Page 81
Terminal CPX Technical data – Bus node CPX-FB14 General technical data Type
CPX-FB14
Fieldbus interface
Baud rate Addressing range Product range Communication profile Device profile Number Configuration support Max. address capacity
[kbit/s]
PDO SDO Inputs Outputs
[byte] [byte]
Nominal value Permissible range Power failure buffering
[V DC] [V DC] [ms] [mA]
Operation Storage/transport
[°C] [°C]
LED displays (bus-specific)
Device-specific diagnostics Parameterisation Additional functions
Control elements Operating voltage
Current consumption Protection class to EN 60529 Temperature range
Materials Grid dimension Dimensions (incl. interlinking block) W x L x H Weight
[mm] [mm] [g]
Sub-D pin, 9-pin (to DS 102) Bus interface galvanically isolated via optocoupler 24 V supply for CAN interface via bus 125; 250; 500 and 1,000 can be set via DIL switch Node ID 1 … 127 Set using DIL switch Digital inputs and outputs DS 301, V4.01 DS 401, V2.0 4 Tx/4 Rx 1 server SDO EDS file and bitmaps 16 digital, 16 analogue channels 16 digital, 16 analogue channels MS = Module status NS = Network status IO = I/O status Via emergency message Object 1001, 1002 and 1003 Via SDO Storage of the last 40 errors with timestamp (access via SDO) 8-bit system status via transmit PDO 4 (default) 2-byte inputs and 2-byte outputs, system diagnostics via PDO 4 Minimum boot-up Variable PDO mapping Emergency message Node guarding Heart beat DIL switch 24 18 … 30 10 Typically 200 IP65, IP67 –5 … +50 –20 … +70 PA-reinforced PC 50 50 x 107 x 50 115
-H- Note Please observe the general limits and guidelines for the system when configuring the electrical modules.
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
81
Page 82
Terminal CPX Technical data – Bus node CPX-FB14 Connection and display components
1
2
4
3
Pin allocation for the CANopen interface Pin allocation Pin
1 Bus-specific LEDs 2 CPX-specific status LEDs 3 Fieldbus connection (9-pin Sub-D, plug) 4 DIL switch cover
Signal
Designation
1 2 3 4 5 6 7 8 9 Housing n.c. CAN_L CAN_GND n.c. CAN_Shld GND CAN_H n.c. CAN_V+ Screened
Not connected Received/transmitted data low 0 V CAN interface Not connected Optional screened connection Ground1) Received/transmitted data high Not connected 24 V DC supply for CAN interface Connection to FE (functional earth)
1 2
Screened CAN_V+
Connection to FE (functional earth) 24 V DC supply for CAN interface
3
CAN_GND
0 V CAN interface
4
CAN_H
Received/transmitted data high
5
CAN_L
Received/transmitted data low
1 2
Screened CAN_V+
Connection to FE (functional earth) 24 V DC supply for CAN interface
3
CAN_GND
0 V CAN interface
4
CAN_H
Received/transmitted data high
5
CAN_L
Received/transmitted data low
1
CAN_GND
0 V CAN interface
2
CAN_L
Received/transmitted data low
3
Screened
Connection to FE (functional earth)
4
CAN_H
Received/transmitted data high
5
CAN_V+
24 V DC supply for CAN interface
Sub-D plug
Micro Style bus connection (M12) Incoming
Outgoing
Open Style bus connection
1)
82
Connected internally via Pin 3
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 83
Terminal CPX Accessories – Bus node CPX-FB14 Ordering data Designation
Part No.
Type
CANopen bus node
526174
CPX-FB14
Sub-D socket for CANopen with terminating resistor and programming interface
574588
NECU-S1W9-C2-ACO
Sub-D plug
532219
FBS-SUB-9-BU-2x5POL-B
Sub-D plug, angled
533783
FBS-SUB-9-WS-CO-K
Connection block, Sub-D socket, 9-pin, plug 7/8", 5-pin
571052
CPX-AB-1-7/8-DN
Micro Style bus connection, 2xM12, 5-pin
525632
FBA-2-M12-5POL
Fieldbus socket for Micro Style connection, M12, 5-pin
18324
FBSD-GD-9-5POL
Plug for Micro Style connection, M12, 5-pin
175380
FBS-M12-5GS-PG9
Open Style bus connection
525634
FBA-1-SL-5POL
Terminal strip for Open Style connection, 5-pin
525635
FBSD-KL-2x5POL
Inspection cover, transparent
533334
AK-SUB-9/15-B
Inscription label holder for connection block
536593
CPX-ST-1
Adapter from 5-pin M12 to mini USB socket and controller software
547432
NEFC-M12G5-0.3-U1G5
User manual for bus node CPX-FB14
526409 526410 526411 526412 526413
P.BE-CPX-FB14-DE P.BE-CPX-FB14-EN P.BE-CPX-FB14-ES P.BE-CPX-FB14-FR P.BE-CPX-FB14-IT
Bus node
Bus connection
User manual
2018/04 – Subject to change
German English Spanish French Italian
è Internet: www.festo.com/catalogue/...
