The text of a spec sheet · part 8 of 25
Modular electrical terminal CPX, pages 71 to 80
Pages 71 to 80 of 246
The original document is the PDF (8.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Festo CPX-EPL-EV
Page 71
Terminal CPX Technical data – Bus node CPX-FB11 Bus node for handling communication between the electrical CPX terminal and a DeviceNet network. The bus node is provided with system supply via the interlinking block and processes communication with the I/O modules. The status of the CPX terminal is displayed as a common message via four CPX-specific LEDs. The fieldbus communication status is displayed via the three DeviceNetspecific LEDs.
Application Bus connection The bus connection can be selected when ordering, either Micro Style as 2xM12 round connectors or OpenStyle as a terminal strip with IP20 protection.
Both connection types have the func tion of an integrated T-distributor with incoming and outgoing bus line.
DeviceNet implementation The CPX-FB11 operates with the “Predefined Master/Slave Connection Set” as a “Group 2 Only Server”. The polled I/O, change of state or synchronous method is used for the transmission of synchronous I/O data. The type of transmission can be selected in the network configuration.
The device diagnostics for all bus nodes CPX-FB11 is effectively gathe red via strobed I/O and displayed in the input table of the controller. In addition to synchronous data trans mission, asynchronous communica tion is supported through explicit messaging, which enables detailed device diagnostics and parameterisation.
A comprehensive EDS file supports the display of asynchronous data. It is also possible to display system infor mation and assign parameters while the controller is running via the user program or the configuration software.
An example of this is access to the in tegrated diagnostic memory function, i.e. storage of the last 40 errors with timestamp, module, channel and error type. With its address capacity of 64 byte inputs and 64 byte outputs, the CPX-FB11 supports any configuration of I/O modules, including pneumatic interface.
via the interlinking of the CPX modules and occupies an address capacity of the CPX system of: 8 byte outputs 8 byte inputs
The remaining address capacity of the control block or CPX system for actuating the peripherals is: 56 byte inputs 56 byte outputs
è Internet: www.festo.com/catalogue/...
71
Special points in combination with CPX-CEC When a bus node is combined with a control block (CPX-CEC, in the fieldbus remote controller operating mode), the connected I/Os and/or valves, sensors and actuators are controlled via the CPX control block.
2018/04 – Subject to change
In this case, the bus node only provides the communication interface to the PLC. Communication between the control block and CPX bus node is established
Page 72
Terminal CPX Technical data – Bus node CPX-FB11 General technical data Type
CPX-FB11
Fieldbus interface
[mm] [mm] [g]
Either Micro Style bus connection: 2xM12 with IP65, IP67 protection Open Style bus connection: 5-pin terminal strip, IP20 125, 250, 500 0 … 63 Set using DIL switch Communication adapter (12 dec.) 4554 dec. Polled I/O, change of state/synchronous, strobed I/O and explicit messaging EDS file and bitmaps 64 64 MS = Module status NS = Network status IO = I/O status Module and channel-oriented diagnostics by means of manufacturer-specific diagnostic object Module and system parameterisation via configuration interface in plain text (EDS) Online in run or program mode Storage of the last 40 errors with timestamp (access via EDS) 8-bit system status in image table for inputs 2-byte inputs and 2-byte outputs, system diagnostics in image table DIL switch 24 18 … 30 10 Typically 200 IP65, IP67 –5 … +50 –20 … +70 PA-reinforced PC 50 50 x 107 x 50 120
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Baud rate Addressing range Product Communication types Configuration support Max. address capacity
[kbps]
Type Code
Inputs Outputs
[byte] [byte]
Nominal value Permissible range Power failure buffering
[V DC] [V DC] [ms] [mA]
Operation Storage/transport
[°C] [°C]
LED displays (bus-specific)
Device-specific diagnostics Parameterisation
Additional functions
Control elements Operating voltage
Current consumption Protection class to EN 60529 Temperature range
Materials Grid dimension Dimensions (incl. interlinking block) W x L x H Weight
-H- Note Please observe the general limits and guidelines for the system when configuring the electrical modules.
