Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of 6K Series Hardware Installation Guide

Manual · Parker Compumotor

6K Series Hardware Installation Guide

Manual70 pagesPDF 3.7 MB

Hardware installation guide for the Parker 6K Series motion controllers (6K2, 6K4, 6K6, 6K8): mounting, wiring, testing and troubleshooting.

Download the PDF3.7 MB

Covers · 1 model

The models it covers

Summary

What is in it

Parker Hannifin guide to installing and troubleshooting the 6K Series motion controllers, including the 6K4 four-axis model. It lists the ship kit and accessories, general specifications, RS-485 setup, dimensions and mounting, and wiring for the enable input, servo and step-and-direction drives, encoders, limits, onboard I/O, communications, RP240 panel, expansion I/O and 24 VDC power. It ends with troubleshooting, VM25 and EVM32 expansion I/O installation, and servo tuning.

Its parts

  1. Installation
  2. Troubleshooting
  3. VM25 Installation
  4. EVM32 Installation
  5. Servo Tuning

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

Hardware installation guide for the Parker Compumotor 6K Series motion controllers: the 6K2, 6K4, 6K6 and 6K8. It covers the ship kit and accessories, specifications, RS-485 setup, wiring of drives, encoders and I/O, troubleshooting, the EVM32 expansion I/O and servo tuning.

Read for this summary: pages 1 to 5, 8 to 11, 39 and 44 to 46 of 70.

Device
6K4: four-axis motion controller; 6K4-NK is the same without the ship kit p. 9
Power
24 VDC ±10%, 2A max., depending on the I/O used p. 10
Drive command output
±10V analog (servo) or step and direction p. 10
Serial ports
RS-232 3-wire; RS-485 2- or 4-wire after DIP switch changes; 9600 baud default (1200-38400); up to 99 units daisy-chained p. 10
Ethernet
10Base-T TCP/IP, RJ-45 connector, default IP address 192.168.10.30 p. 10
Encoder inputs
Two-phase quadrature, differential or single-ended, 5VDC max., 12.0 MHz post quadrature p. 10
Limit, trigger, fault inputs
0-24 VDC, sourcing current by default, 24 VDC reference p. 10
Digital outputs
Open-collector, sink up to 300 mA p. 10
Servo update
As fast as 62.5 µs per axis p. 10
Operating temperature
32 to 122°F (0 to 50°C), 0 to 95% humidity non-condensing p. 10
Power budget
6K2 or 6K4: 24 Watts (1A @ 24 VDC), plus 1.5 Watts per encoder and up to 7.5 Watts per output p. 39
Ship kit
Guides 88-017547-01, 88-017136-01, 88-017137-01; Motion Planner CD 95-017633-01; crossover Ethernet cable 71-017635-01 p. 9
Accessories
Drive cables 71-016137-10 and 71-017003-10, VM25 screw-terminal adapter, PS-60W power supply p. 9
Expansion I/O
Up to eight EVM32 modules, each holding up to four SIM cards p. 9

What this manual walks you through

  • Following the recommended installation steps p. 8
  • Setting the internal DIP switches for RS-485 p. 11
  • Sizing the 24 VDC power supply p. 39
  • Fixing Ethernet and serial communication problems p. 44
  • Correcting reversed motor or encoder direction p. 44
  • Setting encoder resolution for Parker encoders p. 45
  • Reading the POWER and AXIS LEDs p. 46
  • Finding why motion does not occur p. 46

Good to know

  • Remove power before connecting devices or adjusting the internal DIP switches. p. 8
  • If the ENABLE input is not grounded, commanded motion will not occur. p. 10
  • Disconnect the OUT DIODE jumper when the onboard outputs do not drive inductive loads. p. 10
  • Peak encoder frequency must stay below 12.0 MHz post quadrature. p. 45
  • The Master Encoder connector cannot be used for servo feedback or stepper stall detect. p. 10

Questions this manual answers

What power supply does a Parker 6K4 need?

24 VDC ±10%. The guide budgets 24 Watts for a 6K4, plus 1.5 Watts per encoder and up to 7.5 Watts per output; the optional PS-60W gives 60 Watts. p. 10, 39

What is the default IP address of a 6K controller?

192.168.10.30. It is changed with the NTADDR command over the RS-232 port. p. 10

Why is the POWER LED red on my 6K?

A general fault or an ungrounded ENABLE input. Reset by cycling power or with the RESET command, and ground the ENABLE input. p. 46

How do I set up RS-485 on the 6K4?

The RS-232/485 connector (COM2) ships set for RS-232; RS-485 is enabled with the internal DIP switches, for 2-wire or 4-wire. p. 11

What is the 6K4-NK?

The 6K4 four-axis controller without the ship kit. p. 9

The whole text · 7 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 6051-60
  7. Pages 61 to 7061-70

The file

Revision and size

Revisionp/n 88-017547-01 B, November 2005
PublisherParker Hannifin Corporation
Pages70
PDF3.7 MB
TextText from the PDF itself; pages 1, 12, 37, 48 and 55 are scans, read by OCR, which may hold reading errors.

The first pages · 3 of 70

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 70
Page 2
Page 2of 70
Page 3
Page 3of 70