Micro 84 Programmable Controller User's Manual, pages 91 to 100

Pages 91 to 100 of 124

The original document is the PDF (6.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Gould Micro 84 Controller, Modicon Micro 84 Controller, AEG Micro 84 Controller and Schneider Micro 84 Controller

Page 91

Environmental Requirements 0 to 60°C Operating Temperature

8370 rl EFIMINAL sTRIP -

0 to 95% (non-condensing)

Humidity Vibration

0.625 G, 50-500 Hz

EMI

MIL-STD-461-B

MI

Helmholtz coil (20 Gauss)

RFI Surge Withstand Capability (SWC)

FCC Class A

1

ENA=sLE’LATCHLED DISPLAY OR OTHER EC0 DEVICE (REQUIRES 5VI

15 G for 11 ms

’ Shock

IEEE STD. 472-1976 ANSI C37.90A-1976 (25OOV, 1.5 MHz for 61~s) coupled and radiated

Dimensions (W x H x D)

1.63 in x 10.50 in x 5.50 in (41.40 mm x 266.70 mm x i39.70 mm)

Weight

1 lb (0.45 kg)

Termination

Screw terminals on removable wiring strip

Cable

25 feet maximum; longer if shielded; Cmax = .047

Wire Size

Two #18 AWG (max)

Construction

Lexan

Indicator

FAULT (on when diagnostics fail)

ENABLEILATCH

LEDD’SPLAYOR

OTHER BCD DEVICE (REQUIRES 5V1

6370, BCD Register Output Module Terminal Numbering and Output Connections

J

999

:

750

2 ;: u iE w

500 f z 250

B370, BCD Register

Output

Block Diagram

Module 250

500

750

999

BCD VALUE

Numerical Output of B370 is Directly Proportional to Output Value

Page 92

Network No. 1 . Output a tlmer, counter, or sequencer value. 1001 I I

IY Yl xxx

TI.0 4010

Network No. 3 - Output several registers to a single display using a pushbutton sequence.

J

10 0001

0001 I I I I 1002 IX XI xxx CTR 4012

10 0002 r

0002

IY XI

0001

Network #l demonstrates how to output register values to any field device. Register 4010 accumulates time and outputs its value to the B370. Similarly, register 4012 accumulates counts and outputs its value to the second B370 channel. “XXX” may be a constant or another register.

Network No. 2 - Output several registers to a single display using a rotary switch.

I

1005

-

4008

Network #3 shows how to output several internal registers to a single output register for display. Switch 1001 is a pushbutton that increments sequencer register 4008. Registers 40XX can be any register (including 3001 through 3004) except 4008, 4009, and 4010. The display output register is 4010. (Register 4009 should be set to zero.) To display additional registers, add similar logic in another network.

Network No. 4 = Output several registers to a single display using a thumbwheel.

n

Network #2 shows how to output several internal registers to a single output register for display. Switches 1001 through 1006 are contacts of a rotary switch. Only one switch is ON at a time. Registers 40XX can be any register (including 3001 through 3004) except 4009 and 4010. (Register 4009 should be set to zero.) The display output register is 4010. To display additional registers, add similar logic in another network.

Network #4 demonstrates how to output several internal registers to a single output register for display. A thumbwheel increments sequencer register 4002 via additional register 4001. Registers 40XX can be any register (including 3002 through 3004) except 4001, 4002, 4009, and 4010. (Register 4009 should be set to zero.) To display additional registers, add similar logic in another network.

-ii

GOULD Electronics

Page 93

PI-B371-001

Rev B

B371-001 BCD Register Input Module DATA SHEET ,

The 8371-001 BCD Register Input Module converts two, 12-bit binary coded decimal value and applies this value to the Micro 84’” controller.

numbers to a numerical

FEATURES . Two 3-digit channels .

Popular True High BCD Format

.

Active or passive

.

Data inhibit selection

.

TTL and CMOS

.

12-bit BCD resolution

.

Continuous on-line diagnostics

.

Removable wiring strip

.

Designed

.