72
Page 73
Terminal CPX Technical data – Bus node CPX-FB11 Connection and display components
1
2
4
3
Pin allocation for the DeviceNet interface Pin allocation Pin
1 Bus-specific LEDs 2 CPX-specific status LEDs 3 Selectable fieldbus connection Micro Style Open Style 4 DIL switch cover
Signal-specific core colour1)
Signal
Designation
– Blue Black – Blank – White – Red n.c. CAN_L 0 V bus n.c. Screened n.c. CAN_H n.c. 24 V DC bus
Not connected Received/transmitted data low 0 V CAN interface Not connected Connection to housing Not connected Received/transmitted data high Not connected 24 V DC supply for CAN interface
Micro Style bus connection (M12), incoming/outgoing Incoming 1 Blank 2 Red
Screened 24 V DC bus
Connection to housing 24 V DC supply for CAN interface
Sub-D plug 1 2 3 4 5 6 7 8 9
Outgoing
3
Black
0 V bus
0 V CAN interface
4
White
CAN_H
Received/transmitted data high
5
Blue
CAN_L
Received/transmitted data low
1 2
Blank Red
Screened 24 V DC bus
Connection to housing 24 V DC supply for CAN interface
3
Black
0 V bus
0 V CAN interface
4
White
CAN_H
Received/transmitted data high
5
Blue
CAN_L
Received/transmitted data low
1
Black
0 V bus
0 V CAN interface
2
Blue
CAN_L
Received/transmitted data low
3
Blank
Screened
Connection to housing
4
White
CAN_H
Received/transmitted data high
5
Red
24 V DC bus
24 V DC supply for CAN interface
1
Black
Screened
Connection to housing
2
Blue
24 V DC
24 V DC supply for CAN interface
3
Blank
0V
0 V CAN interface
4
White
CAN_H
Received/transmitted data high
5
Red
CAN_L
Received/transmitted data low
Open Style bus connection
Bus connection 7/8"
1)
Typical for DeviceNet connecting cables
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
73
Page 74
Terminal CPX Accessories – Bus node CPX-FB11 Ordering data Designation
Part No.
Type
DeviceNet bus node
526172
CPX-FB11
Sub-D plug
532219
FBS-SUB-9-BU-2x5POL-B
Connection block, socket Sub-D 9-pin, plug 7/8", 5-pin
571052
CPX-AB-1-7/8-DN
Micro Style bus connection, 2xM12
525632
FBA-2-M12-5POL
Socket for MicroStyle connection, M12
18324
FBSD-GD-9-5POL
Plug for Micro Style connection, M12
175380
FBS-M12-5GS-PG9
Open Style bus connection for 5-pin terminal strip
525634
FBA-1-SL-5POL
Terminal strip for Open Style connection, 5-pin
525635
FBSD-KL-2x5POL
Inspection cover, transparent
533334
AK-SUB-9/15-B
Inscription label holder for connection block
536593
CPX-ST-1
Adapter from 5-pin M12 to mini USB socket and controller software
547432
NEFC-M12G5-0.3-U1G5
User manual for bus node CPX-FB11
526421 526422 526423 526424 526425
P.BE-CPX-FB11-DE P.BE-CPX-FB11-EN P.BE-CPX-FB11-ES P.BE-CPX-FB11-FR P.BE-CPX-FB11-IT
Bus node
Bus connection
User manual
74
è Internet: www.festo.com/catalogue/...
German English Spanish French Italian
Subject to change – 2018/04
Page 75
Terminal CPX Technical data – Bus node CPX-FB13 Bus node for handling communication between the electrical CPX terminal and a higher-order master via PROFIBUS DP. The bus node is provided with system supply via the interlinking block and processes communication with the I/O modules. The status of the CPX terminal is displayed as a common message via four CPX-specific LEDs. The fieldbus communication status is displayed via the PROFIBUS-specific error LED.
Application Bus connection The bus connection is established via a 9-pin Sub-D socket with a typical PROFIBUS allocation (to EN 50170).
The bus connector plug (with IP65/IP67 protection from Festo or IP20 protection from other manufac turers) facilitates the connection of an incoming and an outgoing bus cable.
An active bus terminal can be connec ted using the DIL switch integrated in the plug.
The Sub-D interface is designed for controlling network components with a fibre-optic cable connection.
In addition to DPV0, asynchronous communication to the advanced spe cification DPV1 is supported. DPV1 provides asynchronous access to advanced system information and assigns operation parameters while the controller is running via the user program.
