Page 101
PI-B374-001
B374-001
Rev B
I 4-20 mA, Analog Output Module
DATA SHEET ’
The B374-001, 4-20 mA Analog Output Module receives numerical values that range from 0 to 999 from the Micro 84’” Controller and converts them into two 4-20 mA output currents.
FEATURES . Two isolated .
Popular 4-20 mA current outputs
.
Current sink or source capability
.
10 bit resolution
.
Voltage
.
High accuracy
.
“Hold last value” user selectable
.
Optional fanning strip permits module removal without disturbing field wiring
.
Designed for harsh industrial environments
.
UL listed
GENERAL
J channels monitor outputs and speed or “reset to zero”
DESCRIPTION
The B374-001 4-20 mA Analog Output is a dual channel output module for the Micro 84 Controller. It converts numerical values that range from 0 to 999 to an output current. This current ranges from 4 mA to 20 mA and is proportional to the input. For example, if the numerical input increases 10 percent, the output current also increases 10 percent. The 8374 is used to interface output registers with any 4-20 mA analog field device. Typical registers are timers, counters and sequencers. Typical analog field devices are valves, recorders, I/P converters, indicators, and servo controllers. You can connect these field devices to both a power supply and the B374 without using additional components. Field devices can be located several hundred feet from the output module.
J
Specifically, the B374 Analog Output module interfaces field devices with the following output registers: 4010, 4012, 4014, and 4016 of the 1K Micro 84, and 4010, 4012, 4014, 4016, 4018, 4020, 4022, and 4024 of the 2K Micro 84. The 1K Micro 84 supports a maximum of two B374’s, and the 2K Micro 84 supports a maximum of four B374’s.
Whichever Micro 84 you use, it is important that you understand the addressing technique used by the controller and its register output modules. In addition to the B374, the controller can use other modules such as the B370 BCD Register Output Module. Either of these modules can be the first register output module. Whichever you use, the first module addresses module output registers 4010 and 4012. The second module, regardless of whether it is a B370 or a B374, addresses registers 4014 and 4016. The third and fourth modules, if used, address registers 4018 through 4024 in a similar manner. The B374 Analog Output Module features two modes used with the Micro 84’s standby operation. (Standby means that the Micro 84 is powered up but not scanning.) These two modes are “hold last output” (HOLD) or “return to zero” (RTZ). HOLD retains the value of the output current at the time the Micro 84 switches to standby. RTZ switches the output current to zero, which is equivalent to an open circuit, whenever the Micro 84 stops scanning. Scanning of the Micro 84 can be stopped manually from
-ii
GOULD
Page 102
the programming panel, or by a program pack, or by the internal diagnostics of the controller. The RTZ and HOLD modes permit safer operation by allowing you to select the output condition best suited by your application, whenever the Micro 84 enters standby. The HOLD or RTZ mode is switch selectable. The toggle switches for selecting the HOLD and RTZ modes are located on the rear of the B374 housing, (see the last page of this data sheet for the location of these switches.) Switch 1 controls channel 1 and switch 2 controls channel 2. Switches 3 and 4 are not used. Set each switch either “up” for RTZ or “down” for HOLD before installing the B374. The 8374 Analog Output Module is easy to install. It is housed in a lightweight, shielded, durable, dripproof Lexan case. It contains mounting brackets which simplify installation. It can be mounted anywhere in the l/O structure. Connectors located on the left- and right-rear sides of the case plug into similar connectors on adjacent modules. This plugging action automatically connects the B374 to the data bus of the Micro 84 Controller. If the B374 is the right-most module in the l/O structure, plug a termination connector into the connector on the right-rear side. This termination connector is supplied with the Micro 84 controller. Field wiring is also easy to install. Connect field wiring to front-mounted, screw terminal strip. It is recommended that you use shielded, twisted-pair cable with insulating jacket to minimize radiated interference. The terminal strip is compatible with an optional Fanning Strip (P/N 0212-012), which allows quick module replacement without disturbing field wiring. All terminals are clearly marked for their intended function. The B374 requires an external power supply for its operating voltages. This same power supply can also be used to power one or both current loops. Besides the terminal strip, a POWER indicator is also located on the front of the B374 module as a troubleshooting aid. This green indicator is on when the external power supply is connected to the module. When the POWER indicator is off, it shows that the module is not receiving its operating voltages and, thus, will not operate. The screw terminal strip provides terminals that allow you to use a voltmeter to monitor the output current. Just connect a high impedance voltmeter between the VOLTAGE MON. (1 or 2) and CURRENT SOURCE (1 or 2) as shown in the “Terminal Numbering and Output Connections” diagram. The voltage will range from + 1 to +5 VDC. It is proportional to the output current. Both channel 1 and channel 2 outputs are isolated from each other and from all l/O modules connected to the Micro 84. In addition, the channels are isolated from the Micro 84 controller itself. The B374 meets the stringent requirements of both IEEE and ANSI standards for surge withstand capability (SWC). The module has been designed to meet the requirements of both UL and CSA standards. The B374 also withstands the severe voltage transients, electromagnetic interference, and magnetic fields commonly encountered in an industrial environment.