UL listed

GENERAL

J field device compatible capability during data compatible for harsh industrial environments

DESCRIPTION

The B371-001 BCD Register Input is an input module for the Micro 84 controller. It converts each of two 12.bit binary coded decimal (BCD) signals to a numerical value. This value ranges from 0 to 999. The actual numerical value is directly proportional to the BCD input. For example, if the BCD input increases 10 percent, the numerical output also increases 10 percent. The BCD Register takes the numerical value and transfers it automatically to input registers 3001 through 3004. Once in one of these registers, the numberical value can control a timer, or a counter, or a sequencer. It can also be manipulated by arithmetic functions. Typically, the B371 is used in applications such as interfacing operator control panels with the Micro 84, set point control, and data acquisition. Looking at the terminal numbering and connections diagrams, notice that the inputs to the B371 come from thumbwheels, keypads, panel meters, and other BCD compatible devices. The format of this input is true high (positive) BCD with isolating diodes. These diodes are polarized so that the anode of each diode is connected to the thumbwheel switch common, and the cathode is connected to each input of the B371 12-line BCD bus. You can see this by looking at the connections diagram. This diagram shows the connections for two thumbwheels or other BCD devices. If you use only one, the diodes are not required. Digital panel meters should have tri-state outputs, if both channels are used. Notice from the diagram that two BCD devices (or channels) are multiplexed to the B371 on one 12.line BCD bus. These channels are controlled by two strobes: Strobe 1 and Strobe 2. These strobes alternately select, in true high format, each channel at a through-put rate suffi. cient to update both channels on each scan of the Micro 84. The B371 terminal strip shown on the diagram is the front panel connector. This connector contains a removable male plug that contains 15screw terminals. It is easily ii!+ GOULD Electronics

Page 94

removed, which allows you to quickly replace the B371 without disturbing field wiring. For this wiring, you can use shielded or unshielded wiring having a wire size of 14 to 22 AWG. The terminals are clearly marked. This allows you to make your field wiring connections quickly and easily. Besides the connector with its removable plug, a FAULT indicator is also located on the front of the BCD Register. The indicator is a troubleshooting aid. It turns on whenever the internal diagnostic test detects a failure. This test continuously exercises the following B371’s internal circuits: random access memory (RAM), read only memory (ROM), and communications circuitry during each scan of the Micro 84. For predictability and safety, if the test detects multiple consecutive failures, it stops the Micro 84’s scanning operation and turns on FAULT. In addition to the FAULT indicator, Gould provides for an optional data change switch. This switch, when closed, prevents the B371 from reading incorrect values whenever you change thumbwheel settings or change settings of other field devices. Instead of a switch, you could use a keyswitch to prevent unauthorized tampering of thumbwheel or other field devices. The BCD Register is easy to install. First it is housed in a lightweight, shielded durable Lexan case. It contains mounting brackets at the rear of the case, which simplifies installation. Next, it can be mounted anywhere in the I/O structure. Connectors located on the left- and rightrear sides of the case plug into similar connectors on adjacent modules. This plugging action automatically connects the 8371 to the data bus of the Micro 84. If the B371 is the right-most module in the I/O structure, you plug a termination connector into the connector located on the right-rear side. This termination connector is shipped with the Micro 84 controller. The Micro 84 also provides the B371 with operating voltages through this connector. The 8371 does not require a separate power supply. The 8371-001 Register Input meets the stringent requirements of both IEEE and ANSI standards for radiated surge withstand capability (SWC). The 8371 also withstands the severe voltage transients, electromagnetic interference, and magnetic fields commonly encountered in an industrial environment.

SPECIFICATIONS Electrical Characteristics Input Range

O-8 VDC

Output

Current

Levels Bus Inputs

TTL or CMOS compatible Logic “0” < 0.7 VDC Logic “1” > 2.4 VDC

Module

Isolation

Strobe Outputs

Logic “0” < 0.4 VDC @ 2 mA Logic “1” > 4.0 VDC @ 2 mA

Input/Output Protection

Limit

4 mA (typical) 1500 VRMS12500 one minute

VDC for

Field Device Resistance

ON < 200 ohms OFF > 40K ohms

Multiplex

250 Hz (typical)

Frequency

Strobe Width

1 ms (typical)

Data Format

0 to 999 counts inputs linear to

Both channels each scan updated

240 VAC continuous

Circuit Characteristics Topology

Two, 3-digit channels

Field Device

Passive or Active (tristate) True High BCD Nos. 3001 & 3002 or Nos. 3003 & 3004

Register

Format

Throughput

Rate on

Page 95

THUMBWHEEL BCD

OR OTHER

TENS DIGIT

UNITS DIGIT

0371 TERMINAL STRIP

DEVICE HUNDREDS DIGIT

I

REG I (STROBE

I

I1

4 5 6 7 B 9 IO II

-__ -1

DATA CHANGE SWITCH (OPTIONAL) /

/

2

4 e

$0 20 $0 80

’

100*004w 0 ‘ .0 I

_

J

I

~~siQzL~

BCD o~PuTS gy ACTIVE

BCD DEVICE

B371 BCD Register Input Module Terminal Numbering and Input Connections

B371, BCD Register Input Module Block Diagram

Environmental Requirements Operating /

Temperature

Humidity

0 to 95% (non-condensing)