An example of this is access to the in tegrated diagnostic memory function, i.e. storage of the last 40 errors with timestamp, module, channel and error type.
With its address capacity of 64 byte inputs and 64 byte outputs, the CPX-FB13 supports any configura tion of I/O modules, including pneumatic interface.
via the interlinking of the CPX modules and occupies an address capacity of the CPX system of: 8 byte outputs 8 byte inputs
The remaining address capacity of the control block or CPX system for actuating the peripherals is: 56 byte inputs 56 byte outputs
è Internet: www.festo.com/catalogue/...
75
PROFIBUS DP implementation The CPX-FB13 supports the PROFIBUS DP protocol to EN 50170 Volume 2 for synchronous I/O exchange, paramete risation and diagnostic functions (DPV0).
Special points in combination with CPX-CEC When a bus node is combined with a control block (CPX-CEC, in the fieldbus remote controller operating mode), the connected I/Os and/or valves, sensors and actuators are controlled via the CPX control block.
2018/04 – Subject to change
In this case, the bus node only provides the communication interface to the PLC. Communication between the control block and CPX bus node is established
Page 76
Terminal CPX Technical data – Bus node CPX-FB13 General technical data Type
CPX-FB13
Fieldbus interface Baud rate Addressing range
[Mbit/s]
Product range Ident. number Communication types Configuration support Max. address capacity
Inputs Outputs
[byte] [byte]
Nominal value Permissible range Power failure buffering
[V DC] [V DC] [ms] [mA]
Operation Storage/transport
[°C] [°C]
LED displays (bus-specific) Device-specific diagnostics Parameterisation Additional functions
Control elements Operating voltage
Current consumption Protection class to EN 60529 Temperature range
Materials Grid dimension Dimensions (incl. interlinking block) W x L x H Weight
[mm] [mm] [g]
Sub-D socket, 9-pin (EN 50 170) Galvanically isolated 5 V 0.0096 … 12 1 … 125 Set using DIL switch 4: Valves 0x059E DPV0: Synchronous communication DPV1: Asynchronous communication GSD file and bitmaps 64 64 BF: Bus fault Identifier and channel-oriented diagnostics to EN 50170 (PROFIBUS standard) Start-up parameterisation via configuration interface in plain text (GSD) Asynchronous parameterisation via DPV1 Storage of the last 40 errors with timestamp (access via DPV1) 8-bit system status in image table for inputs 2-byte inputs and 2-byte outputs, system diagnostics in image table DIL switch 24 18 … 30 10 Typically 200 IP65, IP67 –5 … +50 –20 … +70 PA-reinforced PC 50 50 x 107 x 50 115
-H- Note Please observe the general limits and guidelines for the system when configuring the electrical modules.
76
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 77
Terminal CPX Technical data – Bus node CPX-FB13 Connection and display components
1
2
4
3
Pin allocation for PROFIBUS DP interface Pin allocation Pin
Signal
Designation
1 2 3 4 5 6 7 8 9 Housing n.c. n.c. RxD/TxD-P CNTR-P1) DGND VP n.c. RxD/TxD-N n.c. Screened
Not connected Not connected Received/transmitted data P Repeater control signal Data reference potential (M5V) Supply voltage (P5V) Not connected Received/transmitted data N Not connected Connection to housing
1 2 n.c. RxD/TxD-N
Not connected Received/transmitted data N
3 n.c.
Not connected
4
RxD/TxD-P
Received/transmitted data P
1 Bus status LEDs/bus fault 2 CPX-specific status LEDs 3 Fieldbus connection (9-pin Sub-D socket) 4 DIL switch cover
Sub-D socket
Bus connection M12 adapter (B-coded) Incoming
Outgoing
5 and M12 Screened
Connection to FE (functional earth)
1 2
VP RxD/TxD-N
Supply voltage (P5V) Received/transmitted data N
3
DGND
Data reference potential (M5V)
4
RxD/TxD-P
Received/transmitted data P
5 and M12 Screened 1)
Connection to FE (functional earth)
The repeater control signal CNTR-P is realised as a TTL signal.
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
77
Page 78
Terminal CPX Accessories – Bus node CPX-FB13 Ordering data Designation
Part No.