Page 103
SPECIFICATIONS Electrical
Characteristics
Output Current Range
Monitor
Voltage
Range
4-20 mA (0 mA when Micro 84 in standby and B374 in RTZ mode) l-5 VDC
Loop Power Supply
60 VDC (max)
Over Voltage
240 VRMS
Protection
Load Resistance
Range Rmax
=
Vloopnr,
7
Voltage Monitor Output Impedance Voltage
Monitor
220 ohms (typical) 1 megohm
Load
Resolution
1 of 999 counts
Accuracy f
Crosstalk ohms
Time dB
6.4 ms (95% of final value) 1.5 ms (99.9% of final value)
30 ohms External
Supply
22 to 30 VDC; 80 mA max.
Channel
Isolation
500 VDC for one minute; 100 VDC continuous (channelto-channel and channel-toexternal supply)
VL (max) = .02 (RL) + 30 VL (min) = .02 (RL) + 7 where VL must never exceed 60 VDC
Module
Isolation
1500 VRMSI2400 minute
2 channels
Data Format
Hold or Return to Zero (each channel)
Throughput
Rate
Both channels each scan
Dimensions
(W x H x D)
1.63 in x 10.50 in x 5.50 in (41.40 mm x 266.70 mm x 139.70 mm)
Vtoop volts Loop Power Supply Range
Vloop-
0.2%12 counts
-66
Settling
.“L
Rmin =
(min)
.02 = current loop supply for a known loop resistance RL then:
VDC for one
Circuit Characteristics Topology Operating Register
Modes Format
Environmental J
Operating
O-999 counts linear with output current
Nos. 4010, 4012, 4014, 4016, 4018 4020, 4022, 4024 updated on
Requirements
Temperature
0 to 60°C
Humidity
0 to 95% (non-condensing)
Shock
15 G for 11 ms
Vibration
0.625 G, 50 to 500 Hz
EMI
MIL-STD-461-B
MI
Helmholtz Coil Test per TP-H ELM-000
RFI
FCC Class A
Surge withstand capability (SWC)
IEEE STD. 472-1974 and ANSI C37.90A-1974 (2500 V, 1.5 mHz for 6~s) couoled
Weight
1 lb (0.45 kg)
Termination
Screw Terminals; Strip compatible
Wire Size
Two #14 AWG (max)
Construction
Lexan
Indicator
POWER (indicates external power ON)
Fanning
NOTES: 1. Each output may be configured for current sourcing or sinking loads. The “Connections” gram shows the configuration for both. Use shielded cable for your field wiring.
dia-
2. To minimize electrical interference, ground the cable shield at either end of the cable but not at both ends. The preferred grounding is at the loop power supply. This grounding is shown in the “CURRENT SINKING” load configuration. You can also ground the cable to your B374 as shown in the “CURRENT SOURCING” load configuration. Be sure to connect the EARTH GND IN terminal to earth ground at your facility. 3. You can use either one loop power supply or the module external loops, provided it has sufficient drive capability.
power supply to power both
4. To meet the requirements of FCC Regulation 20780, Class A; use shielded, twisted-pair cable to connect the power supply to your B374. It is recommended that you ground both ends of the cable as shown in the diagram.