Shock

15 G for 11 ms

Vibration

0.625 G, 50-500 Hz

EMI

MIL-STD-461

MI

Helmholtz

RFI

FCC Class A

Surge Withstand Capability (SWC)

Dimension

J

0 to 60°C

(W x H x 0

B coil (20 Gauss)

IEEE STD 472-1974 and ANSI C37.90-1974 (2500 V, 1.5 mHz for 6 vs) coupled 1.63 in x 10.50 in x 5.50 in (41.40 mm x 266.70 mm x 139.70 mm)

0

260

500

750

999

BCD VALUE

(0.45 kg)

Weight

1 lb

Termination

Screw Terminals on removable wiring strip

Cable

25 feet maximum; shielded

Wire Size

Two #18 AWG (max)

Construction

Lexan

Indicator

FAULT (ON when diagnostics fail)

longer if

Numerical Output of B371 is Directly Proportional to Input BCD Value

Page 96

TYPICAL

USER PROGRAMS

Network No. I - Simple Thumbwheel Entry for Timer, Counter, Sequencer Preset

Network #I demonstrates how to preset any register with a set of thumbwheels. Contact 1001 starts the timer and contact 1002 resets it. Wiring an optional data change switch as shown in the 8371 Connection Diagram prevents erroneous data from getting into register 3001.

Network No. 3 - Loading a Series of Registers with Two Thumbwheels

Network No. 4 - Loading a Series of Registers with Two Thumbwheels (cant)

2208

“0”

