Page 101

PI-B374-001

B374-001

Rev B

I 4-20 mA, Analog Output Module

DATA SHEET ’

The B374-001, 4-20 mA Analog Output Module receives numerical values that range from 0 to 999 from the Micro 84’” Controller and converts them into two 4-20 mA output currents.

FEATURES . Two isolated .

Popular 4-20 mA current outputs

.

Current sink or source capability

.

10 bit resolution

.

Voltage

.

High accuracy

.

“Hold last value” user selectable

.

Optional fanning strip permits module removal without disturbing field wiring

.

Designed for harsh industrial environments

.

UL listed

GENERAL

J channels monitor outputs and speed or “reset to zero”

DESCRIPTION

The B374-001 4-20 mA Analog Output is a dual channel output module for the Micro 84 Controller. It converts numerical values that range from 0 to 999 to an output current. This current ranges from 4 mA to 20 mA and is proportional to the input. For example, if the numerical input increases 10 percent, the output current also increases 10 percent. The 8374 is used to interface output registers with any 4-20 mA analog field device. Typical registers are timers, counters and sequencers. Typical analog field devices are valves, recorders, I/P converters, indicators, and servo controllers. You can connect these field devices to both a power supply and the B374 without using additional components. Field devices can be located several hundred feet from the output module.

J

Specifically, the B374 Analog Output module interfaces field devices with the following output registers: 4010, 4012, 4014, and 4016 of the 1K Micro 84, and 4010, 4012, 4014, 4016, 4018, 4020, 4022, and 4024 of the 2K Micro 84. The 1K Micro 84 supports a maximum of two B374’s, and the 2K Micro 84 supports a maximum of four B374’s.

Whichever Micro 84 you use, it is important that you understand the addressing technique used by the controller and its register output modules. In addition to the B374, the controller can use other modules such as the B370 BCD Register Output Module. Either of these modules can be the first register output module. Whichever you use, the first module addresses module output registers 4010 and 4012. The second module, regardless of whether it is a B370 or a B374, addresses registers 4014 and 4016. The third and fourth modules, if used, address registers 4018 through 4024 in a similar manner. The B374 Analog Output Module features two modes used with the Micro 84’s standby operation. (Standby means that the Micro 84 is powered up but not scanning.) These two modes are “hold last output” (HOLD) or “return to zero” (RTZ). HOLD retains the value of the output current at the time the Micro 84 switches to standby. RTZ switches the output current to zero, which is equivalent to an open circuit, whenever the Micro 84 stops scanning. Scanning of the Micro 84 can be stopped manually from

-ii

GOULD

Page 102

the programming panel, or by a program pack, or by the internal diagnostics of the controller. The RTZ and HOLD modes permit safer operation by allowing you to select the output condition best suited by your application, whenever the Micro 84 enters standby. The HOLD or RTZ mode is switch selectable. The toggle switches for selecting the HOLD and RTZ modes are located on the rear of the B374 housing, (see the last page of this data sheet for the location of these switches.) Switch 1 controls channel 1 and switch 2 controls channel 2. Switches 3 and 4 are not used. Set each switch either “up” for RTZ or “down” for HOLD before installing the B374. The 8374 Analog Output Module is easy to install. It is housed in a lightweight, shielded, durable, dripproof Lexan case. It contains mounting brackets which simplify installation. It can be mounted anywhere in the l/O structure. Connectors located on the left- and right-rear sides of the case plug into similar connectors on adjacent modules. This plugging action automatically connects the B374 to the data bus of the Micro 84 Controller. If the B374 is the right-most module in the l/O structure, plug a termination connector into the connector on the right-rear side. This termination connector is supplied with the Micro 84 controller. Field wiring is also easy to install. Connect field wiring to front-mounted, screw terminal strip. It is recommended that you use shielded, twisted-pair cable with insulating jacket to minimize radiated interference. The terminal strip is compatible with an optional Fanning Strip (P/N 0212-012), which allows quick module replacement without disturbing field wiring. All terminals are clearly marked for their intended function. The B374 requires an external power supply for its operating voltages. This same power supply can also be used to power one or both current loops. Besides the terminal strip, a POWER indicator is also located on the front of the B374 module as a troubleshooting aid. This green indicator is on when the external power supply is connected to the module. When the POWER indicator is off, it shows that the module is not receiving its operating voltages and, thus, will not operate. The screw terminal strip provides terminals that allow you to use a voltmeter to monitor the output current. Just connect a high impedance voltmeter between the VOLTAGE MON. (1 or 2) and CURRENT SOURCE (1 or 2) as shown in the “Terminal Numbering and Output Connections” diagram. The voltage will range from + 1 to +5 VDC. It is proportional to the output current. Both channel 1 and channel 2 outputs are isolated from each other and from all l/O modules connected to the Micro 84. In addition, the channels are isolated from the Micro 84 controller itself. The B374 meets the stringent requirements of both IEEE and ANSI standards for surge withstand capability (SWC). The module has been designed to meet the requirements of both UL and CSA standards. The B374 also withstands the severe voltage transients, electromagnetic interference, and magnetic fields commonly encountered in an industrial environment.

