Allen-Bradley 1771-P4
The power supply module has a green indicator light (labeled P/S ACTIVE). It indicates the operating condition of the module, and can be used for diagnosing faults. The module monitors itself for: over voltage, under voltage, over current. Any of these conditions will shut down the power supply. Following a shutdown, turn the power supply off for at least 15 seconds (-P3 and -P4) or 45 seconds (-P5, -P5E) before you turn it on again.
Module location: 2 adjacent slots in a 1771 I/O chassis
Nominal Input voltage: 120V ac
Input Voltage Range: 97 to 132V ac rms
Input Power: 57 Watts
Fuse: 1.5A 125V slow blow, Bussman MDX1.5, Littelfuse 31301.5
Category | Models |
---|---|
Cable | Allen-Bradley 1771-CP1 |
Encoder | Allen-Bradley 1771-HTE |
Power Supplies | Allen-Bradley 1771-P2, Allen-Bradley 1771-P4S, Allen-Bradley 1772-P1 |
Standard Power Supplies | Allen-Bradley 1771-P7, Allen-Bradley 1771-PA |
Teach Pendant Interface | Allen-Bradley 1771-HD |