Network No. 2 - Thumbwheel Selection of Sequencer Step

I-’ 22*b”-Qr

Oooi

I

Network #2 shows how to force a sequencer to a particular step determined by a thumbwheel. Contact 1001 ON places the thumbwheel value into sequencer register 4002. This turns ON sequencer contact 22XX where “XX” is the thumbwheel value from 1 to 16. A zero value switches sequencer to the home position, therefore no contacts are activated.

~~~0~~~

4023

403 I

(4024

(4032)

Network #3 and #4 demonstrate how to load values into several registers using only two thumbwheels and one 8371 BCD Register Input Module. One thumbwheel, addressed by register 3001, selects the internal register to receive data. Another thumbwheel, addressed by register 3002, selects the loaded numerical value. An addition function in register 4001 increments sequencer control in register 4002. To load an internal register 40Xx, the contents of 3002 is added to another register (address 40Xx-l). Sequencer control determines which addition register is executed. All registers are initialized to zero. For best results and safety, use the B37l’s data change capability.

=”

GOULD Electronics

Page 97

PI-6373-001

Rev B

B373-001 O-IO VDC Analog Input DATA SHEET u’

The B373-001, O-10 VDC Analog Input converts two O-10 VDC analog from 0 to 999 and feeds these values to the Micro 84’” controller.

signals to numerical values that range

FEATURES Two isolated channels

Both channels Differential

O-10 VDC compatible inputs

High Accuracy lo-bit resolution

Self-contained power supply

Optional Fanning Strip permits module removal without disturbing field wiring Designed for harsh industrial environments

UL listed

GENERAL

~

DESCRIPTION

The B373-001 O-10 VDC Analog Input is an input module for the Micro 84 controller. It converts two O-10 VDC analog signals to numerical values that range from 0 to 999. These values are directly proportional to the input. For example, if the input voltage increases 10 percent, the numerical output also increases 10 percent. The Analog Input Module transfers these numerical values to input registers 3001 through 3004. Once in the registers, these values can be used to control timers, counters, sequencers; or it can be manipulated by arithmetic functions. Typically, the B373 is used in data acquisition and set point applications. The varying voltages which are inputs to the B373, represents parameters such as pressure, level, temperature, humidity, weight and position. These inputs come from transmitters or transducers that may be located several hundred feet from the input module. You simply connect these inputs to a front-mounted, screw terminal strip. This strip is compatible with an optional Fanning Strip (P/N 0212-012), which allows quick module replacement without disturbing field wiring. To simplify installation, the terminals on the strip are clearly marked as to which is channel

1 and which is channel 2, so that you can connect the varying d-c voltage operation to either or both channels. The voltage input is actually a differential input to achieve high accuracy and significant noise immunity. Moreover, you can make the connections without adding more electronic components. Besides the terminal strip, an OUT OF RANGE diagnostic indicator for troubleshooting is also located on the front of the B373 module. It flashes whenever the input is out of its prescribed range (O-10 VDC). This indicator will also show that one of the input wires is either shorted to ground or open. Both Channel 1 and Channel 2 inputs are isolated from each other. In addition, the inputs are isolated from all l/O modules connected to the Micro 84 and from the Micro 84 controller itself.

-ii

GOULD Electronics

Page 98

The B373 is easy to install. First it is housed in a lightweight, shielded, durable Lexan case. It contains mounting brackets at the rear of the case which simplifies installation. Next, it can be mounted anywhere in the l/O structure. Connectors located on the left- and right-rear sides of the case plug into similar connectors on adjacent modules. This plugging action automatically connects the Analog Input Module to the data bus of the Micro84. If the B373 is the right-most module in the l/O structure, you have to plug a termination connector into the connector located on the right-rear side. This termination connector is shipped with the Micro 84 controller. To minimize installation costs, the Micro 84 provides the B373 with all operating voltages, thus eliminating the need for a separate power supply. The B373 meets the stringent requirements of both IEEE and ANSI standards for radiated surge withstand capability (SWC). The B373 also withstands the severe voltage transients, electromagnetic interference, and magnetic fields commonly encountered in an industrial environment.

SPECIFICATIONS Electrical Characteristics Input Range

O-10 VDC

Resolution

1 of 999 counts

Voltage

10 mV per count mode

Accuracy

+ 0.1%/l f 0.2%/2 O-60%* count @ 25°C counts @

*(You can recalibrate to + 0.1% at a particular temperature betwen 0-6OOC.) 0.05%

Input Impedance

1 Megohm, differential 0.5 Megohm each input to shield

Modes

Register

Format

Data Format Throughput

Module

Isolation

1500 VRMS minute

Input Protection

240 VRMS

Common Mode Rejection

- 86 dB @ 50160 Hz for one

-3 dB down @ 18 Hz, rolloff 20 dB per decade

Environment Requirements 2 channels

Operating

Independently selectable current or voltage

Humidity

0 to 95% (noncondensing)

Nos. 3001 & 3002 or Nos. 3003 & 3004

Shock

15 G for 11 ms

Vibration

0.625 G, 50-500 Hz

EMI

MI L-STD-461 B

MI

Helmholtz

RFI

FCC Class A

Surge withstand Capability (SWC)

IEEE STD 472-1974 and ANSI C37.90-1974 (2500 V, 1.5 mHz for 6 ps) Coupled

0 to 999 counts inputs Rate

19 VI-7 V (with respect to module shield terminal)

of full scale

Circuit Characteristics Operating

Isolation

Input Filter

Linearity

Topology

Channel linear to

1.25 samples per second (each channel)

Temperature

0 to 60°C coil (20 Gauss)

Page 99

8373, O-10 VDC Analog Input Module Terminal Numbering and Input Connections

J

Dimension (W x H x D)

1.63 in x 10.50 in x 5.50 in (41.40 mm x 266.70 mm x 139.70 mm)

Weight

1 lb (0.45 kg)

Termination

Screw Terminals; Fanning Strip Compatible

Wire Size

Two #14 AWG (max)

Construction

Lexan

Indicator

OUT OF RANGE

8373, O-10 VDC Analog Input Module Block Diagram

NUMERICAL VALUE

I

0

2:5 i

7.5

VOLTS EACH NUMERICAL VALUE IO MV

IO

EQUALS

Relationship Between Numerical Value and Voltage Inputs

Page 100

TYPICAL

USER PROGRAMS

Network No. I Simple Set Point Control l

Network #l compares the value from an analog input with a preset value in register 4009. If the input value is greater than or equal to the preset value, coil 0001 is ON. Conversely, if the input is less than or equal to the preset value, coil 0002 is ON. This comparison is performed on every Micro-84 scan. Network No. 2 . Sat Point Control

Network #2 performs a similar set point function as Network #l, but both coils do not go ON when the input value is equal to the preset value in register 4009. Coil 0002 is ON only when the input is less than the preset value. Greater than or equal input values turns on coil 0001. Alternately, a normally closed 0002 contact positioned prior to coil 0001 (while receiving contact 0001) will prevent equal values from turning ON coi I 0001.

Network #3 will turn ON coil 0001 when the analog-input value is less than or equal to the preset in register 4009. Coil 0002 is ON when the input value is greater than or equal to the preset value in register 4011. The preset value in register 4011 is greater than the preset value in register 4009. Values between these will turn both coils OFF. Network No. 4 - “Pass Bmnd” Set Point Control

Network #4 performs the inverse of Network #3. Coil 0001 is ON only when the analog input is between or equal to preset values in registers 4009 and 4011. The preset value in register 4011 is greater than the preset value in register 4009.

ii.+ GOULD Electronics