Page 103

SPECIFICATIONS Electrical

Characteristics

Output Current Range

Monitor

Voltage

Range

4-20 mA (0 mA when Micro 84 in standby and B374 in RTZ mode) l-5 VDC

Loop Power Supply

60 VDC (max)

Over Voltage

240 VRMS

Protection

Load Resistance

Range Rmax

=

Vloopnr,

7

Voltage Monitor Output Impedance Voltage

Monitor

220 ohms (typical) 1 megohm

Load

Resolution

1 of 999 counts

Accuracy f

Crosstalk ohms

Time dB

6.4 ms (95% of final value) 1.5 ms (99.9% of final value)

30 ohms External

Supply

22 to 30 VDC; 80 mA max.

Channel

Isolation

500 VDC for one minute; 100 VDC continuous (channelto-channel and channel-toexternal supply)

VL (max) = .02 (RL) + 30 VL (min) = .02 (RL) + 7 where VL must never exceed 60 VDC

Module

Isolation

1500 VRMSI2400 minute

2 channels

Data Format

Hold or Return to Zero (each channel)

Throughput

Rate

Both channels each scan

Dimensions

(W x H x D)

1.63 in x 10.50 in x 5.50 in (41.40 mm x 266.70 mm x 139.70 mm)

Vtoop volts Loop Power Supply Range

Vloop-

0.2%12 counts

-66

Settling

.“L

Rmin =

(min)

.02 = current loop supply for a known loop resistance RL then:

VDC for one

Circuit Characteristics Topology Operating Register

Modes Format

Environmental J

Operating

O-999 counts linear with output current

Nos. 4010, 4012, 4014, 4016, 4018 4020, 4022, 4024 updated on

Requirements

Temperature

0 to 60°C

Humidity

0 to 95% (non-condensing)

Shock

15 G for 11 ms

Vibration

0.625 G, 50 to 500 Hz

EMI

MIL-STD-461-B

MI

Helmholtz Coil Test per TP-H ELM-000

RFI

FCC Class A

Surge withstand capability (SWC)

IEEE STD. 472-1974 and ANSI C37.90A-1974 (2500 V, 1.5 mHz for 6~s) couoled

Weight

1 lb (0.45 kg)

Termination

Screw Terminals; Strip compatible

Wire Size

Two #14 AWG (max)

Construction

Lexan

Indicator

POWER (indicates external power ON)

Fanning

NOTES: 1. Each output may be configured for current sourcing or sinking loads. The “Connections” gram shows the configuration for both. Use shielded cable for your field wiring.

dia-

2. To minimize electrical interference, ground the cable shield at either end of the cable but not at both ends. The preferred grounding is at the loop power supply. This grounding is shown in the “CURRENT SINKING” load configuration. You can also ground the cable to your B374 as shown in the “CURRENT SOURCING” load configuration. Be sure to connect the EARTH GND IN terminal to earth ground at your facility. 3. You can use either one loop power supply or the module external loops, provided it has sufficient drive capability.

power supply to power both

4. To meet the requirements of FCC Regulation 20780, Class A; use shielded, twisted-pair cable to connect the power supply to your B374. It is recommended that you ground both ends of the cable as shown in the diagram.

