The text of a spec sheet · part 14 of 25
Modular electrical terminal CPX, pages 131 to 140
Pages 131 to 140 of 246
The original document is the PDF (8.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Festo CPX-EPL-EV
Page 131
Terminal CPX Technical data – Interface CPX-CTEL General technical data Type Protocol Max. address capacity I-Port connection Number of I-Port interfaces Max. cable length Internal cycle time Electrical isolation
CPX-CTEL-4-M12-5POL Outputs Inputs
[bit] [bit]
[m] [ms] Channel – channel Channel – internal bus
LED displays
Diagnostics
Parameterisation
Additional functions Operating elements Operating voltage
Nominal value Permissible range Power failure buffering Intrinsic current consumption at nominal operating voltage Max. power supply per channel Max. residual output current per channel Protection class to EN 60529 Temperature range Operating Storage/transport Materials Note on materials Grid dimension Dimensions (incl. interlinking block) W x L x H Product weight
[V DC] [V DC] [ms] [mA] [A] [A] [°C] [°C]
[mm] [mm] [g]
I-Port 256 256 4x M12 socket, 5-pin, A-coded 4 20 1 per 8 bits of user data No Yes, using an intermediate supply X1 … 4 = Status of the I-Port interface 1 … 4 PS = Electronics supply PL = Load supply -P= Module fault Communication error Module short circuit Module-oriented diagnostics Undervoltage Diagnostic behaviour Failsafe per channel Forces per channel Idle mode per channel Module parameters Tool change mode Tool change mode DIL switch 24 (reverse polarity protected) 18 … 30 10 Typically 65 4x 1.6 4x 1.6 IP65, IP67 –5 … +50 –20 … +70 PA reinforced, PC RoHS-compliant 50 50 x 107 x 55 110
-H- Note Please observe the general limits and guidelines for the system when configuring the electrical modules.
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
131
Page 132
Terminal CPX Technical data – Interface CPX-CTEL Connection and display components 1
2
1 Status LEDs for I-Port interfaces 2 CPX-specific status LEDs 3 Holders for inscription labels (IBS 6x10) 4 I-Port interfaces for up to 4 devices
4
3
Combinations of bus nodes/control blocks and interface CPX-CTEL Bus node/control block Part No.
Interface CPX-CTEL-4-M12-5POL n n n n n n n n n n n n n n n n n n
CPX-CEC-C1 CPX-CEC-C1-V3 CPX-CEC-M1-V3 CPX-CEC CPX-CEC-S1-V3 CPX-FB11 CPX-FB13 CPX-FB14 CPX-FB23-24 CPX-FB33 CPX-M-FB34 CPX-M-FB35 CPX-FB36 CPX-FB37 CPX-FB38 CPX-FB39 CPX-FB40 CPX-M-FB41
567347 3473128 3472765 567346 3472425 526172 195740 526174 526176 548755 548751 548749 1912451 2735960 552046 2093101 2474896 3228960
Pin allocation – I-Port interface Pin allocation
Pin
Signal
Designation
1
24 VSEN
24 V DC supply voltage for electronics and inputs
2
24 VVAL
24 V DC load voltage supply for valves and outputs
3
0 VSEN
0 V DC supply voltage for electronics and sensors
4
C/Q I-Port
Communication signal C/Q, data cable
5
0 VVALVES
0 V DC load voltage supply for valves and outputs
132
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 133
Terminal CPX Technical data – Interface CPX-CTEL Download CAD data è www.festo.com
Dimensions
Type
B1
B2
B3
H1
L1
CPX-CTEL-4-M12-5POL
108.1
118.9
124.9
55.1
50
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
133
Page 134
-V- New Terminal CPX Accessories – Interface CPX-CTEL Ordering data Designation
Part No.