83
Page 84
Terminal CPX Technical data – Bus node CPX-M-FB21 Bus node for handling communication between the electrical terminal CPX and a higher-order master via INTERBUS. The bus node processes communica tion with the I/O modules. The status of the terminal CPX is displayed as a common message via 4 CPX-specific LEDs. The fieldbus communication status is displayed via 6 INTERBUS-specific LEDs.
Application Bus connection The bus connection is established via a socket with INTERBUS Rugged Line connection technology and the associ ated plug, with fibre-optic cables used for the power supply to the valve terminal and data transmission.
The bus node is used as a remote I/O. It supports processing of max. 96 inputs and 96 outputs or max. 6 analogue I/O channels.
The I/O area is divided into: Digital I/O Analogue I/O
System status/system diagnostics (optional) PCP channel (optional)
An example of this is access to the in tegrated diagnostic memory function, i.e. storage of the last 40 errors with timestamp, module, channel and error type.
The PCP channel provides access to advanced system information and assigns operation parameters while the controller is running via the user program.
-H- Note
INTERBUS implementation The CPX-M-FB21 support the INTERBUS protocol to EN 50254. In addition to cyclic I/O exchange, the optional PCP channel can be used for parameterisation and diagnostic functions.
If the PCP channel is used, the max imum number of possible process data bits is reduced by 16.
Special features in combination with CPX-FB21 Remote Controller operating mode is not supported. A CPX-CEC cannot be used in combination with CPX-FB21 in a terminal CPX.
84
Power is supplied via the fieldbus connection. It is therefore not possible to use an interlinking block with system supply within a terminal CPX with CPX-M-FB21.
è Internet: www.festo.com/catalogue/...
Only the valve terminals VTSA and VTSA-F with pneumatic interface VABA-S6-1-X2 can be selected as the pneumatic part.
Subject to change – 2018/04
Page 85
Terminal CPX Technical data – Bus node CPX-M-FB21 General technical data Type Fieldbus interface Baud rate Bus type Max. address capacity LED displays
CPX-M-FB21 [Mbit/s] Inputs Outputs INTERBUS-specific
[bit] [bit]
CPX-specific
Device-specific diagnostics
Parameterisation
Additional functions
Operating elements Operating voltage
Nominal value Permissible range Intrinsic current consumption at nominal operating voltage Protection class to EN 60529 Temperature range Operation Storage/transport CE marking (see declaration of conformity) Housing materials Note on materials Grid dimension Dimensions (incl. interlinking block) W x L x H Product weight CPX-FB21
[V DC] [V DC] [mA] [°C] [°C]
[mm] [mm] [g]
Rugged Line fibre-optic cable connection 0.5 and 2 Remote bus 96 96 BA = Bus active FO1 = Fibre-optic cable 1 FO2 = Fibre-optic cable 2 RC = Remotebus check RD = Remotebus disable UL = Operating voltage for INTERBUS interface M = Parameterisation SF = System fault US1 = Electronics supply, sensor supply US2 = Load supply Diagnostic memory Channel and module-oriented diagnostics Module undervoltage Diagnostic behaviour Fail-safe response Forcing of channels Signal setup System parameters Module and system parameterisation via operator units System status can be represented using process data Additional diagnostic interface for operator units DIL switches 24 (polarity-safe) 18 … 30 Typically 90 IP65, IP67 –5 … +50 –20 … +70 To EU EMC Directive Aluminium RoHS-compliant 50 100 x 110 x 130 1,255
-H- Note Please observe the general limits and guidelines for the system when configuring the electrical modules.
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
85
Page 86
Terminal CPX Technical data – Bus node CPX-M-FB21 Connection and display components 1
2 3
5
1 2 3 4 5
4
Pin allocation for INTERBUS interface FOC pin allocation
DIL switch INTERBUS-specific LEDs Fieldbus connection, incoming CPX-specific status LEDs Fieldbus connection, outgoing
Pin
Wire colour
Designation
A
Black
Transmitted data
B
Orange
Received data
1
–
24 V supply for electronics and inputs
2
–
0 V supply for electronics and inputs
3
–
24 V supply for valves and outputs
4
–
0 V supply for valves and outputs
5
–
Functional earth
A
Orange
Transmitted data
B
Black
Received data
1
–
24 V supply for electronics and inputs
2
–
0 V supply for electronics and inputs
3
–
24 V supply for valves and outputs
4
–
0 V supply for valves and outputs
5
–
Functional earth
Incoming
Outgoing
86
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04
Page 87
Terminal CPX Accessories – Bus node CPX-M-FB21 Ordering data Designation
Part No.