Page 104

I374 MINAL TRIP

FIELD DEVICE

Cil%E~T %zE CURRENT SOURCE I SHIELD (t) VD2c4 IN (-) CURRENT SINK 2 VOLTAGE HON.2 CURRENT SOURCE 2 SHIELD L--_-_-l

EARTH GND IN

FIELD DEVICE

-1

EARTH GROUND

SEE NOTES FOR ADDITIONAL INFORMATION

B374, 4-20 mA Analog Output Module Terminal Numbering and Output Connections

B374, 4-20 mA Analog Output Module Block Diagram

2 cl-i.1

C-H.2 0 000

250

500

750

999

NUMERICAL VALUE

Rear View of B374 Showing Locations of RTZ-HOLD Toggle Switches

Relationship BeWeen Current/Voltage Output and Numerical Input

Page 105

TYPICAL

USER PROGRAMS

Network No. 1 - Output a timer, counter, or sequencer value.

Network #l demonstrates how to output register values to any field device. Register 4010 accumulates time and outputs its value to the B374. Similarly, register 4012 accumulates counts and outputs its value to the second B374 channel. “XXX” may be a constant or another register. Network No. 3 - Simple Discrete-to-Analog Loop Control.

Network No. 2 - Output several constants to to an output using a rotary switch.

Network #2 shows how to output several constants to a single output register. Switches 1001 through 1006 are contacts of a rotary switch to select the appropriate constant. “XXX” may be any constant from 0 to 999. (Register 4009 should be set to zero.) How to determine... 1. The loop power supply (V~oop) knowing the load resistance (RL). 2. The load resistance (RL) knowing the loop power supply WL00p).

J

70 I lOOI

1002

“LOOP = 45V

“LOOP

(volts)

ohms

&

Network #3 demonstrates how to program discrete-to-analog loop control. It may be used for simple level, pressure, temperature, or position control. Switch 1001 controls the upper limit by forcing a zero value into output register 4010, thereby using the B374 to turn off an analog field device. Switch 1002 forces value “XXX” to output register 4010 and the field device. Similarly, switch 1003 forces value “YYY”. Generally, “YYY” is greater than “XXX”. For greater resolution, expand the program with additional inputs to register 4009.

0

I 0

NOTES:

1

I

’

1000

RL

’

’

I ’ 2000 (ohms)

’

’

I 3000

1. For a loop power supply (V~oop) of 45V, the load resistance (RL) can range between 750 and 1900 ohms. 2. For a load resistance (RL) of 1250 ohms, the loop power supply (V~oop) can range between 32 and 55 volts. 3. V~oo~ can never exceed 60 volts.

Page 106

-Ii

GOULD Electronics

Page 107

PI-J375-001

Rev I3

J375 Modbus Adapter DATA SHEET ’

The J375 Modbus”0 adapter is a communications interface for the Micro 84’m controller. FEATURES l Connects Micro 84 (slave) to Modbus communications system. l l

’

Addressing for 247 slaves on one system Mounting and packaging similar to Micro 84 l/O modules

.

No modifications required to Micro 84

.

One RS-232-C port

.

Compatible with Modicon J378 modem plus many commercial modems

.

Permits simultaneous P370 programming and Modbus communications

.

Comprehensive diagnostic capability and extensive error checking

.

Switch selectable address and system parameters

0

Supports mixed Modicon PC network

GENERAL

I .

DESCRIPTION

The J375 Modbus Adapter is a communications interface module for the Micro 84 controller. As such, it interfaces the Micro 84 to a Modbus industrial communication system. It allows the Micro 84 to be a slave PC to a Modbus master. The adapter is packaged in a modified Micro 84 l/O module case. This case is made of Lexan molded plastic with mounting brackets located on the rear of the case. This makes the J375 lightweight and easy to install. The J375 provides port connections for the following: A P370 Micro 84 Programmer, an RS-232-C device and a Micro 84 controller.

d b

In addition, the adapter is equipped with factory selectable options for 1151220 VAC power. The J375 contains its own power supply that generates all operating voltages for the adapter’s internal processor. The J375 does not require power from the Micro 84 or the data bus. The adapter provides three LED indicators.

