Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 14 of 25

Modular electrical terminal CPX, pages 131 to 140

Pages 131 to 140 of 246

The original document is the PDF (8.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Festo CPX-EPL-EV

Page 131

Terminal CPX Technical data – Interface CPX-CTEL General technical data Type Protocol Max. address capacity I-Port connection Number of I-Port interfaces Max. cable length Internal cycle time Electrical isolation

CPX-CTEL-4-M12-5POL Outputs Inputs

[bit] [bit]

[m] [ms] Channel – channel Channel – internal bus

LED displays

Diagnostics

Parameterisation

Additional functions Operating elements Operating voltage

Nominal value Permissible range Power failure buffering Intrinsic current consumption at nominal operating voltage Max. power supply per channel Max. residual output current per channel Protection class to EN 60529 Temperature range Operating Storage/transport Materials Note on materials Grid dimension Dimensions (incl. interlinking block) W x L x H Product weight

[V DC] [V DC] [ms] [mA] [A] [A] [°C] [°C]

[mm] [mm] [g]

I-Port 256 256 4x M12 socket, 5-pin, A-coded 4 20 1 per 8 bits of user data No Yes, using an intermediate supply X1 … 4 = Status of the I-Port interface 1 … 4 PS = Electronics supply PL = Load supply -P= Module fault Communication error Module short circuit Module-oriented diagnostics Undervoltage Diagnostic behaviour Failsafe per channel Forces per channel Idle mode per channel Module parameters Tool change mode Tool change mode DIL switch 24 (reverse polarity protected) 18 … 30 10 Typically 65 4x 1.6 4x 1.6 IP65, IP67 –5 … +50 –20 … +70 PA reinforced, PC RoHS-compliant 50 50 x 107 x 55 110

-H- Note Please observe the general limits and guidelines for the system when configuring the electrical modules.

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

131

Page 132

Terminal CPX Technical data – Interface CPX-CTEL Connection and display components 1

2

1 Status LEDs for I-Port interfaces 2 CPX-specific status LEDs 3 Holders for inscription labels (IBS 6x10) 4 I-Port interfaces for up to 4 devices

4

3

Combinations of bus nodes/control blocks and interface CPX-CTEL Bus node/control block Part No.

Interface CPX-CTEL-4-M12-5POL n n n n n n n n n n n n n n n n n n

CPX-CEC-C1 CPX-CEC-C1-V3 CPX-CEC-M1-V3 CPX-CEC CPX-CEC-S1-V3 CPX-FB11 CPX-FB13 CPX-FB14 CPX-FB23-24 CPX-FB33 CPX-M-FB34 CPX-M-FB35 CPX-FB36 CPX-FB37 CPX-FB38 CPX-FB39 CPX-FB40 CPX-M-FB41

567347 3473128 3472765 567346 3472425 526172 195740 526174 526176 548755 548751 548749 1912451 2735960 552046 2093101 2474896 3228960

Pin allocation – I-Port interface Pin allocation

Pin

Signal

Designation

1

24 VSEN

24 V DC supply voltage for electronics and inputs

2

24 VVAL

24 V DC load voltage supply for valves and outputs

3

0 VSEN

0 V DC supply voltage for electronics and sensors

4

C/Q I-Port

Communication signal C/Q, data cable

5

0 VVALVES

0 V DC load voltage supply for valves and outputs

132

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 133

Terminal CPX Technical data – Interface CPX-CTEL Download CAD data è www.festo.com

Dimensions

Type

B1

B2

B3

H1

L1

CPX-CTEL-4-M12-5POL

108.1

118.9

124.9

55.1

50

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

133

Page 134

-V- New Terminal CPX Accessories – Interface CPX-CTEL Ordering data Designation

Part No.

Type

Interface for max. 4 I/O modules and valve terminals with I-Port interface (devices)

