Page 31
Onboard Programmable Inputs and Outputs
Master Trigger: The “MASTER TRIG” input on this connector has the same circuit design as trigger inputs on the “TRIGGERS/OUTPUTS” connectors.
For easy screw-terminal connections, use the “VM25” screw-terminal converter (sold separately, includes 2-foot cable). Connection instructions are provided on page 41.
PIN OUTS & SPECIFICATIONS (25-pin “TRIGGERS/OUTPUTS” connectors) Pin #* 25 23 21 19 17 15 13 11 9 7 5 3 1
In/Out ----IN IN IN IN IN IN IN IN OUT OUT OUT OUT
Description (axes 1-4) Description (axes 5-8) Reserved Reserved Trigger input 1 (TRIG-1A) Trigger input 9 (TRIG-5A) Trigger input 2 (TRIG-1B) Trigger input 10 (TRIG-5B) Trigger input 3 (TRIG-2A) Trigger input 11 (TRIG-6A) Trigger input 4 (TRIG-2B) Trigger input 12 (TRIG-6B) Trigger input 5 (TRIG-3A) Trigger input 13 (TRIG-7A) Trigger input 6 (TRIG-3B) Trigger input 14 (TRIG-7B) Trigger input 7 (TRIG-4A) Trigger input 15 (TRIG-8A) Trigger input 8 (TRIG-4B) Trigger input 16 (TRIG-8B) GP Output 1 GP Output 5 GP Output 2 GP Output 6 GP Output 3 GP Output 7 GP Output 4 GP Output 8 (GP=general purpose)
* All even number pins are connected to isolated logic ground. ** The VINref, TRIG-P, and GND terminals are located on the screw-terminal connector on top of the 6K chassis.
Chapter 1. Installation
25
Specs for Trigger Inputs • Voltage range is 0-24 VDC. • Trigger input switching levels: Low ≤ 1/3 VINref voltage, High ≥ 2/3 VINref voltage (factory default VINref voltage is +24 VDC, but you can connect a different voltage to the VINref terminal**). To make all limit inputs sinking inputs, connect the TRIG-P terminal** to the GND terminal**. • Status: Check with TIN or IN. • Programmable functions with the INFNC command. Can also be used as a “Trigger Interrupt” input (INFNCi-H) for position capture and registration. • Active level is set with the INLVL command. Default is active low (see n.o. switch in diagram above).
Specs for GP Outputs • Open collector output; will sink up to 300 mA. • Status: Check with TOUT or OUT. • Programmable functions with the OUTFNC command. Can also be used as an “Output on Position” output (OUTFNCi-H). • Active level is set with the OUTLVL command. Default is active low. • If the outputs are driving inductive loads, connect the OUT DIODE terminal to 24 VDC.
Page 32
Trigger Input Connections
If you are connecting to a combination of sinking and sourcing output, connect the VINref terminal to the voltage supply (factory default is internally connected to 24 VDC) to accommodate the sinking outputs. Then for each input connected to a sourcing output, wire an external resistor between the trigger input and GND. The resistor provides a path for current to flow from the device when the output is active. Programming Tip: If connecting to sinking output, set the trigger’s INLVL setting to active low (INLVL0). If connecting to a sourcing output, set the trigger’s INLVL setting to active high (INLVL1). Thus, when the output is active, the TIN/IN status will report a “1” (indicates that the input is active), regardless of the type of output that is connected.
26
6K Hardware Installation Guide
Page 33
Programmable Output Connections
Programming Tip: If connecting to an active-high sinking input, set the output’s OUTLVL setting to active high (OUTLVL1). If connecting to an active-low sourcing input, set the output’s OUTLVL setting to active low (OUTLVL0). Thus, when the 6K’s output is activated, current will flow through the attached input and the TOUT/OUT status will report a “1” (indicates the output is active), regardless of the type of input that is connected.
Chapter 1. Installation
27
Page 34
Communication Interface Communication Interface Options
RS-232 (“COM1” port) Set up for use as the primary RS-232 port; configurable for RP240. Ethernet Port
RS-232/485 (“COM2” port). • Set up for use with an RP240; configurable for RS-485 or as the primary RS-232 port.
Using Multiple Ports You can communicate to either the Ethernet port or the RS-232 port (COM1) at any given time; the port that you communicate to first is the only one that is recognized until you cycle power. You can communicate to the Ethernet port or the RS-232 port (COM1) while the 6K is also communicating with an RP240 via the RS-232/485 port (COM2).