“Run”, “Comm Active”, and “Error”. These indicators display both operating status and trouble indications. You can use these indicators for fast troubleshooting. The J375 provides dip switches at the rear of its case for address and system parameter selection. The Modbus adapter supports function codes l-8 and 15-19. In addition, the J375 allows simultaneous use of both the Modbus port and P370 port. In the event of a conflict, the adapter gives the Modbus port the higher priority, and the P370 port monitors operations only. The J375 assures maximum system integrity through parity and message redundancy checks, exception responses, loopback diagnostics and automatic retries. The J375 Modbus Adapter is compatible with all current Modbus products, which allows a mix of Gould PC’s on a Modbus network.

-!!

GOULD Electronics

Page 108

COMMUNICATION

Showing

Placement

MEDIA

Typical Modbus Network of J375 Modbus Adapter

Pl70

Within

Network

Two Possible

Mounting

Configurations

SPECIFICATIONS EIA RS-232-C Signals Supported 1. Transmitted Data (TXD). an output from the J375 2. Received Data (RXD), an input to the J375 3. Request to Send (RTS), an output from the J375 4. Clear to Send (CTS), an input to the J375 5. Data Set Ready (DSR), an input to the J375 6. Data Terminal Ready (DTR), an output from the J375

Functions

Set Single Register x

Read Exception Status

X

0

Loopback

X

1

Initiate Comm Restart

X

2

Return Diagnostic Register

X

4

Force Listen Only Mode

X

10

19,200

Transmission Parity Option mode, stop bits, and parity supported Even Parity

,L

Odd Parity \

No. of Stop Bits

1

2

1

2

1

2

ASCII

X

X

X

X

NS

X

RTU

X

NS

X

NS

X

NS

Sub. Functions

Description

Supported

Read Output Status

X

Read Input Status

X

Read Output Register Read Input Register

X X

Force Single Coil

X

Environment Ambient Temperature Operating

Not Supported

Fetch Event Counter

X X

13

Program (18413641564 PC’s)

X

14

Poll (18413641584 PC’S)

X

15

Force Multiple Coils

X

16

Set MultiDIe Registers

X

I?

Report Slave ID

X

18

Program Commands (Micro 64 PC) (Gould Modicon (Proprietary Command)

X

19’

Reset Link Command

X

F ‘ unction Code 19 is a new function code. This code, via the Modbus master software, changes the values of the system parameters set by the dip switches.

O’C to 60°C - 40°C to + 85OC

Hum.idity

O-95% (non-condensing)

X

Fetch Communications Event Log

Dimensions (W x H x D)

Storage

X

11

J

X = Supported NS = Not Supported

Program (484 PC only) Poll (484 PC only)

12 by J375

No Parity

Not Suppofled Supported

6

9

9,600

300 600

Descrlstlon

7

4,800 l!iD .-_

Function Codes

Sub-

Codes

8

Modbus Compatibility Baud Rate supported by J375 75 1,200 110 2.4or-I _, .__ 134.5

Function

Weight

1.63 in x 10.50 in x 5.50 in (41.40 mm x 266.70 mm x 139.70 mm) 2 Ibs, 2.5 oz (0.978 kg)

NOTES 1. Install as the last module in the l/O structure, if J378 modem not used.

