The text of a spec sheet · part 7 of 25
Modular electrical terminal CPX, pages 61 to 70
Pages 61 to 70 of 246
The original document is the PDF (8.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Festo CPX-EPL-EV
Page 61
Terminal CPX Technical data – Control block CPX-CEC General technical data Protocol
Processing time Programming software Programming language
Programming
Operating language Support for file handling
Device-specific diagnostics
LED displays
Bus-specific Product-specific
IP address setting
Function blocks Dimensions (incl. interlinking block) W x L x H
[mm]
CODESYS Level 2 EasyIP Modbus TCP TCP/IP Approx. 200 μs/1 k instruction CODESYS provided by Festo To IEC 61131-3 Sequential function chart (SFC) Instruction list (IL) Function chart (FCH), additional continuous function chart (CFC) Ladder diagram (LD) Structured text (ST) German, English Yes Diagnostic memory Channel and module-oriented diagnostics Undervoltage/short circuit of modules TP: Link/traffic RUN: PLC status STOP: PLC status ERR: PLC runtime error PS: Electronics supply, sensor supply PL: Load supply SF: System fault M: Modify/forcing active DHCP Via CODESYS Via MMI CPX diagnostic status, copy CPX diagnostic trace, read CPX module diagnostics, etc. 50 x 107 x 55
Materials Housing
Reinforced PA PC RoHS-compliant
Note on materials Operating and environmental conditions Ambient temperature Storage temperature Relative air humidity Corrosion resistance class CRC1) 1)
[°C] [°C] [%]
–5 … +50 –20 … +70 95, non-condensing 2
Corrosion resistance class CRC 2 to Festo standard FN 940070 Moderate corrosion stress. Indoor applications in which condensation may occur. External visible parts with primarily decorative requirements for the surface and which are in direct contact with the ambient atmo sphere typical for industrial applications.
Electrical data Nominal operating voltage Load voltage
Nominal operating voltage With pneumatics type VTSA With pneumatics type MPA Without pneumatics
Power failure buffering Intrinsic current consumption at nominal operating voltage Degree of protection to EN 60529
2018/04 – Subject to change
[V DC] [V DC] [V DC] [V DC] [V DC] [ms] [mA]
24 24 21.6 … 26.4 18 … 30 18 … 30 10 Typically 85 IP65, IP67
è Internet: www.festo.com/catalogue/...
61
Page 62
Terminal CPX Technical data – Control block CPX-CEC Technical data Type
CPX-CEC-C1
Additional functions
Motion functions for electric drives
CPU data
Flash RAM Processor
Control interface Parameterisation Configuration support Program memory, user program Flags
[MB] [MB] [MHz]
[MB] Remanent data Global data memory
[kB] [MB]
Control elements Total number of axes Ethernet
Fieldbus interface
Number Connection technology Data transmission speed [Mbps] Supported protocols Number Connection technology Data transmission speed, can be [kbps] set via software Supported protocols Galvanic isolation
Technical data Type CPU data
Flash RAM Processor
[MB] [MB] [MHz]
Parameterisation Configuration support Additional functions Program memory, user program Flags
[MB] Remanent data Global data memory
Control elements Ethernet
Data interface
62
Number Connection technology Data transmission speed Supported protocols Number Connection technology Data transmission speed Supported protocols Max. cable length Galvanic isolation
[kB] [MB]
[Mbps]
[kbps] [m]
è Internet: www.festo.com/catalogue/...
