Page 41
Terminal CPX Key features – Diagnostics Diagnostics System performance 3
1
4
2
1 Diagnostics via bus interface 2 Undervoltage monitoring 3 Diagnostic overview LED – Fieldbus status – CPX status 4 Status and diagnostic LED for module and I/O channels 5 Module and channel-specific diagnostics 6 Valve-specific diagnostics for module and solenoid coils 7 MPA pressure sensor – integrated solution on the fieldbus – Pre-assembled for ducts 1, 3, 5 and external pressures
The CPX terminal supports on-the-spot diagnostics via a row of LEDs. This is separate from the connection area and therefore provides good visual access to status and diagnostic information.
Module and channel-specific diagnosis is supported, for example Undervoltage detection for outputs and valves Short circuit detection for sensors, outputs and valves Open-load detection for a missing solenoid coil Storage of the last 40 causes of errors with error start and error end
The diagnostic messages can be read out via the bus interface in the higherorder controller and visualised for the central recording and evaluation of error causes. This is done using the individual fieldbus-specific channels. The CPX-CEC also offer the option of access via the integrated Ethernet interface (remote maintenance via PC/web applications).
1 Fieldbus-specific LEDs On each bus node, a maximum of 4 fieldbus-specific LEDs display the fieldbus communication status of the CPX terminal with the higher-order controller.
2 CPX-specific LEDs A further 4 CPX-specific LEDs provide non-fieldbus-specific information about the status of the CPX terminal, for example – Power system – Power load – System fault – Modification parameters
5
Detailed diagnostic functions are needed in order to quickly locate the causes of errors in the electrical installation and therefore reduce downtimes in production plants. A basic distinction is made between on-the-spot diagnostics using LEDs or an operator unit and diagnostics using a bus interface.
6
Overview of LEDs on the bus node 1
2
Input/output module status and diagnostic LEDs 1
2
3
2018/04 – Subject to change
1 Status LEDs for the inputs and outputs Each input and output channel is assigned a status LED.
2 Channel-oriented diagnostic LEDs Depending on the module design, another diagnostic LED is available for each I/O channel
è Internet: www.festo.com/catalogue/...
3 Group diagnostic LEDs An LED displays the group diagnostics for each module
41
Page 42
Terminal CPX Key features – Parameterisation Diagnostics Display on the operator unit 1 LCD graphical display for on-site plain-text diagnostics – Fault location and type – Without programming
1
Display on a PC
1 3
1 CPX terminal with valve terminal 2 Adapter diagnostic interface to USB 3 Laptop/portable device with USB interface and installed FMT software
– Fault location and type – Without programming – Storing the configuration – Preparing screenshots to 0.1 ms on a "fast" input module for faster processes, or to set the re sponse of a valve following a fieldbus interrupt. Depending on the modules used, parameterisation can be performed via the following interfaces: Ethernet Fieldbus Control block direct interface (programming interface) Operator unit CPX-MMI
2
Parameterisation Changes to the application are often required during commissioning. The parameterisable characteristics of the CPX modules mean that functions can be very easily changed by means of configuration software. This reduces the number of modules needed and, consequently, the amount of storage space required. It is therefore possible, for example, to reduce the switch-on debounce time for an input module – normally 3 ms –
1 2
42
è Internet: www.festo.com/catalogue/...
1 Input debounce time 3 ms 2 Input debounce time 0.1 ms
Subject to change – 2018/04
Page 43
Terminal CPX Key features – Addressing Addressing The various CPX modules occupy a different number of I/O addresses within the CPX system. The maximum address space for bus nodes depends on the performance of the fieldbus systems.
Maximum system configuration: 1 bus node or control block 9 I/O modules 1 pneumatic interface (e.g. pneu matic interface MPA-S with up to 16 MPA manifold blocks)
Overview – Address space for CPX bus node and control block Protocol Max. total Inputs
The maximum system configuration can be limited in individual cases by exceeding the address space.
-H- Note Please refer to the detailed descrip tion of the configuration/addressing rules in the technical data for CPX bus nodes.