28
6K Hardware Installation Guide
Page 35
RS-232 Communication RS-232 Connector
Pin Outs for RS-232 Communication Pin 2 3 5
Description Rx (receive). Connect to Tx on your computer. Tx (transmit). Connect to Rx on your computer. GND (isolate ground). Connect to GND on your computer.
Maximum RS-232 cable length is 50 feet (15.25 meters). The 6K, by default, communicates at 9600 baud. To change this setting, use the BAUD command. To establish unique addresses for daisy-chained units, use the ADDR command.
Ethernet Communication NOTES • •
Status LEDs: Green LED is on when the Ethernet physical connection is OK. Yellow LED is on when the 6K is transmitting over the Ethernet interface. Connect to a standard 10Mbps Ethernet card. IP address default is 192.168.10.30. To change the IP address, use the NTADDR command. To ascertain the Ethernet address, use the TNTMAC command.
Direct PC to 6K Connection
Network Hub Connection
NOTE: Use a “Crossover” Ethernet (10Base-T) cable.
NOTE: Use a “Straight-Through” Ethernet (10Base-T) cable.
A 10-foot cable is provided in the ship kit (p/n 71-017635-01).
Chapter 1. Installation
29
Page 36
RS-485 Communication RS-232 Connector
Pin Outs for RS-485 Communication Pin 1 4 6 7 8 • • • • •
4-Wire Connections (plus ground):
30
6K Hardware Installation Guide
Description Rx + (also called RD B) Tx + (also called TD B) GND (isolate ground) Rx – (also called RD A) Tx – (also called TD A) Maximum RS-485 cable length is 4000 feet (1220 meters). To establish unique addresses for multi-drop units, use the ADDR command. Use termination resistors at both ends of the multi-drop. Keep stubs as short as possible. Recommended cables: 2-wire: Belden 9841 4-wire: Belden 9842 Refer to the diagrams below (or page 5) for necessary DIP switch settings for 2-wire and 4-wire configuration.
Page 37
2-Wire Connections (plus ground):
Master Unit Unit #1 Van Ground RS-232/485 connector | Txt i Tx- fd 1202 t | $ . Rxt Unit #2 BS 4 Tex = 1200 Unit #3 Unit #31 120 ‘ } Pin 4 (Rx*) Imre (pint) + aos Pin 4 ™9 teing i] OmmS Pin 6 (GND’ 1202 Om + aM me N Taz O Tam | seins Z 6812
The DIP switch shown above is configured for RS-485 2-wire.
DIP switches 1-4 select internal resistor values (ON selects the resistor). Use these resistors only for the last unit (or for a single unit).
Refer to page 5 for instructions on how to access and set the switches.
Chapter 1. Installation 31
Page 38
RP240 Remote Operator Panel RS-232 Connector
NOTE for RS-485 Users If you configured the “RS-232/485” connector for RS-485 communication (see page 5), you must connect the RP240 to the “RS-232” connector. NOTE: You will have to issue these commands to configure the “RS-232” connector for use with an RP240: PORT1 Select “RS-232” (COM1) as the affected DRPCHK1 On power up, check for RP240 on COM1.
NOTE: Refer to the Model RP240 User Guide for RP240 specifications and mounting instructions.
Expansion I/O The 6K product allows you to expand your system I/O by connecting up to eight EVM32 expansion I/O bricks. EVM32 bricks are sold separately from the 6K controller. Each I/O brick can hold from 1 to 4 of these I/O SIM modules in any combination: • • •
Digital Inputs SIM (8 inputs) Digital Outputs SIM (8 outputs) Analog Inputs SIM (8 inputs)
For information about connecting the expansion I/O, see Appendix B, page 45.
32
6K Hardware Installation Guide
Page 39
24 VDC Power Input
The “PS-60W” is an optional power supply which can be ordered separately. It provides 60 Watts of power (2.5A @ 25VDC).
Guide to Power Requirements 6K2 or 6K4...............................................................................24 Watts (1A @ 24 VDC) 6K6 or 6K8...............................................................................36 Watts (1.5A @ 24 VDC) For each encoder.....................................................................Add 1.5 Watts For each output........................................................................Add ≤ 7.5 Watts (up to 300 mA/output) For example, a 6K4 with 4 encoders connected and 4 digital outputs (300 mA @ 224 VDC) requires 60 Watts of power.
Chapter 1. Installation
33
Page 40
Testing the Installation Warning, This test procedure allows you to control your system I/O and produce motion. Therefore, you should make sure that exercising the I/O will not damage equipment or injure personnel.
Test Setup 1. 2. 3.