CPX-CEC-C1-V3
CPX-CEC-M1-V3 SoftMotion functions for electric drives 32 256 800 CAN bus CODESYS V3 CODESYS V3 16
32 32 32 256 400 800 CAN bus CAN bus CODESYS V2.3 CODESYS V3 CODESYS V2.3 CODESYS V3 4 16 CODESYS variable concept 30 28 8 – DIL switch for CAN termination Rotary switch for RUN/STOP 31 127 1 RJ45 socket, 8-pin 10/100 TCP/IP, EasyIP, Modbus TCP 1 Sub-D plug connector, 9-pin 125, 250, 500, 800, 125, 250, 500, 800, 1000 1000 CAN bus Yes
28 –
31
125, 250, 500, 800, 1000
CPX-CEC
CPX-CEC-S1-V3
32 32 400 CODESYS V2.3 CODESYS V2.3 Diagnostic functions RS232 communication function 4 CODESYS variable concept 30 8 Rotary switch for RUN/STOP 1 RJ45 socket, 8-pin 10/100 TCP/IP, EasyIP, Modbus TCP 1 Sub-D socket, 9-pin 9.6 … 230.4 RS232 interface – Yes
32 256 800 CODESYS V3 CODESYS V3
16 CODESYS variable concept 28 –
30
Subject to change – 2018/04
Page 63
Terminal CPX Technical data – Control block CPX-CEC Connection and display components CPX-CEC-C1/-M1 1
1 CPX-MMI connection 2 DIL switch 3 Fieldbus interface (Sub-D plug connector, 9-pin) 4 Status LEDs, bus-specific and product-specific 5 RUN/STOP rotary switch 6 Ethernet interface (RJ45 socket, 8-pin)
4
2
5
3 6
Pin allocation – CPX-CEC-C1/-M1 Pin
Signal
Meaning
1 2 3 4 5 6 7 8 9 Housing n.c. CAN_L CAN_GND n.c. CAN_SHLD CAN_GND CAN_H n.c. n.c. Screening
Not connected CAN low CAN ground Not connected Connection to functional earth FE CAN ground (optional) 1) CAN high Not connected Not connected Plug connector housing must be connected to FE
1 2 3 4 5 6 7 8 Housing
TD+ TDRD+ n.c. n.c. RDn.c. n.c. Screening
Transmitted data+ Transmitted dataReceived data+ Not connected Not connected Received dataNot connected Not connected Screening
Fieldbus interface, Sub-D plug connector
Ethernet interface, RJ45 plug connector
1)
If a drive controller with external power supply is connected, CAN ground (optional), pin 6, on the CPX-CEC-C1/-M1 must not be used.
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
63
Page 64
Terminal CPX Technical data – Control block CPX-CEC Connection and display components CPX-CEC/CPX-CEC-S1-V3 1
1 CPX-MMI connection 2 DIL switch 3 RS232 interface (Sub-D socket, 9-pin) 4 Status LEDs, bus-specific and product-specific 5 RUN/STOP rotary switch 6 Ethernet interface (RJ45 socket, 8-pin)
4
2
5
3 6
Pin allocation – CPX-CEC/CPX-CEC-S1-V3 Pin
Signal
Meaning
1 2 3 4 5 6 7 8 9 Screening n.c. RXD TXD n.c. GND n.c. n.c. n.c. n.c. Screening
Not connected Received data Transmitted data Not connected Data reference potential Not connected Not connected Not connected Not connected Connection to functional earth
1 2 3 4 5 6 7 8 Housing
TD+ TDRD+ n.c. n.c. RDn.c. n.c. Screening
Transmitted data+ Transmitted dataReceived data+ Not connected Not connected Received dataNot connected Not connected Screening
RS232 interface, Sub-D socket
Ethernet interface, RJ45 plug connector
64
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 65
Terminal CPX Accessories – Control block CPX-FEC Ordering data Designation
Part No.