Page 104
I374 MINAL TRIP
FIELD DEVICE
Cil%E~T %zE CURRENT SOURCE I SHIELD (t) VD2c4 IN (-) CURRENT SINK 2 VOLTAGE HON.2 CURRENT SOURCE 2 SHIELD L--_-_-l
EARTH GND IN
FIELD DEVICE
-1
EARTH GROUND
SEE NOTES FOR ADDITIONAL INFORMATION
B374, 4-20 mA Analog Output Module Terminal Numbering and Output Connections
B374, 4-20 mA Analog Output Module Block Diagram
2 cl-i.1
C-H.2 0 000
250
500
750
999
NUMERICAL VALUE
Rear View of B374 Showing Locations of RTZ-HOLD Toggle Switches
Relationship BeWeen Current/Voltage Output and Numerical Input
Page 105
TYPICAL
USER PROGRAMS
Network No. 1 - Output a timer, counter, or sequencer value.
Network #l demonstrates how to output register values to any field device. Register 4010 accumulates time and outputs its value to the B374. Similarly, register 4012 accumulates counts and outputs its value to the second B374 channel. “XXX” may be a constant or another register. Network No. 3 - Simple Discrete-to-Analog Loop Control.
Network No. 2 - Output several constants to to an output using a rotary switch.
Network #2 shows how to output several constants to a single output register. Switches 1001 through 1006 are contacts of a rotary switch to select the appropriate constant. “XXX” may be any constant from 0 to 999. (Register 4009 should be set to zero.) How to determine... 1. The loop power supply (V~oop) knowing the load resistance (RL). 2. The load resistance (RL) knowing the loop power supply WL00p).
J
70 I lOOI
1002
“LOOP = 45V
“LOOP
(volts)
ohms
&
Network #3 demonstrates how to program discrete-to-analog loop control. It may be used for simple level, pressure, temperature, or position control. Switch 1001 controls the upper limit by forcing a zero value into output register 4010, thereby using the B374 to turn off an analog field device. Switch 1002 forces value “XXX” to output register 4010 and the field device. Similarly, switch 1003 forces value “YYY”. Generally, “YYY” is greater than “XXX”. For greater resolution, expand the program with additional inputs to register 4009.
0
I 0
NOTES:
1
I
’
1000
RL
’
’
I ’ 2000 (ohms)
’
’
I 3000
1. For a loop power supply (V~oop) of 45V, the load resistance (RL) can range between 750 and 1900 ohms. 2. For a load resistance (RL) of 1250 ohms, the loop power supply (V~oop) can range between 32 and 55 volts. 3. V~oo~ can never exceed 60 volts.
Page 106
-Ii
GOULD Electronics
Page 107
PI-J375-001
Rev I3
J375 Modbus Adapter DATA SHEET ’
The J375 Modbus”0 adapter is a communications interface for the Micro 84’m controller. FEATURES l Connects Micro 84 (slave) to Modbus communications system. l l
’
Addressing for 247 slaves on one system Mounting and packaging similar to Micro 84 l/O modules
.
No modifications required to Micro 84
.
One RS-232-C port
.
Compatible with Modicon J378 modem plus many commercial modems
.
Permits simultaneous P370 programming and Modbus communications
.
Comprehensive diagnostic capability and extensive error checking
.
Switch selectable address and system parameters
0
Supports mixed Modicon PC network
GENERAL
I .
DESCRIPTION
The J375 Modbus Adapter is a communications interface module for the Micro 84 controller. As such, it interfaces the Micro 84 to a Modbus industrial communication system. It allows the Micro 84 to be a slave PC to a Modbus master. The adapter is packaged in a modified Micro 84 l/O module case. This case is made of Lexan molded plastic with mounting brackets located on the rear of the case. This makes the J375 lightweight and easy to install. The J375 provides port connections for the following: A P370 Micro 84 Programmer, an RS-232-C device and a Micro 84 controller.
d b
In addition, the adapter is equipped with factory selectable options for 1151220 VAC power. The J375 contains its own power supply that generates all operating voltages for the adapter’s internal processor. The J375 does not require power from the Micro 84 or the data bus. The adapter provides three LED indicators.
