Omega PX273-050DI
The OMEGA PX273 is an all DP25B-E,* DP24-E* stainless steel wet/wet differential pressure transmitter, incorporating dual diffused resistive sensing elements with stainless steel media isolation. The unit is compatible with all media encountered in industrial applications, including freon, ammonia, treated water, and steam. The PX273 is ideal for monitoring and controlling pump differential pressure, CW/HW system differential pressure, chiller/boiler differential pressure drop, and many other industrial applications.
SPECIFICATIONS
Excitation: 24 Vdc @ 50 mA
Output: 4 to 20 mA
Accuracy: ±0.75% FS
Zero Adjustment: ±50% FS
Span Adjustment: ±25% FS
Operating Temp: -18 to 82°C
(0 to 180°F)
Compensated Temp: -18 to 65°C
(0 to 150°F)
Thermal Effects:
Zero: ±0.025% FS/°F
Span: ±0.01% FS/°F
cab-bat-acc
Cables, batteries and other accessories are sold separately unless otherwise stated.