If you haven’t already done so, made the necessary communication connections (see page 28). Install Motion Planner (CD is provided in your ship). Launch Motion Planner and click on the “Terminal” window tab to view the terminal emulator. You now have live communication with the 6K product. Connections Test Procedure Response Format (left to right) TLIM response: NOTE: If you are not using end-of-travel limits, issue the Disable Limits (@LHØ) End-of-travel command and ignore the first two bits in each response field. bit 1 = Axis 1 POS limit and bit 2 = Axis 1 NEG limit 1. Enable the hardware end-of-travel limits with the @LH3 command. Home Limits bit 3 = Axis 1 HOM limit 2. Close the end-of-travel switches and open the home switches. bit 4 = Axis 2 POS limit 3. Enter the TLIM command. The response should be *TLIM11Ø_11Ø_11Ø … bit 5 = Axis 2 NEG limit 4. Open the end-of-travel switches and close the home switches. bit 6 = Axis 2 HOM limit 5. Enter the TLIM command. The response should be *TLIMØØ1_ØØ1_ØØ1 … and so on (3 inputs/axis) 6. Close the end-of-travel switches and open the home. 7. Enter the TLIM command. The response should be *TLIM11Ø_11Ø_11Ø … “POS” means positive travel. “NEG” means negative travel. “HOM” means home. TPE response (encoder counts): 1. Enter these commands, (preset the RETURN key after each command): ENCCNT1, Encoder L, TPE, T.3, and then LN. This will begin a continuous display of all encoder ±encoder1, ±encoder1, … (not coupled to positions. Press the RETURN key to move the display to the next line and save the current value. the load or Direction of rotation: 2. Manually rotate the encoder shaft and verify that the position changes as you rotate motor) the encoder shaft. If you connected the encoder as instructed earlier in this chapter, moving the shaft clockwise should increase the position reading. If the reading does not change, or if the direction is reversed, check the connections. If the direction is reversed, swap the A+ and A- connections. 3. When finished, enter the ^K (ctrl-K) command to stop the continuous report-back. Trigger Inputs
1. 2. 3. 4.
1.
Onboard Outputs
2. 3. 4. 1. 2.
RP240
3.
Open the trigger input switches or turn off the device driving the inputs. Enter the TIN command. Response should be *TINØØØØ_ØØØØ_Ø or *TINØØØØ_ØØØØ_ØØØØ_ØØØØ_Ø. Close the trigger input switches or turn on the device driving the inputs. Enter the TIN command. Response should be *TIN1111_1111_1 or *TIN1111_1111_1111_1111_1.
TIN response:
Enter the @OUT1 command to turn on (sink current on) all programmable outputs. Verify that the device(s) connected to the outputs activated properly. Enter the TOUT command. Response should be *TOUT1111 or *TOUT1111_1111. Enter the @OUTØ command to turn off all programmable outputs. Verify that the device(s) connected to the outputs de-activated properly. Enter the TOUT command. Response should be *TOUTØØØØ or *TOUTØØØØ_ØØØØ. Cycle power to the 6K. If the RP240 is connected properly, the RP240’s status LED should be green and one of the lines on the computer or terminal display should read *RP24Ø CONNECTED. If the RP240’s status LED is off, check to make sure the +5V connection is secure. If the RP240’s status LED is green, but the message on the terminal reads *NO REMOTE PANEL, the RP240 Rx and Tx lines are probably switched. Remove power and correct. Assuming you have not written a program to manipulate the RP240 display, the RP240 screen should display the following:
TOUT response:
COMPUMOTOR 6Kn CONTROLLER RUN JOG STATUS DRIVE DISPLAY Enable Input
34
1. 2. 3. 4.
Bits 1-n, from left to right, represent outputs 1-n. The 6K2 & 6K4 have 4 outputs, the 6K6 & 6K8 have 8 outputs. ASSUMPTIONS RP240 connected to the COM 2 (“RS-232/485”). COM 2 configured for RP240. To verify, type these commands: PORT2 <cr> DRPCHK<cr> The system response should report “*DRPCHK3”.
ETC
Open the enable input (ENABLE) switch. Enter the TINO command. Response should be *TINOØØØØ_ØØØØ. Close the ENABLE switch. Enter the TINO command. Response should be *TINOØØØØ_Ø1ØØ.
6K Hardware Installation Guide
Bits 1-n, from left to right, represent trigger inputs 1-n. Bit #17 represents the Master Trigger (“MASTER TRG”). The 6K2 & 6K4 have 9 inputs, the 6K6 & 6K8 have 17 inputs.
TINO response: bit 6 = Enable (ENABLE) input, all other bits are not used.