Type
Interface for max. 4 I/O modules and valve terminals with I-Port interface (devices)
1577012
CPX-CTEL-4-M12-5POL
Cover cap
M12
165592
ISK-M12
Connecting cable M12-M12, 5-pin Straight socket Angled plug
Cable characteristics: standard
0.5 m
8003617
NEBU-M12G5-K-0.5-M12W5
2m
8003618
NEBU-M12G5-K-2-M12W5
Connecting cable M12-M12, 5-pin Angled socket Angled plug
Cable characteristics: standard
0.5 m
570733
NEBU-M12W5-K-0.5-M12W5
2m
570734
NEBU-M12W5-K-2-M12W5
Connecting cable M12-M12, 5-pin Straight socket Staright plug
Cable characteristics: Suitable for chain link trunking
5m
574321
NEBU-M12G5-E-5-Q8N-M12G5
7.5 m
574322
NEBU-M12G5-E-7.5-Q8N-M12G5
10 m
574323
NEBU-M12G5-E-10-Q8N-M12G5
536593
CPX-ST-1
574600 574601 574602 574603 574604
P.BE-CPX-CTEL-DE P.BE-CPX-CTEL-EN P.BE-CPX-CTEL-ES P.BE-CPX-CTEL-FR P.BE-CPX-CTEL-IT
CPXCTEL master
Bus connection
Inscription label holder for manifold block
Manual Manual CPXCTEL master
134
German English Spanish French Italian
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 135
Terminal CPX Technical data – Interface CPX-CTEL-2 The electrical interface CPX-CTEL-2-… enables the connection of modules with IO-Link interface (IO-Link device) to the CPX terminal. The I/O data of the connected devices are transmitted to the connected CPX bus node and thus to the higher-order controller via fieldbus. A maximum of two IO-Link devices can be connected to an electrical interface CPX-CTEL-2-… via the corresponding M12 interfaces.
Application IO-Link interface The communication system IO-Link is used to exchange serial data from decentralised function modules (devices) at the field level. The electrical interface CPX-CTEL-2-… provides two IO-Link interfaces to the outside, on each of which one device can be connected. The connection type corresponds to a star topology, which means that only one device can be connected to each port.
The address space that the module makes available and assigns accordingly in the CPX system can be configured according to various presettings. Selection of the operating mode and the setting for manual configuration takes place via the DIL switches. These DIL switches are not required during continuous operation and are only accessible in the disassembled state.
The process data length of the inputs and outputs is limited to 16 bytes per port for inputs and outputs
The driver strength on the C/Q line is limited to 250 mA
SIO mode is not supported
The power supply for the devices and the inputs is supplied by the power supply for the electronics and sensors of the CPX terminal. The power supply for the outputs and valves is supplied by the power supply for the valves of the CPX terminal. The interlinking block with additional supply ensures a separate the supply voltage for the valves and outputs. This means it is possible to disconnect this supply voltage separately. The valves and outputs of the connected I-Port devices can therefore be disconnected separately without disconnecting the devices.
Restrictions The interfaces (ports) of electrical interface CPX-CTEL-2-… support the connection of IO-Link devices with few limitations. Power supply for devices The electrical interface CPX-CTEL-2-… provides two separate power supplies for the connected devices: For the operation of the device and the inputs connected to it For the outputs and valves that are connected to the device
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
135
Page 136
Terminal CPX Technical data – Interface CPX-CTEL-2 General technical data Type Protocol Max. address capacity I-Port connection Number of IO-Link interfaces Max. cable length Internal cycle time Electrical isolation
CPX-CTEL-2-M12-5POL-LK Outputs Inputs
[bit] [bit]
[m] [ms] Channel – channel Channel – internal bus
LED displays
Diagnostics
Parameterisation
Additional functions Control elements Operating voltage
Nominal value Permissible range Power failure buffering Intrinsic current consumption at nominal operating voltage Max. power supply per channel Max. residual current of outputs per channel Degree of protection to EN 60529 Temperature range Operation Storage/transport Materials Note on materials Grid dimension Dimensions (incl. interlinking block) W x L x H Product weight
[V DC] [V DC] [ms] [mA] [A] [A] [°C] [°C]
[mm] [mm] [g]
IO-Link, master version V 1.0 256 256 2x socket M12, 5-pin, A-coded 2 20 1 per 8 bits of user data No Yes, using an intermediate supply X1 … 2 = status of the IO-Link interface 1 … 2 PS = Electronic supply PL = Load supply -P= Module error Communication error Module short circuit Module-oriented diagnostics Undervoltage Diagnostic behaviour Fail-safe mode per channel Forcing per channel Idle mode per channel Module parameters – DIL switches 24 (polarity-safe) 18 … 30 10 Typically 65 2 x 1.6 2x 1.6 IP65, IP67 –5 … +50 –20 … +70 PA reinforced, PC RoHS-compliant 50 50 x 107 x 55 110
-H- Note Please observe the general limits and guidelines for the system when configuring the electrical modules.
136
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 137
Terminal CPX Technical data – Interface CPX-CTEL-2 Connection and display components 1
2
4
5
3
Combinations of bus nodes/control blocks and interface CPX-CTEL-2 Bus node/control block Part No.