Type
INTERBUS bus node, incoming and outgoing fieldbus connection
572221
CPX-M-FB21
Blanking plate for covering the DIL switches
572818
CPX-M-FB21-IB-RL
575107 575108 575109 575110 575111
P.BE-CPX-FB20/21-DE P.BE-CPX-FB20/21-EN P.BE-CPX-FB20/21-ES P.BE-CPX-FB20/21-FR P.BE-CPX-FB20/21-IT
Bus node
Bus connection
Manual Manual – Bus nodes CPX-M-FB21
2018/04 – Subject to change
German English Spanish French Italian
è Internet: www.festo.com/catalogue/...
87
Page 88
Terminal CPX Technical data – Bus node CPX-FB23-24 Bus node for handling communication between the electrical CPX terminal and a higher-order master for Control & Communication-Link (CC-Link) from Mitsubishi. The bus node is provided with system supply via the interlinking block and processes communication with the I/O modules. The status of the CPX terminal is displayed as a common message via 4 CPX-specific LEDs. The fieldbus communication status is displayed via 4 CC-Link-specific LEDs.
Application Bus connection The bus connection can be selected when ordering and is established by means of a screw terminal with IP20 protection, a Sub-D plug with IP65/IP67 protection from Festo or IP20 protection from other manufacturers. Both connection types have the func tion of an integrated T-distributor and thus support the connection of an incoming and outgoing bus cable.
Function module F24 corresponds to CC-Link version 2.0 and supports a maximum of four stations per slave, up to an address capacity 64 bytes of digital I/O and 64 bytes of analogue I/O each. It is possible to optimise the configur ation of the addressing in terms of either cycle time or station.
Function module F23 corresponds to CC-Link version 1.1 and supports a maximum of four stations per slave, up to an address capacity 32 bytes of digital I/O and 14 bytes of analogue I/O each.
The function module and option are set using the DIL switch on the CPX bus nodes.
When a bus node is combined with a control block (CPX-CEC, in the fieldbus remote controller operating mode), the connected I/Os and/or valves, sensors and actuators are controlled via the CPX control block.
In this case, the bus node only provides the communication interface to the PLC. Communication between the control block and CPX bus node takes place by interlinking of the CPX modules and takes up the following address capacity in the CPX system: 8 byte outputs 8 byte inputs The following address capacity remains in the control block or CPX system for actuation of the peripherals: 56 byte inputs 56 byte outputs
88
è Internet: www.festo.com/catalogue/...
CC-Link implementation The CPX bus node CPXFB2324 op tionally supports the CC-Link versions 2.0 (as function module F24) and 1.1. (as function module F23). These designations are also found in the system diagram for the CPX Maintenance Tool (CPX-FMT) or in the operator unit (CPXMMI-1) from Festo.
Points to note in connection with CPX-CEC
Subject to change – 2018/04
Page 89
Terminal CPX Technical data – Bus node CPX-FB23-24 General technical data Type
CPX-FB23-24
Fieldbus interface
Baud rates Protocol Max. address capacity, inputs
[kbps] FB23 FB24
Max. address capacity, outputs
FB23 FB24
RWr Rx RWr Rx RWw Ry RWw Ry
[byte] [byte] [byte] [byte] [byte] [byte] [byte] [byte]
LED displays (bus-specific)
Device-specific diagnostics
Parameterisation
Additional functions Control elements Operating voltage Current consumption Protection class to EN 60529 Temperature range
Nominal value Permissible range
[V DC] [V DC] [mA]
Operation Storage/transport
[°C] [°C]
Materials Grid dimension Dimensions (incl. interlinking block) W x L x H Product weight
[mm] [mm] [g]
Either Sub-D socket, 9-pin Sub-D plug, for self-assembly Screw terminal strip, IP20 156 … 10,000 CC-Link 32 14 64 64 32 14 64 64 RUN = Communication status ERROR = Communication error SD = Send data RD = Receive data Diagnostic memory Channel and module-oriented diagnostics Module undervoltage Diagnostic behaviour Fail-safe response Forcing of channels Signal setup System parameters System status can be displayed using process data Additional diagnostic interface for operator units DIL switches 24 18 … 30 Typically 200 IP65, IP67 –5 … +50 –20 … +70 PA reinforced, PC 50 50 x 107 x 50 115
-H- Note Please observe the general limits and guidelines for the system when configuring the electrical modules.
2018/04 – Subject to change
è Internet: www.festo.com/catalogue/...
89
Page 90
Terminal CPX Technical data – Bus node CPX-FB23-24 Connection and display components
1
2
4
3
Pin allocation for the CC-Link interface Pin allocation
1 Bus-specific status LEDs 2 CPX-specific status LEDs 3 Fieldbus connection (9-pin, Sub-D socket) 4 DIL switch cover
Pin
Signal
Designation
1 2 3 4 5 6 7 8 9 n.c. DA DG n.c. FE1) n.c. DB n.c. n.c.
Not connected Data A Data reference potential Not connected Functional earth Not connected Data B Not connected Not connected
1
FG
Functional earth/housing
2
SLD
Screening
3
DG
Data reference potential
4
DB
Data B
5
DA
Data A
Sub-D socket
Screw terminal bus connection
90
è Internet: www.festo.com/catalogue/...
Subject to change – 2018/04