2. Install anywhere wlthin the range of the Micro 84 cable (cable is 6 ft. long and interchangeable with P370 cable).

iii

GOULD Electronics

Page 109

J

PI-6375-001

B375001

Rev B

4-20 mA Analog Input Module DATA SHEET

The B375001, 4-20 mA Analog Input Module converts two 4-20 mA, or two l-5 VDC analog signals, or one of each to numerical values that range from 0 to 999 and applies these values to the Micro 84’” controller. FEATURES Two isolated channels

Both channels compatible Differential

4-20 mA and l-5 VDC inputs

High accuracy IO-bit resolution Self-contained power supply

Optional Fanning Strip permits module removal without disturbing field wiring Designed for harsh industrial environments UL listed

GENERAL

DESCRIPTION

The B375001 4-20 mA Analog Input is an input module for the Micro 84 controller. It converts two 4-20 mA, or two l-5 VDC analog signals, or one of each to numerical values that range from 0 to 999. These values are directly proportional to the input. For example, if the input current or voltage increases 10 percent, the numerical output also increases 10 percent. The Analog Input Module transfers these numerical values to input registers 3001 through 3004. Once in the registers, these values can be used to control timers, counters, sequencers; or it can be manipulated by arithmetic functions. Typically, the B375 is used in data acquisition and set point applications. The varying current/voltage, which are inputs to the 8375, represent parameters such as pressure, level, temperature, humidity, weight and position. These inputs come from transmitters or transducers that may be located several hundred feet from the Input Module. You simply connect these inputs to a front-mounted, screw terminal strip. This strip is compatible with an optional Fanning Strip (P/N 0212-012), which allows quick module replacement without disturbing field wiring. To simplify installation, the terminals on the strip are clearly marked so that you can connect either the 4-20 mA current loop or the varying d-c voltage (1-5 V) operation to each channel. (The voltage input is actually a differential input to achieve high accuracy and significant noise immunity.) Moreover, you can make the connections without adding more electronic components. To further simplify installation, the B375 is factory configured in the current loop mode using shorting bar between terminals 1 and 2 and 7 and 8, as shown on the terminal iii

GOULD Electronics

Page 110

numbering and connections diagram. For voltage operation, simply remove this shorting bar. Besides the terminal strip, an OUT OF RANGE diagnostic indicator for troubleshooting is also located on the front of the B375 module. It flashes whenever the input is out of its prescribed range (4 to 20 mA or 1 to 5 V). This indicator will also show that one of the input wires is either shorted to ground or open. Both channel 1 and channel 2 inputs are isolated from each other. In addition, the inputs are isolated from all I/O modules connected to the Micro 84 and from the Micro 84 controller itself. The 8375 is easy to install. First it is housed in a light-weight, shielded, durable Lexan case. It contains mounting brackets at the rear of the case which simplify installation. Next, it can be mounted anywhere in the l/O structure. Connectors located on the left- and right-rear sides of the case plug into similar connectors on adjacent modules. This plugging action automatically connects the Analog Input Module to the data bus of the Micro 84. If the B375 is the rightmost module in the l/O structure, you plug a termination connector into the connector located on the right-rear side. This termination connector is shipped with the Micro 84 controller. To minimize installation costs, the Micro 84 provides the B375 with all operating voltages, thus eliminating the need for a separate power supply. The B375 meets the stringent requirements of both IEEE and ANSI standards for radiated surge withstand capability (SWC). The B375 also withstands the severe voltage transients, electromagnetic interference, and magnetic fields commonly encountered in an industrial environment.

SPECIFICATIONS Electrical Characteristics voltage mode

1 Megohm, differential 0.5 megohm each input to shield

Input Range

4-20 mA or l-5 VDC

Resolution current mode

1 of 999 counts 16 PA per count

Input Protection

240 VRMS voltage

4 mV per count

Channel

Isolation

20 V/-9.5 V (with respect to module shield terminal)

Module

Isolation

1500 VRMS for one minute mode

+ 0.1 %/I count @ 25OC f 0.3%/3 counts @ O-60 OC* *(You can recalibrate to + 0.15% at a particular temperature betwen 0-6OOC.) Accuracy

Linearity

0.1% of full scale

Input Impedance current mode

250 ohms

Common Mode Rejection

- 86 dB @ 50/60 Hz

Input Filter

-3 dB down @ 18 Hz; rolloff 20 dB per decade

2 channels

Data Format

Independently selectable current or voltage

0 to 999 counts to inputs

Throughput

Circuit Characteristics Topology Operating

Register

Modes

Format

Nos. 3001 & 3002 or Nos. 3003 & 3004

Rate linear

1.25 samples per second (each channel)