Outputs
Max. digital Inputs
Outputs
Max. analogue Inputs Outputs
CoDeSys level 2 512 bits TCP/IP Easy IP Modbus TCP INTERBUS 96 bits DeviceNet 512 bits PROFIBUS 512 bits CANOpen 256 bits INTERBUS (LWL) 96 bits CC-Link 512 bits PROFINET RT 512 bits PROFINET RT 512 bits PROFINET RT 512 bits EtherNet/IP 512 bits EtherCAT 512 bit EtherCAT 512 bits Sercos III 512 bit POWERLINK 512 bit PROFINET RT 512 bit
512 bits
512 DI
512 DO
32 AI
18 AO
96 bits 512 bits 512 bits 256 bits 96 bits 512 bits 512 bits 512 bits 512 bits 512 bits 512 bit 512 bits 512 bit 512 bit 512 bit
96 DI 512 DI 512 DI 64 DI (+ 64 DI) 96 DI 512 DI 512 DI 512 DI 512 DI 512 DI 512 DE 512 DI 512 DE 512 DE 512 DE
96 DO 512 DO 512 DO 64 DO (+ 64 DO) 96 DO 512 DO 512 DO 512 DO 512 DO 512 DO 512 DA 512 DO 512 DA 512 DA 512 DA
6 AI 32 AI 32 AI 8 AI (+ 8 AI) 6 AI 32 AI 32 AI 32 AI 32 AI 32 AI 32 AE 32 AI 32 AE 32 AE 32 AE
6 AO 18 AO 18 AO 8 AO (+ 8 AO) 6 AO 18 AO 18 AO 18 AO 18 AO 18 AO 18 AA 18 AO 18 AA 18 AA 18 AA
Digital inputs
Digital outputs
Notes
3x CPX-8DE 1x CPX-8DE-8DA 2x CPX-2AE 1x CPX-2AA 3x VMPA1 Allocated address space
24 8 64 – – 96
– 8 – 32 24 96
The address space is occupied by 7 CPX I/O modules plus pneumatic interface No additional modules can be configured
DI
DO = Digital outputs (1 bit)
AO = Analogue outputs (16 bits)
AI
CPX-CEC
CPX-FB6 CPX-FB11 CPX-FB13 CPX-FB14 CPX-M-FB21 CPX-FB23-24 CPX-FB33 CPX-M-FB34 CPX-M-FB35 CPX-FB36 CPX-FB37 CPX-FB38 CPX-FB39 CPX-FB40 CPX-M-FB41
-H- Note The bandwidth of the bus nodes can be restricted by the choice of module and the maximum number of modules.
Example CPX-FB6 (INTERBUS)
= Digital inputs (1 bit)
2018/04 – Subject to change
= Analogue inputs (16 bits)
è Internet: www.festo.com/catalogue/...
43
Page 44
-V- New CPX-4AE-4AA-H Terminal CPX Key features – Addressing Overview – Allocated addresses for CPX modules Inputs [bit] CPX-CP-4-FB CPX-CTEL-4-M12-5POL CPX-CTEL-2-M12-5POL-LK CPX-CM-HPP CPX-CMAX-C1-1 CPX-CMPX-C-1-H1 CPX-CMIX-M1-1 CPX-4DE CPX-8DE CPX-8DE-D CPX-8NDE CPX-F8DE-P CPX-16DE CPX-M-16DE-D CPX-L-16DE-16-KL-3POL CPX-4DA CPX-8DA CPX-8DA-H CPX-8DE-8DA CPX-L-8DE-8DA-16-KL-3POL CPX-2ZE2DA CPX-4AE-4AA-H CPX-2AE-U-I CPX-4AE-U-I CPX-4AE-I CPX-4AE-P-B2 CPX-4AE-P-D10 CPX-4AE-T CPX-4AE-TC CPX-2AA-U-I CPX-FVDA-P2 VMPA1-FB-EMS-8 VMPA1-FB-EMG-8 VMPA2-FB-EMS-4 VMPA2-FB-EMG-4 VMPA1-FB-EMS-D2-8 VMPA1-FB-EMG-D2-8 VMPA2-FB-EMS-D2-4 VMPA2-FB-EMG-D2-4 VMPA-FB-PS-1 VMPA-FB-PS-3/5 VMPA-FB-PS-P1 VMPA-FB-EMG-P1 VMPAL-EPL-CPX VABA-S6-1-X1 VABA-S6-1-X2 VABA-S6-1-X2-D 1)
44
16, 32, 48, 64, 80, 96, 1281) 0, 64, 128, 192, 2561) 64, 128, 192, 2561) 256 64 48 48 4 8 8 8 48 16 16 16 – – – 8 8 96 0, 16, 32, 48, 64, 128, 144, 160, 176, 1921) 2 x 16 4 x 16 4 x 16 4 x 16 4 x 16 4 x 16 4 x 16 – 48 – – – – – – – – 16 16 16 16 – – – 8, 16, 24, 321)
-V-
Outputs [bit] 16, 32, 48, 64, 80, 96, 1281) 0, 64, 128, 192, 2561) 64, 128, 192, 2561) 256 64 48 48 – – – – 56 – – – 4 8 8 8 8 96 0, 16, 32, 48, 641) – – – – – – – 2 x 16 48 8 8 4 4 8 8 4 4 – – – 16 4, 8, 16, 24, 321) 8, 16, 24, 321) 8, 16, 24, 321) 8, 16, 24, 321)
Dependent on the DIL switch setting on the module
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 45
Terminal CPX Technical data
-K- Module width 50 mm
-H- Note The data given here apply to the CPX system. If components that conform to lower values are used in the sys tem, the specification for the entire system is reduced to the values of those components used.