Type
PROFIBUS bus node
195740
CPX-FB13
Sub-D straight plug connector with terminating resistor and programming interface
574589
NECU-S1W9-C2-APB
Sub-D plug, straight
532216
FBS-SUB-9-GS-DP-B
Sub-D plug, angled
533780
FBS-SUB-9-WS-PB-K
Bus connection M12 adapter (B-coded)
533118
FBA-2-M12-5POL-RK
Connection block M12 adapter (B-coded)
541519
CPX-AB-2-M12-RK-DP
Socket M12x1, 5-pin, straight, for self-assembly of a connecting cable for FBA-2-M12-5POL-RK and CPX-AB-2-M12-RK-DP
1067905 NECU-M-B12G5-C2-PB
Plug M12x1, 5-pin, straight, for self-assembly of a connecting cable for FBA-2-M12-5POL-RK and CPX-AB-2-M12-RK-DP
1066354 NECU-M-S-B12G5-C2-PB
Terminating resistor, M12, B-coded for PROFIBUS
1072128 CACR-S-B12G5-220-PB
Bus node
Bus connection
78
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 79
Terminal CPX Accessories – Bus node CPX-FB13 Ordering data Designation
Part No.
Type
Inscription label holder for connection block M12
536593
CPX-ST-1
Inspection cover, transparent
533334
AK-SUB-9/15-B
Adapter from 5-pin M12 to mini USB socket and controller software
547432
NEFC-M12G5-0.3-U1G5
User manual for bus node CPX-FB13
526427 526428 526429 526430 526431
P.BE-CPX-FB13-DE P.BE-CPX-FB13-EN P.BE-CPX-FB13-ES P.BE-CPX-FB13-FR P.BE-CPX-FB13-IT
Bus connection
User manual
2018/04 – Subject to change
German English Spanish French Italian
è Internet: www.festo.com/catalogue/...
79
Page 80
Terminal CPX Technical data – Bus node CPX-FB14 Bus node for handling communication between the electrical CPX terminal and a CANopen network master or CANopen network. The bus node is provided with system supply via the interlinking block and processes communication with the I/O modules. The status of the CPX terminal is displayed as a common message via four CPX-specific LEDs. The different CANopen statuses and the fieldbus communication status are displayed via three additional LEDs. Application Bus connection The bus connection is established via a 9-pin Sub-D plug (pin) as per the CAN in Automation (CiA) specification DS 102 with additional 24 V CAN transceiver supply (option as per DS 102).
The bus connector plug (with IP65/IP67 protection from Festo or IP20 protection from other manufac turers) facilitates the connection of an incoming and an outgoing bus cable.
There are four contacts available for the four wires (CAN_L, CAN_H, 24 V, 0 V) of the incoming and outgoing bus cables.
Advanced system information can also be accessed by means of SDO commu nication. SDO communication also facilitates parameterisation before network startup or while the controller is running via the user program. An example of this is access to the in tegrated diagnostic memory function, i.e. storage of the last 40 errors with timestamp, module, channel and error type.
With its address capacity, the CPX-FB14 supports a large number of I/O module configurations, including pneumatic interface. By default, 8 byte digital inputs and 8 byte digital outputs can be addres sed via PDO 1.
8 analogue input channels and 8 ana logue output channels can be addres sed via PDO 2 and 3. Status and dia gnostic information can be evaluated via PDO 4. Additional 8 byte digital inputs and outputs as well as 8 analogue input and output channels can be addres sed via mapping.
via the interlinking of the CPX modules and occupies an address capacity of the CPX system of: 8 byte outputs 8 byte inputs
The remaining address capacity of the control block or CPX system for actuating the peripherals is: 56 byte inputs 56 byte outputs
CANopen implementation The CPX-FB14 supports the CANopen protocol in accordance with the specifications DS 301 V4.01 and DS 401 V2.0. Implementation is based on the CiA Pre-defined Connection Set. There are four PDOs available for fast I/O data exchange.
Special points in combination with CPX-CEC When a bus node is combined with a control block (CPX-CEC, in the fieldbus remote controller operating mode), the connected I/Os and/or valves, sensors and actuators are controlled via the CPX control block.
In this case, the bus node only provides the communication interface to the PLC. Communication between the control block and CPX bus node is established
80
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04