“Run”, “Comm Active”, and “Error”. These indicators display both operating status and trouble indications. You can use these indicators for fast troubleshooting. The J375 provides dip switches at the rear of its case for address and system parameter selection. The Modbus adapter supports function codes l-8 and 15-19. In addition, the J375 allows simultaneous use of both the Modbus port and P370 port. In the event of a conflict, the adapter gives the Modbus port the higher priority, and the P370 port monitors operations only. The J375 assures maximum system integrity through parity and message redundancy checks, exception responses, loopback diagnostics and automatic retries. The J375 Modbus Adapter is compatible with all current Modbus products, which allows a mix of Gould PC’s on a Modbus network.
-!!
GOULD Electronics
Page 108
COMMUNICATION
Showing
Placement
MEDIA
Typical Modbus Network of J375 Modbus Adapter
Pl70
Within
Network
Two Possible
Mounting
Configurations
SPECIFICATIONS EIA RS-232-C Signals Supported 1. Transmitted Data (TXD). an output from the J375 2. Received Data (RXD), an input to the J375 3. Request to Send (RTS), an output from the J375 4. Clear to Send (CTS), an input to the J375 5. Data Set Ready (DSR), an input to the J375 6. Data Terminal Ready (DTR), an output from the J375
Functions
Set Single Register x
Read Exception Status
X
0
Loopback
X
1
Initiate Comm Restart
X
2
Return Diagnostic Register
X
4
Force Listen Only Mode
X
10
19,200
Transmission Parity Option mode, stop bits, and parity supported Even Parity
,L
Odd Parity \
No. of Stop Bits
1
2
1
2
1
2
ASCII
X
X
X
X
NS
X
RTU
X
NS
X
NS
X
NS
Sub. Functions
Description
Supported
Read Output Status
X
Read Input Status
X
Read Output Register Read Input Register
X X
Force Single Coil
X
Environment Ambient Temperature Operating
Not Supported
Fetch Event Counter
X X
13
Program (18413641564 PC’s)
X
14
Poll (18413641584 PC’S)
X
15
Force Multiple Coils
X
16
Set MultiDIe Registers
X
I?
Report Slave ID
X
18
Program Commands (Micro 64 PC) (Gould Modicon (Proprietary Command)
X
19’
Reset Link Command
X
F ‘ unction Code 19 is a new function code. This code, via the Modbus master software, changes the values of the system parameters set by the dip switches.
O’C to 60°C - 40°C to + 85OC
Hum.idity
O-95% (non-condensing)
X
Fetch Communications Event Log
Dimensions (W x H x D)
Storage
X
11
J
X = Supported NS = Not Supported
Program (484 PC only) Poll (484 PC only)
12 by J375
No Parity
Not Suppofled Supported
6
9
9,600
300 600
Descrlstlon
7
4,800 l!iD .-_
Function Codes
Sub-
Codes
8
Modbus Compatibility Baud Rate supported by J375 75 1,200 110 2.4or-I _, .__ 134.5
Function
Weight
1.63 in x 10.50 in x 5.50 in (41.40 mm x 266.70 mm x 139.70 mm) 2 Ibs, 2.5 oz (0.978 kg)
NOTES 1. Install as the last module in the l/O structure, if J378 modem not used.