Example Protection class IP65/IP67 applies only to the fully assembled system with fitted plugs or covers (which must also conform to IP65/IP67). If compo nents with a lower protection class are used, the protection level of the entire
General technical data Module No. Max. no. of modules1)
Max. address capacity Internal cycle time Configuration support LED displays
197330 Control block Bus node I/O modules/CP interface/CTEL interface/ electrical interface CPX-CTEL-2/multi-axis interface Pneumatic interface Inputs [byte] Outputs [byte] [ms] Bus node/control block
I/O modules Pneumatic interface Diagnostics
1)
system is reduced to the protection class of the component with the lowest protection level, for example CageClamp connection block with IP20 protection or MPA pneumatics with IP65 protection.
1 1 9
1 64 64 1 Fieldbus-specific Up to 4 LEDs, bus-specific 4 LEDs, CPX-specific PS = Power system PL = Power load SF = System fault M = Modify parameter/forcing active Min. one group diagnostic LED Channel-oriented status and diagnostic LED, depending on module One group diagnostic LED Valve status LED on valve Channel and module-oriented diagnostics for inputs/outputs and valves Detection of module undervoltage for the different voltage potential values Storage of the last 40 errors with timestamp (asynchronous access)
A maximum of 11 modules in total can be combined (e.g. 1 control block + 9 I/O modules + 1 pneumatic interface, or 1 control block + 1 bus node + 8 I/O modules + 1 pneumatic interface)
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
45
Page 46
Terminal CPX Technical data General technical data Module No.
197330
Parameterisation
Commissioning support Protection class to EN 60529 Nominal operating voltage Operating voltage range Current supply
Interlinking block with system supply for electronics plus sensors actuators plus valves Additional power supply for actuators Additional power supply for valves
Current consumption Power failure bridging (bus electronics only) Power supply connection
Fuse concept Tests
[V DC] [V DC]
Module-specific and entire system, for example: Diagnostic behaviour Condition monitoring Profile of inputs Fail-safe response of outputs and valves Forcing of inputs and outputs IP65, IP67 24 18 … 30
[A] [A]
16 (8/10 with 7/8” supply, 5-pin/4-pin) 16 (8/10 with 7/8” supply, 5-pin/4-pin)
[A] [A]
16 (8/10 with 7/8” supply, 5-pin/4-pin) 16 (10 with 7/8” supply, 4-pin)
[ms]
Vibration test to DIN IEC 68 Shock test to DIN IEC 68
PWIS classification Interference immunity Interference emission Isolation test for galvanically isolated circuits to IEC 1131 Part 2 Galvanic isolation of electrical voltages Protection against direct and indirect contact Materials Grid dimension
[V DC] [V DC]
[mm]
Operating and environmental conditions Module No. Ambient temperature Storage temperature
46
Depending on system configuration 10 M18, 4-pin 7/8”, 5-pin 7/8”, 4-pin AIDA push-pull, 5-pin Per module with electronic fuses With wall mounting: Severity level 2 With H-rail mounting: Severity level 1 With wall mounting: Severity level 2 With H-rail mounting: Severity level 1 PWIS-free (free of paint-wetting impairment substances) EN 61000-6-2 (industry) EN 61000-6-4 (industry) 500 80 PELV (Protective Extra-Low Voltage) End plates: Die-cast aluminium 50
197330 [°C] [°C]
è Internet: www.festo.com/catalogue/...