Type
Control block Motion functions for electric drives
CODESYS V2.3
155 g
567347
CPX-CEC-C1
CODESYS V3
135 g
3473128
CPX-CEC-C1-V3
SoftMotion functions for electric drives
CODESYS V3
135 g
3472765
CPX-CEC-M1-V3
RS232 communication function
CODESYS V2.3
155 g
567346
CPX-CEC
CODESYS V3
135 g
3472425
CPX-CEC-S1-V3
Sub-D plug connector, 9-pin, for CANopen
532219
FBS-SUB-9-BU-2x5POL-B
Connecting cable for RS232 interface
539642
FEC-KBG7
Connecting cable for RS232 interface
539643
FEC-KBG8
Micro Style bus connection, 2xM12 for DeviceNet/CANopen
525632
FBA-2-M12-5POL
Socket for Micro Style connection, M12
18324
FBSD-GD-9-5POL
Plug connector for Micro Style connection, M12
175380
FBS-M12-5GS-PG9
Open Style bus connection for 5-pin terminal strip for DeviceNet/CANopen
525634
FBA-1-SL-5POL
Terminal strip for Open Style connection, 5-pin
525635
FBSD-KL-2x5POL
Fieldbus interface
Ethernet interface RJ45 plug connector
Protection class IP65, IP67
534494
FBS-RJ45-8-GS
Cover for RJ45 connection
Protection class IP65, IP67
534496
AK-Rj45
8040451 8040452 8040453 8040454 8040455
NEBC-D12G4-ES-1-S-R3G4-ET NEBC-D12G4-ES-3-S-R3G4-ET NEBC-D12G4-ES-5-S-R3G4-ET NEBC-D12G4-ES-10-S-R3G4-ET NEBC-R3G4-ES-1-S-R3G4-ET
Straight plug, RJ45, 8-pin
Straight plug, M12x1, 4-pin, D-coded
Protection class IP20
Straight plug, RJ45, 8-pin
Straight plug, RJ45, 8-pin
Protection class IP20
2018/04 – Subject to change
1m 3m 5m 10 m 1m
è Internet: www.festo.com/catalogue/...
65
Page 66
Terminal CPX Accessories – Control block CPX-FEC Ordering data Designation
Part No.
Type
Covers and attachments Inspection cover, transparent, for Sub-D connection
533334
AK-SUB-9/15-B
536593
CPX-ST-1
German
569121
P.BE-CPX-CEC-DE
English
569122
P.BE-CPX-CEC-EN
Inscription label holder for manifold block
User documentation Manual for control block CPX-CEC
66
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 67
Terminal CPX Technical data – Bus node CPX-FB6 Bus node for handling communication between the electrical CPX terminal and a higher-order master via INTERBUS. The bus node is provided with system supply via the interlinking block and processes communication with the I/O modules. The status of the CPX terminal is displayed as a common message via four CPX-specific LEDs. The fieldbus communication status is displayed via four INTERBUS-specific LEDs.
Application Bus connection The bus connection is established via a 9-pin Sub-D socket and a 9-pin Sub-D plug with a typical INTERBUS pin allocation.
The bus connector plugs (with IP65/IP67 protection from Festo or IP20 protection from other manufac turers) facilitate the connection of the incoming and outgoing bus cable.
The outgoing bus plug contains the typical INTERBUS RBST bridge for identification of the outgoing bus connection.
The Sub-D interfaces are designed for controlling network components with a fibre-optic cable connection.
An example of this is access to the in tegrated diagnostic memory function, i.e. storage of the last 40 errors with timestamp, module, channel and error type.
With its address capacity of 96 inputs and 96 outputs, the CPX-FB6 supports a large number of I/O module configurations, including pneumatic interface.
-H- Note via the interlinking of the CPX modules and occupies an address capacity of the CPX system of: 8 byte outputs 8 byte inputs
The remaining address capacity of the control block or CPX system for actuating the peripherals is: 56 byte inputs 56 byte outputs
è Internet: www.festo.com/catalogue/...
67
INTERBUS implementation The CPX-FB6 supports the INTERBUS protocol to EN 50254. In addition to synchronous I/O exchange, the optional PCP channel can be used for parameterisation and diagnostic functions. The PCP channel provides access to advanced system information and assigns operation parameters while the controller is running via the user program.
If the PCP channel is used, the maximum number of possible process data bits is reduced by 16.
Special points in combination with CPX-CEC When a bus node is combined with a control block (CPX-CEC, in the fieldbus remote controller operating mode), the connected I/Os and/or valves, sensors and actuators are controlled via the CPX control block.
