

NEBC-D12G4-ES-0.5-S-D12G4-ET NEBC-D12G4-ES-1-S-D12G4-ET NEBC-D12G4-ES-3-S-D12G4-ET NEBC-D12G4-ES-5-S-D12G4-ET NEBC-D12G4-ES-10-S-D12G4-ET NEBC-D12G4-ES-1-S-R3G4-ET NEBC-D12G4-ES-3-S-R3G4-ET NEBC-D12G4-ES-5-S-R3G4-ET NEBC-D12G4-ES-10-S-R3G4-ET NEBC-LE4-ES-5-D12G4-ET CPX-AK-P

Inspection cover, transparent

533334

AK-SUB-9/15-B

Inscription label holder for connection block

536593

CPX-ST-1

5-pin M12 adapter for mini USB socket and controller software

547432

NEFC-M12G5-0.3-U1G5

8028650 8028651 8028652 8028653 8028654 8028655

P.BE-CPX-FB40-DE P.BE-CPX-FB40-EN P.BE-CPX-FB40-ES P.BE-CPX-FB40-FR P.BE-CPX-FB40-IT P.BE-CPX-FB40-ZH

Bus node

Bus connection

Connecting cable, straight plug, M12x1, 4-pin, D-coded

Straight plug, M12x1, 4-pin, D-coded

Straight plug, RJ45, 8-pin

Open end, 4-wire Transparent cover for DIL switch and memory card

0.5 m 1m 3m 5m 10 m 1m 3m 5m 10 m 5m

User documentation User documentation for bus node CPX-FB40

2018/04 – Subject to change

German English Spanish French Italian Chinese

è Internet: www.festo.com/catalogue/...

123

Page 124

Terminal CPX Technical data – CPX-CP interface The CPX-CP electrical interface esta­ blishes the connection to CP modules of the CPI installation system via prefabricated connecting cables. The I/O data of the connected valve termi­ nals with CP string extension and CP input and output modules are trans­ ferred to the connected CPX bus node and thus via fieldbus to the higherorder controller. This enables modular centralised and compact decentralised concepts to be established with one system.

Application CP connection As well as transmitting the communi­ cation data, the max. four CP strings of a CPX-CP interface also transmit the supply voltage to the connected sen­ sors and the load supply to the valves (or outputs). Both circuits are supplied separately with 24 V, but with a common reference potential. The valve terminals with CP string ex­ tension (or outputs) are supplied with voltage for the electronics and valves by the interlinking block.

The following combinations are made possible by the CP interface: Centralised analogue and digital inputs and outputs of the CPX terminal

Decentralised digital inputs and outputs of the CP installation system Valve/valve terminals that can be connected both centrally and decentrally

Configuration example – CP interface with CP modules

124

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 125

Terminal CPX Technical data – CPX-CP interface Implementation The CPX-CP interface supports the CPI system: Max. 4 individual electronically protected CP strings Max. 4 CP modules per string Max. 32 inputs/32 outputs per string The maximum length of a string is 10 m. If the CP interface is positioned centrally, the CP system can cover an area of 20 m in diameter Modules with CPI functionality

The following CP module variants are available: Input modules with 8 or 16 digital inputs (connection technology M8, M12 and CageClamp) Output modules with 4 or 8 digital outputs (connection technology M12) Valve terminals with CP string extension (up to 32 solenoid coils, different valve functions)

CPI modules support the following functions: Module-oriented diagnostics Module/channel-oriented parameterisation Support for all functions by the CPX-MMI or CPX-FMT operator unit Module can be positioned anywhere within the string

Several CP interface modules can be combined in one CPX terminal, depending on the address capacity of the bus node. Example: CPX-FB13 (512 I/O) Max. 4 CP interface modules (128 I/O each) possible

Maximum extension: 4 input modules and 4 valve terminals/output modules without CPI functionality 16 CP modules with CPI functionality

The configuration of the strings with respect to the module type and posi­ tion of the modules in the string is entered by activating the SAVE key in the CPX-CP interface and saved there remanently. Saved data are retained even when the CP interface is isolated from the voltage supply.