–5 … +50 –20 … +70
Subject to change – 2018/04
Page 47
Terminal CPX Technical data Certifications – Maximum permissible values Module No. ATEX category gas Ex-ignition protection type gas ATEX ambient temperature CE mark (see declaration of conformity)
197330
[°C]
Protection class to EN 60529 Certification Explosion protection certification outside the EU 1)
II 3G Ex nA IIC T4 X Gc –5 ≤ Ta ≤ +50 To EU Explosion Protection Directive (ATEX) To EU EMC Directive1) IP65, IP67 c UL us - Recognized (OL) C-Tick EPL Gc (Ru)
For information about the applicability of the component see the manufacturer’s EC declaration of conformity at: www.festo.com/sp è Certificates. If the component is subject to restrictions on usage in residential, office or commercial environments or small businesses, further measures to reduce the emitted interference may be necessary.
-H- Note The values indicated represent the maximum performance limits that can be achieved with the fully assembled product. Depending on the individual components used, the value actually achieved for the overall product may be lower.
You can select e.g. the individual components required to achieve the ATEX category by choosing the corresponding features in the online product configurator: è Internet:cpx
Weight [g] Control block Bus node
I/O module
Counter module CP interface CTEL interface Electrical interface Axis interface Axis controller End-position controller Measuring module
2018/04 – Subject to change
CEC CEC…V3 FB6 FB11 FB13 FB14 FB21 FB23-24 FB33 FB34 FB35 FB36 FB37 FB38 FB39 FB40 FB41 CPX CPX-L HART 2ZE2DA CP CTEL CTEL-2 CM-HPP CMAX CMPX CMIX
155.0 135.0 125.0 120.0 115.0 115.0 1255.0 115.0 280.0 280.0 280.0 125.0 125.0 125.0 125.0 125.0 280.0 38.0 170.0 77.4 130.0 140.0 110.0 110.0 140.0 140.0 140.0 140.0
Connection block
Plastic Metal Interlinking block, Without power supply plastic With system supply Interlinking block, Without power supply metal With system supply, 7/8" 4-pin With system supply, 7/8" 5-pin With system supply, Push-pull Tie rod 1-fold 2-fold 3-fold 4-fold 5-fold 6-fold 7-fold 8-fold 9-fold 10-fold End plate for plastic Left-hand version Left-hand, with system supply Right-hand End plate for metal Left-hand version Right-hand End plate with extension Left-hand Right-hand Pneumatic interface MPA-S VTSA/VTSA-F
è Internet: www.festo.com/catalogue/...
70.0 175.0 100.0 125.0 169.0 228.0 187.0 279.0 19.0 ±2.5 32.5 ±2.5 46.0 ±2.5 59.5 ±2.5 73.0 ±2.5 86.5 ±2.5 100.0 ±2.5 113.5 ±2.5 127.0 ±2.5 140.5 ±2.5 77.0 145.0 70.0 113.0 113.0 190.0 175.0 238.4 485.0
47
Page 48
Terminal CPX Accessories Ordering data – Accessories Designation
Part No.
Type
Attachment for wall mounting (for long valve terminals, 10 pieces), design for plastic manifold sub-bases
529040
CPX-BG-RW-10x
Attachment for wall mounting, design for metal manifold sub-bases
2 mounting brackets and 4 screws
550217
CPX-M-BG-RW-2X
1 mounting bracket and 2 screws
2721419
CPX-M-BG-VT-2X
Mounting for H-rail
CPX without pneumatic components CPX-VTSA CPX-VTSA-F CPX-MPA
526032
CPX-CPA-BG-NRH
Tie rod CPX
Extension 1-fold 1-fold 2-fold 3-fold 4-fold 5-fold 6-fold 7-fold 8-fold 9-fold 10-fold
525418 195718 195720 195722 195724 195726 195728 195730 195732 195734 195736
CPX-ZA-1-E CPX-ZA-1 CPX-ZA-2 CPX-ZA-3 CPX-ZA-4 CPX-ZA-5 CPX-ZA-6 CPX-ZA-7 CPX-ZA-8 CPX-ZA-9 CPX-ZA-10
– M18 M18, for ATEX environment 7/8" – 5-pin 7/8" – 5-pin, for ATEX environment 7/8" – 4-pin M18 M18, for ATEX environment 7/8" – 5-pin 7/8" – 5-pin, for ATEX environment 7/8" – 4-pin M18 M18, for ATEX environment 7/8" – 4-pin
195742 195746 8022170 541244 8022172 541248 195744 8022166 541246 8022173 541250 533577 8022171 541252
CPX-GE-EV CPX-GE-EV-S CPX-GE-EV-S-VL CPX-GE-EV-S-7/8-5POL CPX-GE-EV-S-7/8-5POL-VL CPX-GE-EV-S-7/8-4POL CPX-GE-EV-Z CPX-GE-EV-Z-VL CPX-GE-EV-Z-7/8-5POL CPX-GE-EV-Z-7/8-5POL-VL CPX-GE-EV-Z-7/8-4POL CPX-GE-EV-V CPX-GE-EV-V-VL CPX-GE-EV-V-7/8-4POL
– 7/8" – 5-pin 7/8" – 5-pin, for ATEX environment 7/8" – 4-pin Push-pull – 5-pin 7/8" – 5-pin 7/8" – 5-pin, for ATEX environment Push-pull – 5-pin
550206 550208 8022165 568956 563057 550210 8022158 563058
CPX-M-GE-EV CPX-M-GE-EV-S-7/8-5POL CPX-M-GE-EV-S-7/8-5POL-VL CPX-M-GE-EV-S-7/8-CIP-4P CPX-M-GE-EV-S-PP-5POL CPX-M-GE-EV-Z-7/8-5POL CPX-M-GE-EV-Z-7/8-5POL-VL CPX-M-GE-EV-Z-PP-5POL
Mounting
Tie rod
Plastic interlinking block Without power supply With system supply
With additional power supply for outputs
With additional power supply for valves
Metal interlinking block Without power supply With system supply
With additional power supply for outputs
48
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 49
Terminal CPX Accessories Ordering data – Accessories Designation
Part No.