2. Install anywhere wlthin the range of the Micro 84 cable (cable is 6 ft. long and interchangeable with P370 cable).
iii
GOULD Electronics
Page 109
J
PI-6375-001
B375001
Rev B
4-20 mA Analog Input Module DATA SHEET
The B375001, 4-20 mA Analog Input Module converts two 4-20 mA, or two l-5 VDC analog signals, or one of each to numerical values that range from 0 to 999 and applies these values to the Micro 84’” controller. FEATURES Two isolated channels
Both channels compatible Differential
4-20 mA and l-5 VDC inputs
High accuracy IO-bit resolution Self-contained power supply
Optional Fanning Strip permits module removal without disturbing field wiring Designed for harsh industrial environments UL listed
GENERAL
DESCRIPTION
The B375001 4-20 mA Analog Input is an input module for the Micro 84 controller. It converts two 4-20 mA, or two l-5 VDC analog signals, or one of each to numerical values that range from 0 to 999. These values are directly proportional to the input. For example, if the input current or voltage increases 10 percent, the numerical output also increases 10 percent. The Analog Input Module transfers these numerical values to input registers 3001 through 3004. Once in the registers, these values can be used to control timers, counters, sequencers; or it can be manipulated by arithmetic functions. Typically, the B375 is used in data acquisition and set point applications. The varying current/voltage, which are inputs to the 8375, represent parameters such as pressure, level, temperature, humidity, weight and position. These inputs come from transmitters or transducers that may be located several hundred feet from the Input Module. You simply connect these inputs to a front-mounted, screw terminal strip. This strip is compatible with an optional Fanning Strip (P/N 0212-012), which allows quick module replacement without disturbing field wiring. To simplify installation, the terminals on the strip are clearly marked so that you can connect either the 4-20 mA current loop or the varying d-c voltage (1-5 V) operation to each channel. (The voltage input is actually a differential input to achieve high accuracy and significant noise immunity.) Moreover, you can make the connections without adding more electronic components. To further simplify installation, the B375 is factory configured in the current loop mode using shorting bar between terminals 1 and 2 and 7 and 8, as shown on the terminal iii
GOULD Electronics
Page 110
numbering and connections diagram. For voltage operation, simply remove this shorting bar. Besides the terminal strip, an OUT OF RANGE diagnostic indicator for troubleshooting is also located on the front of the B375 module. It flashes whenever the input is out of its prescribed range (4 to 20 mA or 1 to 5 V). This indicator will also show that one of the input wires is either shorted to ground or open. Both channel 1 and channel 2 inputs are isolated from each other. In addition, the inputs are isolated from all I/O modules connected to the Micro 84 and from the Micro 84 controller itself. The 8375 is easy to install. First it is housed in a light-weight, shielded, durable Lexan case. It contains mounting brackets at the rear of the case which simplify installation. Next, it can be mounted anywhere in the l/O structure. Connectors located on the left- and right-rear sides of the case plug into similar connectors on adjacent modules. This plugging action automatically connects the Analog Input Module to the data bus of the Micro 84. If the B375 is the rightmost module in the l/O structure, you plug a termination connector into the connector located on the right-rear side. This termination connector is shipped with the Micro 84 controller. To minimize installation costs, the Micro 84 provides the B375 with all operating voltages, thus eliminating the need for a separate power supply. The B375 meets the stringent requirements of both IEEE and ANSI standards for radiated surge withstand capability (SWC). The B375 also withstands the severe voltage transients, electromagnetic interference, and magnetic fields commonly encountered in an industrial environment.
SPECIFICATIONS Electrical Characteristics voltage mode
1 Megohm, differential 0.5 megohm each input to shield
Input Range
4-20 mA or l-5 VDC
Resolution current mode
1 of 999 counts 16 PA per count
Input Protection
240 VRMS voltage
4 mV per count
Channel
Isolation
20 V/-9.5 V (with respect to module shield terminal)
Module
Isolation
1500 VRMS for one minute mode
+ 0.1 %/I count @ 25OC f 0.3%/3 counts @ O-60 OC* *(You can recalibrate to + 0.15% at a particular temperature betwen 0-6OOC.) Accuracy
Linearity
0.1% of full scale
Input Impedance current mode
250 ohms
Common Mode Rejection
- 86 dB @ 50/60 Hz
Input Filter
-3 dB down @ 18 Hz; rolloff 20 dB per decade
2 channels
Data Format
Independently selectable current or voltage
0 to 999 counts to inputs
Throughput
Circuit Characteristics Topology Operating
Register
Modes
Format
Nos. 3001 & 3002 or Nos. 3003 & 3004
Rate linear
1.25 samples per second (each channel)