1577012

CPX-CTEL-4-M12-5POL

Cover cap

M12

165592

ISK-M12

Connecting cable M12-M12, 5-pin Straight socket Angled plug

Cable characteristics: standard

0.5 m

8003617

NEBU-M12G5-K-0.5-M12W5

2m

8003618

NEBU-M12G5-K-2-M12W5

Connecting cable M12-M12, 5-pin Angled socket Angled plug

Cable characteristics: standard

0.5 m

570733

NEBU-M12W5-K-0.5-M12W5

2m

570734

NEBU-M12W5-K-2-M12W5

Connecting cable M12-M12, 5-pin Straight socket Staright plug

Cable characteristics: Suitable for chain link trunking

5m

574321

NEBU-M12G5-E-5-Q8N-M12G5

7.5 m

574322

NEBU-M12G5-E-7.5-Q8N-M12G5

10 m

574323

NEBU-M12G5-E-10-Q8N-M12G5

536593

CPX-ST-1

574600 574601 574602 574603 574604

P.BE-CPX-CTEL-DE P.BE-CPX-CTEL-EN P.BE-CPX-CTEL-ES P.BE-CPX-CTEL-FR P.BE-CPX-CTEL-IT

CPX­CTEL master

Bus connection

Inscription label holder for manifold block

Manual Manual CPX­CTEL master

134

German English Spanish French Italian

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 135

Terminal CPX Technical data – Interface CPX-CTEL-2 The electrical interface CPX-CTEL-2-… enables the connection of modules with IO-Link interface (IO-Link device) to the CPX terminal. The I/O data of the connected devices are transmitted to the connected CPX bus node and thus to the higher-order controller via fieldbus. A maximum of two IO-Link devices can be connected to an electrical interface CPX-CTEL-2-… via the corresponding M12 interfaces.

Application IO-Link interface The communication system IO-Link is used to exchange serial data from decentralised function modules (devices) at the field level. The electrical interface CPX-CTEL-2-… provides two IO-Link interfaces to the outside, on each of which one device can be connected. The connection type corresponds to a star topology, which means that only one device can be connected to each port.

The address space that the module makes available and assigns accordingly in the CPX system can be configured according to various presettings. Selection of the operating mode and the setting for manual configuration takes place via the DIL switches. These DIL switches are not required during continuous operation and are only accessible in the disassembled state.

The process data length of the inputs and outputs is limited to 16 bytes per port for inputs and outputs

The driver strength on the C/Q line is limited to 250 mA

SIO mode is not supported

The power supply for the devices and the inputs is supplied by the power supply for the electronics and sensors of the CPX terminal. The power supply for the outputs and valves is supplied by the power supply for the valves of the CPX terminal. The interlinking block with additional supply ensures a separate the supply voltage for the valves and outputs. This means it is possible to disconnect this supply voltage separately. The valves and outputs of the connected I-Port devices can therefore be disconnected separately without disconnecting the devices.

Restrictions The interfaces (ports) of electrical interface CPX-CTEL-2-… support the connection of IO-Link devices with few limitations. Power supply for devices The electrical interface CPX-CTEL-2-… provides two separate power supplies for the connected devices: For the operation of the device and the inputs connected to it For the outputs and valves that are connected to the device

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

135

Page 136

Terminal CPX Technical data – Interface CPX-CTEL-2 General technical data Type Protocol Max. address capacity I-Port connection Number of IO-Link interfaces Max. cable length Internal cycle time Electrical isolation

CPX-CTEL-2-M12-5POL-LK Outputs Inputs

[bit] [bit]

[m] [ms] Channel – channel Channel – internal bus

LED displays

Diagnostics

Parameterisation

Additional functions Control elements Operating voltage

Nominal value Permissible range Power failure buffering Intrinsic current consumption at nominal operating voltage Max. power supply per channel Max. residual current of outputs per channel Degree of protection to EN 60529 Temperature range Operation Storage/transport Materials Note on materials Grid dimension Dimensions (incl. interlinking block) W x L x H Product weight

[V DC] [V DC] [ms] [mA] [A] [A] [°C] [°C]

[mm] [mm] [g]

IO-Link, master version V 1.0 256 256 2x socket M12, 5-pin, A-coded 2 20 1 per 8 bits of user data No Yes, using an intermediate supply X1 … 2 = status of the IO-Link interface 1 … 2 PS = Electronic supply PL = Load supply -P= Module error Communication error Module short circuit Module-oriented diagnostics Undervoltage Diagnostic behaviour Fail-safe mode per channel Forcing per channel Idle mode per channel Module parameters – DIL switches 24 (polarity-safe) 18 … 30 10 Typically 65 2 x 1.6 2x 1.6 IP65, IP67 –5 … +50 –20 … +70 PA reinforced, PC RoHS-compliant 50 50 x 107 x 55 110

-H- Note Please observe the general limits and guidelines for the system when configuring the electrical modules.

136

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 137

Terminal CPX Technical data – Interface CPX-CTEL-2 Connection and display components 1

2

4

5

3

Combinations of bus nodes/control blocks and interface CPX-CTEL-2 Bus node/control block Part No.