The representation of the CP inter­ face within a CPX terminal and thus at the fieldbus is dependent on the characteristics of the relevant field­ bus system. In addition to input and output addressing, this also applies to the representation of the diag­ nostics and parameterisation of the CP module and the characteristics of the CPI system.

-H- Note When arranging the CP modules it should be taken into consideration that CP input modules without CPI functionality should always be placed at the end of a string.

Configuration The following rules apply for a string of a CPX-CP interface: Max. one output module or one valve terminal without CPI functionality Max. one output module without CPI functionality or one valve terminal with CP string extension Any number of CP modules with CPI functionality, up to the maximum limit of 4 modules and/ or 32 inputs/32 outputs per string

-H- Note The remanent saving of configur­ ation data means that changes in the configuration or faulty modules are still displayed even after a voltage failure.

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

125

Page 126

Terminal CPX Technical data – CPX-CP interface General technical data Type Brief description Max. number of

CP connection Baud rate Cycle time

CPX-CP-4-FB

[kbit/s] [ms]

CP interface 4 4 32 32 M9 socket, 5-pin 1,000 4

[ms]

2

CP strings CP modules per string Outputs per string Inputs per string

CP modules without CPI functionality CP modules with CPI functionality

LED displays

Device-specific diagnostics Operating voltage

Supply voltage of sensors Load voltage of actuators Current consumption Protection class to EN 60529 Temperature range

L1 … 4 = Status of the CP string 1 … 4 PS = Electronic supply, sensor supply PL = Load supply RN = Status of the CP system SF = System fault Nominal value Permissible range Power failure buffering

Without CP modules Per CP string

[V DC] [V DC] [ms] [V DC] [V DC] [A] [A]

Operation Storage/transport

[°C] [°C]

Materials Grid dimension Dimensions (incl. interlinking block) W x L x H Weight

[mm] [mm] [g]

Via bus node 24 (reverse polarity protected) 18 … 30 20 24 ±25% coming from bus node 24 ±10% coming from bus node Max. 0.2 Max. 1.6 IP65, IP67 –5 … +50 –20 … +70 PA 50 50 x 107 x 45 140

-H- Note Please observe the general limits and guidelines for the system when configuring the electrical modules.

126

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 127

Terminal CPX Accessories CPX-CP interface Connection and display components 1

4

2

3

5

1 CP string LEDs 2 SAVE key 3 Holders for inscription labels (IBS 6x10) 4 CPX-specific status LEDs 5 CP connections for up to 4 strings (0 … 3)

Power supply The module combines the 0 V potential of the power supply for electronics and sensors with the 0 V potential of the power supply for valves. If all poles of the valves of a pneumatic interface connected to the right of the CP interface are to be switched off, an appropriate interlinking block with additional power supply must be used to the right of the CP interface.

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

127

Page 128

Terminal CPX Accessories CPX-CP interface Ordering data Designation

Part No.

Type

Interface for max. 16 I/O modules and valve terminals of the CPI system

526705

CPX-CP-4-FB

Cover cap

M12

165592

ISK-M12

Connecting cable, angled plug, angled socket

0.25 m 0.5 m 2m 5m 8m 2m 5m 8m

540327 540328 540329 540330 540331 540332 540333 540334 536593

KVI-CP-3-WS-WD-0,25 KVI-CP-3-WS-WD-0,5 KVI-CP-3-WS-WD-2 KVI-CP-3-WS-WD-5 KVI-CP-3-WS-WD-8 KVI-CP-3-GS-GD-2 KVI-CP-3-GS-GD-5 KVI-CP-3-GS-GD-8 CPX-ST-1