2018/04 – Subject to change
In this case, the bus node only provides the communication interface to the PLC. Communication between the control block and CPX bus node is established
Page 68
Terminal CPX Technical data – Bus node CPX-FB6 General technical data Type
CPX-FB6
Fieldbus interface Baud rate Bus type Ident. code Profile PCP channel Configuration support Max. no. of process data bits
[Mbit/s]
Inputs Outputs
[bit] [bit]
LED displays (bus-specific)
Device-specific diagnostics Parameterisation Additional functions
Control elements Operating voltage
Current consumption Protection class to EN 60529 Temperature range
Nominal value Permissible range Power failure buffering
[V DC] [V DC] [ms] [mA]
Operation Storage/transport
[°C] [°C]
Materials Grid dimension Dimensions (incl. interlinking block) W x L x H Weight
[mm] [mm] [g]
Sub-D, 9-pin, socket and pin 0.5 and 2 Remote bus 1, 2 or 3 (configuration-specific) 243 (PCP-channel activated) 12 (I/O device) Yes, 16 bit (optional via DIL switch) Icons for CMD software 96 96 UL = Operating voltage for INTERBUS interface RC = Remotebus check BA = Bus active RD = Remotebus disable TR = Transmit/receive Via peripherals error Start-up parameterisation via user functions (CMD) Via PCP communication Storage of the last 40 errors with timestamp (access via PCP) 8-bit system status in image table for inputs 2-byte inputs and 2-byte outputs, system diagnostics in image table DIL switch 24 (reverse polarity protected) 18 … 30 10 Typically 200 IP65, IP67 –5 … +50 –20 … +70 PA-reinforced PC 50 50 x 107 x 50 125
-H- Note Please observe the general limits and guidelines for the system when configuring the electrical modules.
68
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 69
Terminal CPX Technical data – Bus node CPX-FB6 Connection and display components 1
2
5
5
3
4
Pin allocation for the INTERBUS interface Pin allocation for Sub-D Pin
1 INTERBUS-specific LEDs 2 CPX-specific status LEDs 3 Fieldbus connection, incoming (9-pin Sub-D plug) 4 Fieldbus connection, outgoing (9-pin Sub-D socket) 5 DIL switch
Signal
Designation
Pin
1 2 3 4 5 6 7 8 9 Hous ing
DO1 DI1 GND n.c. n.c. /DO1 /DI1 n.c. n.c. Screened
Data out Data in Reference conductor/ground Not connected Not connected Data out inverse Data in inverse Not connected Not connected Connection to FE (functional earth) via R/C combination
1 3 5 2 4
1 2 3 4 5 6 7 8 9 Hous ing
DO2 DI2 GND n.c. +5 V /DO2 /DI2 n.c. RBST Screened
Data out Data in Reference conductor/ground Not connected Station detection1) Data out inverse Data in inverse Not connected Station detection1) Connection to FE (functional earth)
1 3 5 2 4
Pin allocation for M12
Incoming
Hous ing
Outgoing
Hous ing
The incoming interface is galvanically isolated from the CPX peripherals. The plug housing is connected to the functional earth FE of the CPX terminal via an R/C combination. 1) The CPX terminal contains the protocol chip SUPI 3 OPC. This ensures automatic detection of additional connected INTERBUS stations. There is therefore no need for a bridge between pin 5 and pin 9.
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
69
Page 70
Terminal CPX Accessories – Bus node CPX-FB6 Ordering data Designation
Part No.
Type
195748
CPX-FB6
Incoming
532218
FBS-SUB-9-BU-IB-B
Outgoing
532217
FBS-SUB-9-GS-IB-B
Connection block M12 adapter (B-coded)
534505
CPX-AB-2-M12-RK-IB
Inspection cover, transparent
533334
AK-SUB-9/15-B
Inscription label holder for connection block
536593
CPX-ST-1
Threaded sleeve, 4 pieces
533000
UNC4-40/M3x6
Adapter from 5-pin M12 to mini USB socket and controller software
547432
NEFC-M12G5-0.3-U1G5
User manual for bus node CPX-FB6
526433 526434 526435 526436 526437
P.BE-CPX-FB6-DE P.BE-CPX-FB6-EN P.BE-CPX-FB6-ES P.BE-CPX-FB6-FR P.BE-CPX-FB6-IT
Bus node INTERBUS bus node
Bus connection Sub-D plug
User manual
70
è Internet: www.festo.com/catalogue/...
German English Spanish French Italian
Subject to change – 2018/04