1 Status LEDs for I-Port interfaces 2 CPX-specific status LEDs 3 Holders for inscription labels (IBS 6x10) 4 IO-Link interfaces for up to 2 devices 5 Unoccupied connections

Interface CPX-CTEL-2-M12-5POL-LK n n n n n n n n

CPX-CEC-C1-V3 CPX-CEC-M1-V3 CPX-CEC-S1-V3 CPX-FB33 CPX-M-FB34 CPX-M-FB35 CPX-FB36 CPX-FB39

3473128 3472765 3472425 548755 548751 548749 1912451 2093101

Pin allocation of IO-Link interface Pin allocation

Pin

Signal

Designation

1

24 VSEN

24 V DC supply voltage for electronics and inputs

2

24 VVAL

24 V DC load voltage supply for valves and outputs

3

0 VSEN

0 V DC supply voltage for electronics and sensors

4

C/Q I-PORT

Communication signal C/Q, data cable

5

0 VVALVES

0 V DC load voltage supply for valves and outputs

2018/04 – Subject to change

è Internet: www.festo.com/catalogue/...

137

Page 138

Terminal CPX Technical data – Interface CPX-CTEL-2 Download CAD data è www.festo.com

Dimensions

Type

B1

B2

B3

H1

L1

CPX-CTEL-2-M12-5POL-LK

108.1

118.9

124.9

55.1

50

138

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04

Page 139

Terminal CPX Interface accessories CPX-CTEL-2 Ordering data Designation

Part No.

Type

CPX CTEL­Master, IO-Link Interface for max. 2 I/O modules and valve terminals with IO-Link interface (devices)

2900543

CPX-CTEL-2-M12-5POL-LK

165592

ISK-M12

0.5 m

8003617

NEBU-M12G5-K-0.5-M12W5

2m

8003618

NEBU-M12G5-K-2-M12W5

0.5 m

570733

NEBU-M12W5-K-0.5-M12W5

2m

570734

NEBU-M12W5-K-2-M12W5

5m

574321

NEBU-M12G5-E-5-Q8N-M12G5

7.5 m

574322

NEBU-M12G5-E-7.5-Q8N-M12G5

10 m

574323

NEBU-M12G5-E-10-Q8N-M12G5

536593

CPX-ST-1

8034115 8034116 8034117 8034118 8034119 8034120

P.BE-CPX-CTEL-LK-DE P.BE-CPX-CTEL-LK-EN P.BE-CPX-CTEL-LK-ES P.BE-CPX-CTEL-LK-FR P.BE-CPX-CTEL-LK-IT P.BE-CPX-CTEL-LK-ZH

Bus connection Cover cap

M12

Connecting cable M12-M12, 5-pin Straight socket Angled plug

Cable characteristics: standard

Connecting cable M12-M12, 5-pin Angled socket Angled plug

Cable characteristics: standard

Connecting cable M12-M12, 5-pin Straight socket Staright plug

Cable characteristics: Suitable for chain link trunking

Inscription label holder for connection block

User documentation User documentation for CPX CTEL­Master

2018/04 – Subject to change

German English Spanish French Italian Swedish

è Internet: www.festo.com/catalogue/...

139

Page 140

Control block CPX-CM-HPP Technical data The control block CPX-CM-HPP is a module in the CPX terminal for controlling electric drives. The control component is independent of the bus node used. This means that Festo’s electric drive technology is compatible with all industrial communication interfaces. The control block does not need to be programmed.

Max. 4 individual electric axes can be controlled via CAN bus No programming required Standardised communication with the drives via the Festo Handling and Positioning Profile (FHPP) Quick configuration and diagnos­ tics via the operator unit CPX-MMI Simple, flexible and cost-effective

General technical data Fieldbus interface Protocol Max. address volume for inputs Max. address volume for outputs LED display (product-specific)

[byte] [byte]

Device-specific diagnostics

Parameterisation Configuration support Total number of axes Nominal operating voltage Operating voltage range Power failure buffering Intrinsic current consumption at nominal operating voltage Protection class to EN 60529 (plug connector plugged in) Dimensions W x L x H (incl. interlinking block) Product weight (without interlinking block)

[V DC] [V DC] [ms] [mA]

1x socket M9, 5-pin FHPP 32 32 Error: Error PL: Power supply Diagnostic memory Channel and module-oriented diagnostics Undervoltage/short circuit of modules Forcing of channels System parameters Operator unit CPX-MMI 4 24 18 … 30 10 Typically 80 IP65, IP67

[mm]

50 x 107 x 55

[g]

140

Materials Housing

PA, reinforced PC RoHS-compliant

Note on materials Technical data – Interfaces Interface Control interface Baud rate

[Mbps]

CAN-Bus 1

Operating and environmental conditions Ambient temperature [°C] Storage temperature [°C] CE mark (see declaration of conformity)

140

–5 … +50 –20 … +70 To EU Low Voltage Directive

è Internet: www.festo.com/catalogue/...

Subject to change – 2018/04