Type
Bus node/metal connection block Bus node/plastic connection block Bus node/metal connection block
550218
CPX-DPT-30X32-S-4X
550219
CPX-M-M3x22-4x
550216
CPX-M-M3x22-S-4x
–
195716
CPX-EPL-EV
With system supply
576315
CPX-EPL-EV-S
With extension
576314
CPX-EPL-EV-X
–
195714
CPX-EPR-EV
With extension
576313
CPX-EPR-EV-X
5 pieces
538892
CPX-EPFE-EV
–
550212
CPX-M-EPL-EV
With extension
576317
CPX-M-EPL-EV-X
–
550214
CPX-M-EPR-EV
With extension
576316
CPX-M-EPR-EV-X
Plug socket for mains connection M18x1, straight, 4-pin Plug socket for mains connection M18x1, angled, 4-pin Plug socket for mains connection 7/8", straight, 5-pin
For 1.5 mm2 For 2.5 mm2 For 1.5 mm2 For 2.5 mm2 0.25 … 2.0 mm2
18493 18526 18527 533119 543107
NTSD-GD-9 NTSD-GD-13,5 NTSD-WD-9 NTSD-WD-11 NECU-G78G5-C2
Plug socket for mains connection 7/8", straight, 4-pin
0.25 … 2.0 mm2
543108
NECU-G78G4-C2
Plug socket for mains connection 7/8", angled, 5-pin – open cable end, 5-wire
2m
573855
NEBU-G78W5-K-2-N-LE5
Power supply socket push-pull, connection pattern PP, fulfils requirements according to AIDA
5-pin
5195383
NECU-M-PPG5PP-C1-PN
Straight plug, spring-loaded terminal, for end plate left-hand with system supply
7-pin
576319
NECU-L3G7-C1
Mounting accessories Screws for mounting the bus node/connection block on a plastic interlinking block Screws for mounting the bus node/connection block on a metal interlinking block
End plates for plastic version End plate, left-hand
End plate, right-hand
Earthing element for right-hand/left-hand end plate
End plates for metal version End plate, left-hand
End plate, right-hand
Power supply
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
49
Page 50
Terminal CPX Accessories Ordering data – Accessories Designation
Part No.
Type
18576
IBS-6x10
572256
CAFC-X1-S
572257
CAFC-X1-BE
Inscription labels Inscription labels 6x10, 64 pieces, in frames
Hood Mounting rail for securing the cover
1,000 mm
Mounting kit for CPX cover
Hood section for CPX terminal including mounting attachments for connecting several hood sections in series
200 mm
572258
CAFC-X1-GAL-200
300 mm
572259
CAFC-X1-GAL-300
CPX System Manual
German English Spanish French Italian German English French Italian Spanish
526445 526446 526447 526448 526449 534824 534825 534827 534828 534826
P.BE-CPX-SYS-DE P.BE-CPX-SYS-EN P.BE-CPX-SYS-ES P.BE-CPX-SYS-FR P.BE-CPX-SYS-IT P.BE-CPX-MMI-1-DE P.BE-CPX-MMI-1-EN P.BE-CPX-MMI-1-FR P.BE-CPX-MMI-1-IT P.BE-CPX-MMI-1-ES
Manual
Operator unit CPX-MMI-1
50
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04