German English Spanish French Italian

539293 539294 539295 539296 539297

P.BE-CPX-CP-DE P.BE-CPX-CP-EN P.BE-CPX-CP-ES P.BE-CPX-CP-FR P.BE-CPX-CP-IT

CP interface

Bus connection

Connecting cable, straight plug, straight socket

Inscription label holder for connection block

User manual User manual for CPX-CP interface

128

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 129

Terminal CPX Technical data – Interface CPX-CTEL The electrical interface CPX-CTEL master establishes the connection to modules with I-Port interface (device) from the CTEL/CTEU series. The I/O data from the connected devices is transferred to the connected CPX bus node and therefore transferred to the higher-level controller via fieldbus. A maximum of 4 devices can be connected to a CPX­CTEL master via appropriate M12­ interfaces.

Application I-Port interface As well as transmitting the communication data, the I-Port interfaces of a CPX­CTEL master also transmit the power supply for the connected sensors and the load supply for the valves (or outputs). Both circuits are supplied separately with 24 V, with a separate reference potential. The connecting cables used must meet the increased requirements resulting from their double function as a signal line and power supply cable.

The CPX­CTEL master provides four I-Port interfaces to which one device each can be connected. I-Port is an interface for exchanging serial data for connecting decentralised mod­ ules or valve terminals from Festo. The I-Port interface is based on IOLink and is compatible with it in cer­ tain areas. The connection type corresponds to a star topology. In other words, only one module or valve terminal can be connected to each I-Port.

The restrictions compared to IO-Link include: Permanently set baud rate of 230.4 kbit/s SIO mode is not supported Max. 32 bytes of input data and 32 bytes of output data Only one dump of the master commands is used Configuration via IODD is not supported

Sample configuration – CPX­CTEL master with CTEL modules

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

129

Page 130

Terminal CPX Technical data – Interface CPX-CTEL Implementation The CPX­CTEL master from Festo enables modules with an I-Port interface to be connected to a CPX system: Max. 4 devices with individual electronic fuse protection Max. 64 inputs/64 outputs per I-Port interface The maximum length of a string is 20 m Configuration Setting The precise number of I/O bytes made available is geared towards the requirements of the connected devices and the selected operating mode. The operating mode and configuration presetting of the CPX­CTEL master can be defined by the user. DIL switches are used for selecting the operating mode and making the setting for manual configuration. These DIL switches are not required during operation and are only accessible in unassembled condition.

The following device variants are available: Input modules with 16 digital inputs (3-pin M8 and 5-pin M12 connection technology) Valve terminals with I-Port interface (up to 48 solenoid coils, different valve functions)

The decentralised arrangement of the modules and valve terminals with I-Port enables them to be mounted near the cylinders and actuators/sensors to be controlled. This allows the use of shorter air supply lines and sensor connecting cables or possibly smaller valves, which saves costs.

Manual configuration

Several CPX­CTEL masters can be combined in one CPX terminal, depending on the address capacity of the bus node. Example: CPX-FB13 (512 I/O) Max. 2 CPX­CTEL masters (256 I/O each) possible

Automatic configuration

With manual configuration (tool change mode), the number of inputs and outputs in the process image of the CPX system or higher-level fieldbus can be manually defined via the DIL switches.

The process image then always has the same number of bytes, regardless of the connected devices. The defined I/O length always applies to all four I-Ports (max. 8 bytes per I-Port).

With automatic configuration, the I/O length for each I-Port is individually determined and this value is used to select the appropriate or next highest configuration presetting.

The CPX-CTEL master provides two separate power supplies for the connected devices: One for operating the device and the inputs connected to it One for outputs and valves connected to the device

The power supply for devices and inputs comes from the power supply for the electronics and sensors of the CPX terminal. The power supply for outputs and valves comes from the power supply for the valves of the CPX terminal. The interlinking block with additional power supply enables a separate voltage supply for valves and outputs. This allows this supply voltage to be switched off separately. In other words, the valves and outputs of the connected I-Port devices can be switched off separately without having to switch off the devices themselves.

130

è Internet: www.festo.com/catalogue/...

Power supply for I-Port devices

Subject to change – 2018/04