1 Status LEDs for I-Port interfaces 2 CPX-specific status LEDs 3 Holders for inscription labels (IBS 6x10) 4 IO-Link interfaces for up to 2 devices 5 Unoccupied connections
Interface CPX-CTEL-2-M12-5POL-LK n n n n n n n n
CPX-CEC-C1-V3 CPX-CEC-M1-V3 CPX-CEC-S1-V3 CPX-FB33 CPX-M-FB34 CPX-M-FB35 CPX-FB36 CPX-FB39
3473128 3472765 3472425 548755 548751 548749 1912451 2093101
Pin allocation of IO-Link interface Pin allocation
Pin
Signal
Designation
1
24 VSEN
24 V DC supply voltage for electronics and inputs
2
24 VVAL
24 V DC load voltage supply for valves and outputs
3
0 VSEN
0 V DC supply voltage for electronics and sensors
4
C/Q I-PORT
Communication signal C/Q, data cable
5
0 VVALVES
0 V DC load voltage supply for valves and outputs
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
137
Page 138
Terminal CPX Technical data – Interface CPX-CTEL-2 Download CAD data è www.festo.com
Dimensions
Type
B1
B2
B3
H1
L1
CPX-CTEL-2-M12-5POL-LK
108.1
118.9
124.9
55.1
50
138
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 139
Terminal CPX Interface accessories CPX-CTEL-2 Ordering data Designation
Part No.
Type
CPX CTELMaster, IO-Link Interface for max. 2 I/O modules and valve terminals with IO-Link interface (devices)
2900543
CPX-CTEL-2-M12-5POL-LK
165592
ISK-M12
0.5 m
8003617
NEBU-M12G5-K-0.5-M12W5
2m
8003618
NEBU-M12G5-K-2-M12W5
0.5 m
570733
NEBU-M12W5-K-0.5-M12W5
2m
570734
NEBU-M12W5-K-2-M12W5
5m
574321
NEBU-M12G5-E-5-Q8N-M12G5
7.5 m
574322
NEBU-M12G5-E-7.5-Q8N-M12G5
10 m
574323
NEBU-M12G5-E-10-Q8N-M12G5
536593
CPX-ST-1
8034115 8034116 8034117 8034118 8034119 8034120
P.BE-CPX-CTEL-LK-DE P.BE-CPX-CTEL-LK-EN P.BE-CPX-CTEL-LK-ES P.BE-CPX-CTEL-LK-FR P.BE-CPX-CTEL-LK-IT P.BE-CPX-CTEL-LK-ZH
Bus connection Cover cap
M12
Connecting cable M12-M12, 5-pin Straight socket Angled plug
Cable characteristics: standard
Connecting cable M12-M12, 5-pin Angled socket Angled plug
Cable characteristics: standard
Connecting cable M12-M12, 5-pin Straight socket Staright plug
Cable characteristics: Suitable for chain link trunking
Inscription label holder for connection block
User documentation User documentation for CPX CTELMaster
2018/04 – Subject to change
German English Spanish French Italian Swedish
è Internet: www.festo.com/catalogue/...
139
Page 140
Control block CPX-CM-HPP Technical data The control block CPX-CM-HPP is a module in the CPX terminal for controlling electric drives. The control component is independent of the bus node used. This means that Festo’s electric drive technology is compatible with all industrial communication interfaces. The control block does not need to be programmed.
Max. 4 individual electric axes can be controlled via CAN bus No programming required Standardised communication with the drives via the Festo Handling and Positioning Profile (FHPP) Quick configuration and diagnos tics via the operator unit CPX-MMI Simple, flexible and cost-effective
General technical data Fieldbus interface Protocol Max. address volume for inputs Max. address volume for outputs LED display (product-specific)
[byte] [byte]
Device-specific diagnostics
Parameterisation Configuration support Total number of axes Nominal operating voltage Operating voltage range Power failure buffering Intrinsic current consumption at nominal operating voltage Protection class to EN 60529 (plug connector plugged in) Dimensions W x L x H (incl. interlinking block) Product weight (without interlinking block)
[V DC] [V DC] [ms] [mA]
1x socket M9, 5-pin FHPP 32 32 Error: Error PL: Power supply Diagnostic memory Channel and module-oriented diagnostics Undervoltage/short circuit of modules Forcing of channels System parameters Operator unit CPX-MMI 4 24 18 … 30 10 Typically 80 IP65, IP67
[mm]
50 x 107 x 55
[g]
140
Materials Housing
PA, reinforced PC RoHS-compliant
Note on materials Technical data – Interfaces Interface Control interface Baud rate
[Mbps]
CAN-Bus 1
Operating and environmental conditions Ambient temperature [°C] Storage temperature [°C] CE mark (see declaration of conformity)
140
–5 … +50 –20 … +70 To EU Low Voltage Directive
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04